Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹49,700
Closing Date
15 Oct 2020, 3:00 pmClosed
EE(SDW)VI
Delhi Jal Board WSTP KESHOPUR NEW DELHI
Repair / renovation of Jyoti make 3.3 KV HT Panel (Incomer No.1) installed at Sayyad Nangloi SPS.
2020_DJB_195080_2
Press NIT NO. 08 (2020-2021)
Open Tender
Miscellaneous Works
Works
120 days
WSTP KESHOPUR NEW DELHI
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
As per NIT
₹49,700
Yes
21 Oct 2020
29 Sept 2020
15 Oct 2020
29 Sept 2020
15 Oct 2020
29 Sept 2020
Voltmeter 0-5 KV
Multi Funtional Meter
Ammeter 0-300 Amp
Ammeter 0-100 Amp
Illumination Lamp
Indication lamp with dome R,G,B,Y,A collors
TNC Switch
HRC Fuse(2A, 4A, 6A, 10A)
Cureent transformers CTR 300/5/5, Class-1,5P10,15VA
RE-300 Relay 30 VDC
PT Fuse
Vacuum Contractor Spares, Closing coil for VC240v
2-Pole Auxillary Switch
5- Pole Auxillary Switch
Push Button with 1NO,1NC
Bridge Rectifier
Contactor
PDS Assembly for VC
Trip Coil for VC30vdc
Vacuum contactor JVM-1-604 3.3KV
VCB SPARES VK10J13, Pinion gear
Spur gear
Tripping half shaft
Closing half shaft
Tripping coil30vdc
Closing coil30vdc
Power pack 220AC/30VDC
Power pack 220VAC/110VDC
Micro Switch
Servicing of Jyoti Make VCB as per scope of work attached 1. Visual Inspection and Cleaning of Breaker. 2. Lubrication of moving parts of mechanism. 3. Checking the operation of closing and tripping coil. 4. Checking of test/service aux. switch operation. 5. Checking of tripping mechanism operation. 6. Checking of breaker Aux. switch operation. 7. Checking of spring charging limit switch operation. 8. Checking of damper setting. 9. Measurement of stoke gaps for VI contacts in VCB and adjustment if required. 10. Tightness checking of power connection of VCB and electrical wiring in breakers. 11. Checking and tightening of Nuts/Bolts and other fasteners in VCB. 12. Checking of all circlips and lock washers of VCB. 13.Checking of Breakers On/OFF operation manually and electrically. 14. Cleaning of U barrier. 15. Cleaning of Jaw contacts. 16. Checking the alignment of breakers with the male contacts of panel. 17. Checking the anti- pumping operation in VCB. 18. Replacement of defective parts. 19. Measurement of contact resistance , HV Test , Closing & Tripping timing. 20. Scope also includes complete servicing of panel and replacing the recommended Spares as taken in the supply Part.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .