Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance B 176 SECTOR 71 NOIDA GAUTAM BUDH NAGAR | NOIDA | GAUTAM BUDH NAGAR | UTTAR PRADESH | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹23,000
Closing Date
25 Mar 2023, 1:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE, ECWD, SAHARANPUR
EE, ECWD, SAHARANPUR
Increasing Capacity of of SS HAKIMPURA
2023_PVVNL_775933_1
T-02/ECWD/DRE/2022-23
Open Tender
Electrical Works
Lump-sum
45 days
SAHRANPUR
PLEASE REFER TENDER DOCUMENTS
2 documents required · 2 mandatory
₹5,900
EE, ECWD
₹23,000
Yes
31 Mar 2023
17 Feb 2023
25 Mar 2023
17 Feb 2023
25 Mar 2023
17 Feb 2023
17 Feb 2023 - 17 Feb 2023
Supply of following Items :- Supply for neutral link L type Galvanised Structure i) Galvanised Channel (100x50x6)mm
ii) Galvanised Angle (50x50x6)mm
2.Supply for cable support Galvanised Structure i) Galvanised Channel (100x50x6)mm
ii) Galvanised Angle (50x50x6)mm
3. Supply for copper bus bar support T-type Galvanised Structure i) Galvanised Channel (100x50x6)mm
ii) Galvanised Angle (50x50x6)mm
iii) Al. Binding wire
4. Supply of ready mixed primer & ISI mark Aluminium Paint & ISI mark synthetic enaimel green paint for painting of installed all Structure & G.I.Strip.
5. 33 KV Bus Isolator 800 Amp
6. 33 KV Fuse Set
7. 33 KV Lightening Arrestor
8. 33 KV Post Insulator
9. (a) 2x2.5 mm2 Control Cable
(b) 4x2.5 mm2 Control Cable
10. (a) Supply of Heat shrinkable Out door jointing kits suitable for 11KV, 3x300q.mm XLPE cable (Raychem / Dension or PVVNL Approved vender).
(b) Supply of Heat shrinkable indoor jointing kits suitable for 11KV, 3x300q.mm XLPE cable (Raychem / Dension or PVVNL Approved vender).
11. Supply of G.I. Strip size 50x6mm for earthing of outdoor & indoor equipment
12. Supply of copper bus bar of size (2500x50x6)mm
13. Supply for Water level earthing i) G.I. pipe size 40 mm inner dia & thickness 2mm
ii) Solid copper cone Approx 225 mm long and 750 gm in weight
iii) Copper wire 6 SWG
iv) Copper flexible earthing strip of size 50x6mm for neutral
14. Safe carriage of with loading & unloading at both ends respectively. (under jurisdiction of PVVNL) i) 33 KV VCB 800 Amp, 750 MVA with Steel Structure
(ii) Control panel I/C for 33 KV Double T/F
(iii) 33 KV C.T 400/200 1A
(iv) 11 KV 3X300 mm2 XLPE Cable
15. Miscellaneous Civil works of Increasing Capacity of 33/11 KV Substation Hakimpura Sre. from 2x5 MVA to 2x10 MVA Construction of Plinth for 33/11KV T/F of (3.46x4.46x1.0)m 0.5 m above ground level) as per details:- (a) Supply of 90 lbs rail pieces for T/F (44.64Kg/Mtrs.)
(b) Supply & Erection of 1st Class brick work for side walls size 0.23 m wide upto 0.35 m height cm C.C. ratio of 1:4 (cement & fine sand)
( c) Supply & Filling of brick ballast in plinth in ratio 1:4:8 (cement, coarse sand & brick ballast) with proper ramming. Size (3.0x4.0x0.65)m.
(d) Supply & Erection of R.C.C. work on the top of plinth in ratio 1:2:4 in (3.46x4.46)m size and 0.20m in thickness by using M.S. Tor of 12 mm dia. 12 Nos. in each direction across to each other & M.S.Channel (125x65x6mm) 52Kgs. The work also includes cutting, bending of M.S. Tor etc.
( e) Supply & Erection of Quantity of M.S. Tor of size 12 mm dia required for reinforcement of plinth in R.C.C. work, work also includes cutting, winding and laying etc. in the T/F plinth.
(f) Grouting of 02 Nos. 90/105 lb. Rail pieces of 3.46m long and (50x50x6)mm M.S. Angle in R.C.C. work at the top of plinth work also includes cutting of rail and angles pieces etc.
(g) Supply & Erection of 12mm thick plaster with cement mortar ratio 1:4 (cement & fine sand) of plinth of 0.4m upper side.
16. Hiring of D/G Set including carriage, loading, unloading & operating charges (with fuel) at 33/11 KV Substation under construction in case L.T. supply is not available near S/S within prescribed accessible limit. 63 KVA, Three phase, D/G Set for fabrication of different structure at Substation.
17. Dismantling of Existing ( 5 MVA-2 Nos) Transformer/33 KV VCB outdoor -1 No Kept at suitable place outside switchyard
(a) Disconnecting HT cable connection from 33KV side & 11KV side of 05MVA Power transformer for removing power transformer from plinth after proper shutdown. Dismantling of 11KV cable support structure, copper bus bar structure, M.S.Frame etc.
(b) Disconnecting copper flexible/Earthing strip from Power transformer neutral & Dismantling neutral earthing system to facilitate removal of Power transformer from plinth.
(c ) Disconnecting Earthing strip from body of 05MVA Power transformer.
(d) Draining of transformer oil from conservator, radiators of existing 05 MVA T/F, at 33/11 KV S/S HAKIMPURA (Saharanpur) into the dry & clean drums and stacking at the safe place in Substation outside of switchyard. Empty drums shall be provided by contractor.
(e ) Removal of conservator, radiators and other accessories from existing 05 MVA Power transformer.
(f) Safe Shifting of 05 MVA Power transformer main body and other accessories from the substation switchyard to outside the switchyard at suitable place assigned by concern J.E/S.D.O (Distribution).
(g) Re-assembling of conservator, radiators and other accessories to existing 05 MVA Power transformer.
(h) Re-filling the transformer oil (old & used in existing 5MVAT/F)
18. Miscellaneous Electrical works of Increasing Capacity of 33/11 KV Substation Hakimpura from 2x5 MVA to 2x10 MVA Installation of 33/11 KV, 10 MVA Transformer : (a) Shifting of available 10 MVA 33/11 KV, Transformer to transformer plinth in Switch Yard.
(b) Erection of shifted Transformer at plinth by fixing all accessories like radiators, conservator tank, filling the transformer oil to desired level and ensuring that there is no leakage, complete job in all respect.
19. Plinth for 33 KV V.C.B. Construction of plinth for the structure of 33 KV VCB & C.T.'s as per details for 01 No.:- (a) Excavation of earth of size (2.4x1.5x1.0)m pits for construction of plinth.
(b) Brick Ballast ratio (1:3:6) (cement, sand & stone grift for foundation work (2.4x1.5x0.15)m plinth.
(c ) R.C.C. work in ratio 1:2:4 (cement, coarse sand & stone grit of 20mm size) for making plinth of size (2.4x1.5x1.0)m and grouting of foundation bolts 04 Nos. for 33 KV VCB.
(d) 12mm thick plaster with cement mortar in ratio 1:4 (cement & fine sand) of plinth of side size (2.4x1.5x0.4)m.
(e ) Laying of G.I.Earth strip of size 50x6mm for connecting the Earth Mat with steel structure. The work also includes cutting, bending, straigthning, over-lapping and welding the earth strip with Earth Mat and various steel structures by using high quality Arc welding in already digged trenches.
(f) Painting of Earth Strip of size (50x6)mm with one coat of ready mixed primer with two coats of ISI mark synthetic oil enamal green paint.
20. Water level earthing by Boring and lowering of G.I. pipe size 40 mm dia & thickness 2mm into the ground at 20 Mtr depth or upto the water level with the lower end of solid copper cone Approx 225 mm long and 750 gm in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG from the cone up to the ground surface where it will be bolted to the G.I. earth Strip for Transformer neutral connection, the earth strip will be welded to the G.I. pipe and neutral earthing support.
21. Fabrication and erection of neutral earthing L Type support made of M.S. Channel size 100x50mm. Structure shall be 4 Mtr. long with 1 Mtr. Arms and 0.75Mtr bracing. Structure shall be grouted in ratio 1:3:6 in block size 300x300x1000mm including plinth and painted with one coat of Ready Mixed primer and Two coat of enamel Aluminium paint work includes connecting neutral bushing rod of power Transformer and M.S. Earthing strip with the help of flexible copper bond, M.S. Bolt and washer with stone Pad of size (300x300x75mm).
22. (a) Fabrication and erection of cable support made of two pieces of M.S. Channel (100x50x6)mm, 2.75 meter long, joined to each other by means of 5 Nos. M.S. Angle (50x50x6) mm pieces of size 0.75Mtr long each by welding at equal intervals and grouting in a block of size (300x1000x1000)mm in C.C. 1:3:6 complete with one coat of ready mixed primer and two coats of Al. paint. Work includes providing of three Nos. M.S. clamps made of (50x6)mm M.S. Flat for holding the cable including nuts and bolts with stone Pad of size (300x300x75mm).
(b) Fixing 110mm dia 2mm thick 2M long G.I.Pipe over 11KV, 3x300Sq.mm XLPE Cable before mounting the 2No. Cable on cable support structure. Work includes fixing of Clamp, sealing of top and bottom end of the G.I.Pipe. One end of G.I.Pipe is to be buried under earth about 500mm.
(c ) Fabrication of copper bus bar of size (2500×50×6)mm in L.V. side of 10 MVA 33/11 KV, power transformer. Work includes connection of outside bus bar in L.V. side busing rod of Power Transformer and other side with outdoor 11 KV cable box as well as providing empire tape and H.T. tape etc. for proper insulation work.
23. H.T. Power Cable Laying : (a) Laying 11 KV, (3x300) mm2 XLPE Cable from power transformer to 11 KV incoming switch gear in the cable trench 0.45 m wide, 0.90m depth. Providing 150 mm local sand for cushion beneath and 150 mm above the cable (quality of local sand required 0.375 cum/m in length). The cable shall be dully protected by brick. On both side of cable by laying brick vertically and bricks would also be laid bricks along the cable (minimum 18 Nos. of bricks are to be laid top and outer side along the single cable. The work includes digging of trenches, laying of cable in under ground trenches, joining of terminal's, back filling of earth and testing and commissioning of power cable etc. Spare cable shall be left over and laid in the trenches in shape of 6 m ring at both ends.
(b) Laying and dressing of 11 KV 3x300 mm2 power cable in air/Trench.
24. Preparation of 11 KV Power Cable ends: (a) Making of cable end termination by Heat shrinkable Out door jointing kits suitable for 11KV, 3x300q.mm XLPE cable. Providing, fixing and crimping of proper size good quality lugs complete in all respect.
(b) Making of cable end termination by Heat shrinkable indoor jointing kits suitable for 11KV, 3x300Sq.mm XLPE cable. Providing, fixing and crimping of proper size good quality lugs complete in all respect.
25. Control Cable Laying (a) Laying of different size of (2×2.5)mm2 control cables i.e. from Buchholz realy to Marshalling box Marshalling box to switch gear room, 33 KV CT's to CT's Junction Box, CT 33 KV, 33 KV P.T, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box as per required for installed equipment.
(b) Laying of different size of (4×2.5)mm2 control cables i.e. from Buchholz realy to Marshalling box Marshalling box to switch gear room, 33 KV CT's to CT's Junction Box, CT 33 KV, 33 KV P.T, V.C.B. Control Panel Junction Box to 33 KV VCB control panel and control panel to 33 KV VCB outdoor operating mechanism panel from T/F etc. in the cable trench including making proper connection at Buchholz Relay, Marshalling box as per required for installed equipment.
26. Construction of fire wall between Transformer (as per Specification)
27. Supply & Fabrication and fixing cable trench cover of M.S. Angle Iron size 50x50x6mm of size 0.3m wide 0.5 to 1.0 mtr. length with proper welding of 8 mm size of bar 2 Nos. in length and 6 Nos. in width & 25mm thick C.C. in Cable Trench Cover in ratio 1:2:4 (cement, coarse sand and stone grift) (i) 0.5 Mtr. long
(ii) 1.00 Mtr. Long
28. Construction of SSO Approach Road (as per Specification)
29. Installation of 33 KV VCB Assembling and installation of 33 KV VCB on the VCB out door structure on the plinth. Adjustment of operating mechanism in proper alignment for smooth operation of the same. The work also includes fabrication of addition arrangement for proper fixing, if required.
30. Installation of 33 KV Bus Isolators : Assembling and installation of Bus Isolator on the isolator structure. Adjusting of operating mechanism in proper alignment so as to ensure smooth operation of the same. In case of Bus Isolator proper operation of earth links shall also be ensured. The work includes fabrication for proper fixing if required.
31. Installation of 33 KV Fuse Set : Assembling and installation of fuse set on the fuse set structure. The work includes fabrication for proper fixing, if required.
32. Installation of 33 KV Lightening Arrestors : Assembling and installation/mounting of 3 Nos. lighting arrestors on the L.A.'s structure/terminal gantry, complete with earthing and line connections. The work includes fabrication for proper fixing, if required.
33. Installation of 33 KV Post Insulators : Installation of 12 Nos. Post Insulators on structure. The work includes fabrication for proper fixing, if required.
34. Installation of 33 KV Control Panel of Double T/F Assembling and installation of 33 KV VCB Control Panel of Double T/F Adjustment of operating mechanism in proper alignment for smooth operation of the same. The work also includes fabrication of addition arrangement for proper fixing, if required.
35. Installation of 33 KV C.T.'s :Installation of 3 Nos. C.T.'s on the C.T.'s structure. The work includes fabrication for proper fixing, if required to complete the work.
36. Outdoor switchyard Earthing with 32 mm.size MS round Earth mat with Delta Earthing on power Transformer Nutral & 33 KV LA as per respo specification
37. Testing & commissioning of Power T/F and all 33KV & 11KV switchgears / Panels. providing required No. of technicians with proper testing equipments during commissioning & energisation.
M/S KUMAR TRADERS KAKA NAGAR
Saraswati Electricals & Contractors
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .