EE-l CKHED PWD
Central Kolkata Health Electrical Division P-12, C.I.T Road(1st floor) KOLKATA
Supply, Installation, Testing and Commissioning of fire detection and alarm system at central library building, canteen building, sub-station bldg and several areas of other buildings within the college campus of CNMC and H, Kolkata. (Electrical Work
2025_WBPWD_866843_1
WBPWD/EE-I/CKHED/eNIT19/25-26
Open Tender
ELECTRICAL WORKS ORG
Item Rate
40 days
NMCH
Please refer Tender documents.
3 documents required · 3 mandatory
₹49,132
Central Kolkata Health Electrical Division
14 Aug 2025
19 Jun 2025
11 Jul 2025
19 Jun 2025
9 Jul 2025
25 Jun 2025
24 Jun 2025
Amount
SITC of Microprocessor based intelligent, addressable 4 loops fire alarm control panel (VDS/ UL/FM/ULC approved) with S&F of 4 Loop Cards and fully networkable with each loop capable of taking minimum 125 devices, minimum 160 character alpha-neumeric liquid crystal display. The panel shall be able to give pinpoint location of all fire/ fault conditions. Further, the panel must be able to automatically switch off respective control switchs whenever any alarm is triggered. The Panel should be able to store sufficient numbers of log events in in its Memory as per recommended standards. (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
The panel shall have in built rectifire, provision for external & internal printer (if required), Loop cards, LCD unit to indicate Fire/ Fault Signal with address analog output, complete in all respects, in built surge protection facility, integral SMF laed-acid batteries with sealed cells of 24V or 12V 7AH 02(two) nos capable of running for 24 hours normal working & then be capable of operating the system for 30 minutes during emergency condition with integral battery charger complete as required. The panel shall have extra loop card to serve as standby in case of burnout or malfuntioning of any operating loop cards. The FACP shall be capable of being networked (future expansion) with other similar FACP located at different part of the premises through single RS485 bus. The panel should have Modbus output & ready to communicate with remote computer. The system must be preuploaded with licensed software. (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
Upon completion of the commissioning process, a comprehensive Single Line Diagram (SLD) and chart of the installed fire alarm system will be submitted. This documentation will detail the block/room names, specific locations of detectors, Manual Call Points (MCP), hooters, and the associated cable path lines. This SLD will serve as a precise and thorough representation of the fire alarm system layout and configuration, ensuring easy reference for maintena-nce,troubleshooting, and future upgrades. Soft as well as printed hard copies of the SLD and chart will be provided within three days of the commissioning date, ensuring timely and accurate documentation for all relevant.
SITC of Analog Addressable Intelligent multi-sensor detector (VDS/EN54/UL/FM/ULC approved) with two inbuilt optical smoke sensor as well as additional heat detector sensor with decentralised intelligence, addressable Phototharmal type with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost). (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
SITC of Analog Addressable Heat detector (Fixed temperature cum rate of rise) (EN54/VDS/UL/FM/ULC approved with inbuilt fault isolator as per NFPA style 7 wiring complete with base having IP as per recommended standard. (Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost). (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
SITC of Analog Addressable Manual Call Point (EN54/VDS/UL/FM/ULC approved) addresable type with in-built fault isolator(Note: Detectors without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost) as per NFPA style 7 wiring completed as required. (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
SITC of Analog Addressable Hooter (sound output minimum 90dB) cum strobe (strength of light 10cd) complete with necessary modules if required with inbuilt isolator(Note: Devices without built-in fault isolator is also acceptable but in such case the contractor shall provide one independent fault isolator module for every group of addressable devices in group will be as per latest recommended standard without any additional cost) & and (EN54/VDS/ UL/FM/ULC approved) and approved.(Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
Supply, Installation, Testing & Commissioning of Analog Addressable transponder/ Monitor Modules ( EN54/VDS / UL / FM / ULC approved ) for monitoring flow switches/Fire exit doors / AHU / Lift etc complete as required. (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
Supply, Installation, Testing & Commissioning of Addressable Relay Modules (EN54/VDS / UL & FM approved) for switching / integration of Lift / AHU etc complete as required(Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
SITC of LED metal body type Response Indicator having 2 Nos. red coloured LED lamps including connection set, etc. (Make- Esser / cerberuspro / /Secutron / notifier/ morley / Apollo)
Supply & Laying of 2 Core 1.5 sq. mm FRLS shielded copper Cable (For Loop) (Make: Finolex/ KEI) with 20 mm NB PVC rigid conduit pipe (Make: Precision-Medium) on the surface of the wall.
Checking, Rectification, Testing and Re-commissioning of existing installed Esser make 2 and 4 Loop Fire Alarm Panel Installed at Anatomy, Admin & Academic Building of CNMC&H.(Upon completion of the Re-commissioning process, a comprehensive Single Line Diagram (SLD) and chart of the installed fire alarm system will be submitted. This documentation will delineate block/room names, precise locations of detectors, Manual Call Points (MCP), Hooters, and the associated cable path lines. Four copies of the SLD and chart will be provided within 3 days of the Re-commissioning date, ensuring a thorough representation of the fire alarm system layout and configuration.)
NOTE: The Fire Alarm system shall comply with latest requirements of- 1. National Fire Alarm Protection Association (NFPA) Standards. 2. IS 2189. 3. NFPA 70 National Electric Code. 4. NFPA 72 National Fire Alarm Code. 5. Local Statutory Regulations. 6. Manufacturer Recommendation.
TESTS: 1.The system shall be tested and commissioned by a qualified competent, trained engineer or technician authorized by the manufacturer of the fire alarm equipment to technically supervise and participate during all of the adjustments and tests for the system 2. Before energizing the cables and wires, check for correct connections and test for short circuits,ground faults, connectivity and insulation and other test as per above standards must be done.
Terms and condition: The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill.If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
Computer Gallery (BID ID -6698904)
Creative Projects (BID ID -6697529)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .