Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.3 LAccepted-AOC | L1 | Accepted-AOC Accepted | |
| 2 | L2₹38.3 L+₹3.9 L (11.5%)Rejected-AOC 101 1ST FLOOR JASOL RESIDENCY 14TH CROSS KANAKANAGAR R T NAGAR POST BANGALORE 560032 | BANGALORE | BANGALORE | KARNATAKA | 560032 | L2 | Rejected-AOC Rejected | |
| 3 | L3₹39.9 L+₹5.5 L (16.1%)Rejected-AOC NO 12 5TH B CROSS SHARADAMBA NAGAR M E S ROAD BANGALORE 560013 | BANGALORE | BANGALORE | KARNATAKA | 560013 | L3 | Rejected-AOC Rejected | |
| 4 | L4₹39.9 L+₹5.6 L (16.3%)Rejected-AOC KG 115 SABIRA MANZIL HBR 2ND STAGE VENKATESH PURAM BANGALORE 560 045 | BENGALURU URBAN | KARNATAKA | 560045 | L4 | Rejected-AOC Rejected | |
| 5 | L5₹40.3 L+₹6.0 L (17.4%)Rejected-AOC M S RRK PROJECTS D 306 ADG P CHENNAI 11 3RD CROSS SIR MV LAYOUT VIDHYARANYAPURA POST BANGALORE 560097 | BENGALURU URBAN | KARNATAKA | 560097 | L5 | Rejected-AOC Rejected |
Tender Value
Refer Docs
EMD Value
₹90,000
Closing Date
2 Jan 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
BANGALORE
GARRISON ENGINEER NORTH BANGALORE T 64 MEANEE LINES MEG AND CENTRE BANGALORE 560042
REPAIRS MAINTENANCE OF EXTERNAL ELECTRICATION SYSTEM OH LINES CABLES LT SWITCH GEARS SECURITY LIGHTS AND OTHER CONNECTED ITEMS AT GUNATHA VIHAR MD ACCN DGQA OFFICERS ENCLAVE AND OFFICERS MESS UNDER GE NORTH BANGALORE
2020_MES_401441_1
8492
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
BANGALORE
Class D category b(i)
6 documents required · 6 mandatory
₹500
Yes
GARRISON ENGINEER NORTH BANGALORE
₹90,000
Yes
11 Jan 2021
7 Dec 2020
4 Jan 2021
7 Dec 2020
2 Jan 2021
21 Dec 2020
7 Dec 2020 - 19 Dec 2020
60 days
Amount
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in deep for cable laying / errection of poles and getting in hard/dense soil complete all as specified and as directed by Engineer-in-charge.
Excavation in trenches in hard/dense soil not less than 1.5 mtr deep and not exc 3 mtr in deep for pole foundation etc complete all as specified and as directed.
Returning, filling in excavated soil, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm thick in hard / dense soil etc complete as specified as directed.
Removing the excavated material to a distance n.exc. 50m and depositing where directed at a level n. exc. 1.5m above the starting point.
Sand cushioning in layers for cables in trenches / ducts for cable using dry river sand including consolidation complete all as specified and directed. NOTE: Punned thickness will be measured for payment purpose.
Bricks, sub class 'B' of old size 230 mm x 115 mm x 75 mm laid in trenches for cable protection all as specified and directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq.mm 2 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq.mm 4 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq.mm 4 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 sq.mm 3.5 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sq.mm 3.5 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 sq.mm 3.5 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 185 sq.mm 3.5 core connected with suitable legs including taking out the existing unserviceable cable complete all as specified and as directed.
Galvinised iron tubing, light grade, 50mm bore with all accessories for cable protection fixed on poles/buildings or laid in trenches including necessary MS clamps, bolts and nuts etc., including taking down the existing complete all as specified and as directed.
Galvinised iron tubing, light grade, 80mm bore with all accessories for cable protection fixed on poles/buildings or laid in trenches including necessary MS clamps, bolts and nuts etc., including taking down the existing complete all as specified and as directed.
Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6mm thick burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr, connected to galvanized strip 25 x 4 mm as earth lead up to 7.5 mtr long by means of nuts, bolts, thimbles, check nuts and washers etc made of galvanized iron connected to earthing test point all as shown in electrical plate No. 3 of SSR Part-I 2010 and as specified or indicated including earth work and excavation in any type of soil, PCC (1:3:6) type C1 chamber, pre cast RCC slab 40mm thick in Reinforced Cement Concrete (1:2:4) type B1 with 8 mm dia TMT bars reinforced at 10 cm centre to centre both ways including funnel with watering pipe wire mesh and lugs, including test point and testing on completion complete all as specified and as directed.
Earthing complete with galvanised steel plate electrode 600mm x 600mm x 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge not less than 1.5 m below ground level connected to earth lead by GI wire 4 mm dia by means of bolts nuts, check nuts, washers made out of galvanised iron connected to main switch all as shown in elect plate No 3 of MES SSR Part -I includingn excavation and earth work in any type of soil,funnel, 20 mm dia light grade GI watering pipe with chamber of PCC 1:3:6 type C1 40mm thick of size 450mm x450mm (1:2:4) type B1 for cover slab reinforced with 8mm dia TMT bars 10cm c/c both ways and with 6mm MS hook etc complete all as specified including testing on completion all as specified and directed.
MCCB, 100 Amps, 16 KA, four pole, 415 Volts, 50Hz with adjustable thermal settig with complete connections with incoming cable and out going cable with suitable thimbles, crimping the thimbles with crimping tools insulating the naked portion with insulation tape and including taking down the existing unserviceable MCCB complete all as specified and as directed.
MCCB, 200 Amps, 36 KA, four pole, 415 Volts, 50Hz with adjustable thermal settig with complete connections with incoming cable and out going cable with suitable thimbles, crimping the thimbles with crimping tools insulating the naked portion with insulation tape and including taking down the existing unserviceable MCCB complete all as specified and as directed.
MCCB, 250 Amps, 36 KA, four pole, 415 Volts, 50Hz with adjustable thermal settig with complete connections with incoming cable and out going cable with suitable thimbles, crimping the thimbles with crimping tools insulating the naked portion with insulation tape and including taking down the existing unserviceable MCCB complete all as specified and as directed.
MCCB, 315 Amps, 36 KA, four pole, 415 Volts, 50Hz with adjustable thermal settig with complete connections with incoming cable and out going cable with suitable thimbles, crimping the thimbles with crimping tools insulating the naked portion with insulation tape and including taking down the existing unserviceable MCCB complete all as specified and as directed.
Cable jointing kit suitable for 1.1KV grade cable for straight through joint complete with jointing material and accessories suitable for 3.5 core / 4core XLPE armoured aluminium conductor cable including taking down the existing for following sizes:- (a) 3.5 core x 25 to 35 sq.mm.
(b) 70 to 150 sq.mm
(c) 185 to 300 sq.mm
Painting of PCC poles of any height and type with two coat of cement based paint with painting black and white strip or as ordered by Engineer-in-charge on poles up to 1.5 mtr high above coping level and numbering with writing letters or figures(Block), height not exc. 30 cm & letters or figures n.exc. 10 Nos complete all specified and as directed.
Boring of holes under road, pavement, hard standing by trenchless technic and nessary machine including inserting of HDPE pipe of bore 100mm dia, suitable for 0.40 Mpa working pressure including excavation at ends complete all as specified and as directed.
Dismantling the damaged concrete poles/struts any size complete all as specified and as directed.
Steel tubular poles complete with cast iron plate, finial tapper plug, bolts nuts & screws as per type 410 SP -31 ,9 mtr long complete all as specified and as directed.
Plain Cement Concrete, (1:2:4), type B1, using 20mm graded stone aggregate, as in coping of pole, including necessary form work make good to road surface , hard standing etc all as specified and as directed.
Plain Cement Concrete, (1:4:8), type D2 using 40 mm graded stone aggregate for filling and mass concrete of pole / cutting of road, all as specified and as directed.
Supply, testing and commissioning in replacement of weather and vermin proof LT feeder pillar box factory fabricated outdoor cubicle / kiosk type CPRI approved and confirming to IS 5036 totally enclosed made out of 3 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel, centre opening, front and rear opening doors (covers) with handles, each control switch to be fixed in each compartment with hinged door, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC / rubber bushes to prevent ingress of water / vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, Condt/-- 1.32
Supply,testing and commissioning in replacement of weather and vermin proof LT feeder pillar box factory fabricated outdoor cubicle / kiosk type CPRI approved and confirming to IS 5036 totally enclosed made out of 3 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel, centre opening, front and rear opening doors (covers) with handles, each control switch to be fixed in each compartment with hinged door, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC / rubber bushes to prevent ingress of water / vermin etc, inside the enclosure, the required Nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, Condt/-- 1.34
Supply,testing and commissioning in replacement of weather and vermin proof LT feeder pillar box factory fabricated outdoor cubicle / kiosk type CPRI approved and conforming to IS 5036 totally enclosed made out of 3 mm thick sheet metal enclosure with angle iron frame of MS angle 50x50x6 mm suitable for operation on 3 phase 4 wire, 440 volts 50 Hz system, with hinged panel, centre opening, front and rear opening doors (covers) with handles, each control switch to be fixed in each compartment with hinged door, bottom gland plate and locking arrangement consisting of sufficient Nos of circular cable entry holes at bottom only with suitable PVC/rubber bushes to prevent ingress of water/vermin etc, inside the enclosure, the required nos of holes to be fixed with chromium plated brass cable glands for cable entry and exit complete with necessary internal wiring with stranded copper conductor PVC insulated cables of adequate size, Condt/-- 1.36
Sheet metal enclosure / junction box of size 800x800x300mm, outdoor type, double door with aluminium bus bar 200 Amps suitable for 3 phase and neutral including MCCB 4 pole 415 volts 100 Amps 16 KA and removing old unserviceable junction box complete all as specified and as directed.
Disconnecting electric supply from electric meters and dismantling MS electric meter box of any type / size including electric meters, switch gear, MCCB / MCBs etc. supply, install, testing and commissioning of electric meter box made out of 2mm thick MS sheet, double door type with locking arrangement of size /dimensions not less than 1300 x750x300mm with suitable thickness of hylem sheet for fixing existing electric meter -08 Nos, including provision of new MCCB 100 Amps -01 No, MCB SPN 32 Amps -09 Nos with suitable size of aluminium busbar for phase and neutral, see through glass-08 Nos, connecting internally, prewired copper conductor witth electric meter connection of required size ,applied with powder coated synthetic enammeled paint and making good to the disturbed wall surface complete all as specified and as directed .
Disconnecting electric supply from electric meters, dismantling MS electric meter box of any type / size including electric meters, switch gear, MCCB / MCBs etc complete, supply, install, testing and commissioning of electric meter box made out of 2 mm thick MS Sheet double door type, with locking arrangements of size /dimensions not less than 1200 x750x300mm with suitable thickness of hylem sheet for fixing existing electric meter -07 Nos, including provision of new MCCB 100 Amps -01 No, MCB SPN 32 Amps-08 Nos with suitable size of aluminium busbar suitable for phase and neutral, see through glass-07 Nos,connecting internally prewired copper conductor with electric meter connections of required size ,applied with powder coated synthetic enammeled paint and making good to the disturbed wall surface complete all as specified and as directed.
Cable fault finding in LT cables any sizes complete all as specified and as directed
60 Watt LED street light fitting with pressure die cast housing along with prismatic polycarbonate modular secondary lens optics with IP 66 ingress protection and impact resistance of IK 08.4kV inbuilt and 10 kV external surge protection with top opening driver cover for easy maintenance including taking down old unserviceable street light fittings from pole all as per Halonix Cat No.HLSLD 15-60 CWL-R-SH / Bajaj Cat No. ENXT P 72 L WH CR PC SD or techno commercially equivalent makes specified in PS complete all as specified and as directed.
90 Watt LED street light fitting with pressure die cast housing and toughened glass and individual LEDs with secondary lens optics with IP 66 ingress protection and impact resistance of IK 07. 5kV inbuilt and 10 kV external surge protection with top opening driver cover for easy maintenance including taking down old unserviceable street light fittings from pole all as per Halonix Cat No.HLSLD 10-90 CWL-I / Bajaj Cat No. BRTFG 90W LED CR or techno commercially equivalent makes specified in PS complete all as specified and as directed.
LED driver suitable fro 25 Watt to 60 Watt LED fittings of any type including dismanling and taking out the LED street light fittings from pole and removing the burned out /unserviceable driver and replacement of the same to make the fitting serviceable and refixing in the existing / new location all as directed at site.
FRP moulded junction box with IP 65 protection of size 300x200x80mm with 32 Amps 4 way heavy duty terminal block with 6 Amps MCB SP and two number of cable entry gland of standard size with suitable MS clamps to fix with pole including taking down the existing complete all as specified and as directed.
Brackets made out of GI tubing medium grade 40mm bore of 1.50 mtr length bent to required shape and pattern to mount the street light, including MS clamps made out of MS flat iron 25 x 3mm, nuts, bolts, washers etc and applying two coats of alumium paint over a coat of red oxide primer complete all as specified and as directed.
Sub main wiring with two runs of single core 2.5 sq.mm, 1100 volts grade multi stranded copper conductor cable along with one run of 2.5 sq.mm PVC insulated single core multistranded copper conductor cable as earth continuity conductor drawn through and including non metalic rigid PVC conduit medium grade of suitable size complete including taking down the existing all as specified and as directed. NOTE:- Two runs of 2.5 sq.mm cable, one run of 2.5 sq.mm earth continuity conductor and one run of PVC conduit shall be measured as one unit for payment purpose.
LED bulb 40 watt including dismanling and taking down old unserviceable CFL type street light fittings from pole , removing the unserviceable CFL and replacement of new LED with suitable size holder and refixing the existing / new location complete all as directed at site.
LED Post top lantern 40 watt with die cast aluminium, spigot, spun aluminium powder coated top cover, heat sink, opal PC diffuser and clear acrylic IP-65 protection, including taking down old unserviceable lantern all as per HALONIX Cat No. HLPT-04-40-CW or techno commercially equivalent makes specified in PS complete all as specified and as directed.
LED bollard 10 watt with MS pipe housing glare free PMMA diffuser and IP 65 protection all as per HALONIX Cat No. HLOB-05-10-CW or techno commercially equivalent makes specified in PS complete all as specified and as directed.
30 Watt LED security light fitting with pressure die cast housing, with secondary optics and IP 65 protection including taking out old fittings all as per Halonix Cat No.HLSLD-09H -30-CWL-R / Bajaj Cat No. BCLST 30W LED I or techno commercially equivalent makes specified in PS complete all as specified and as directed.
LED flood light luminaries 120 Watt, with ultra sleek , light weight and secondary optics made of pressure die cast housing with IP 66 ingress protection and impact resistance of IK 07 inbuilt including channel for fixing of wall with complete fitments, all as per Halonix Cat No.HLFLD ML01-120-CWL-R / Bajaj Cat No. BAJAJ BJFL 120W LED I or techno commercially equivalent makes specified in PS complete all as specified and as directed.accessories .
Vasavi Electricals
Shanthi Construction
GS TRADERS
RRK PROJECTS
S S BUILDERS
K T ASSOCIATES
RAMSON TRADERS
M.G. Enterprises
LITE SYSTEMS INDUS
KAALIKA ELEVATORS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .