Commissioner Municipal Corporation Bharatpur
Municipal Corporation Bharatpur
Laying of Oxygen Pipe Line at Janana Hospital Bharatpur
2021_DLB_234033_1
Nit (Oxygen Pipe) Municipal Corporation Bharatpur
Open Tender
Miscellaneous Works
Item Rate
60 days
Municipal Corporation Bharatpur
Please refer Tender documents.
2 documents required · 2 mandatory
₹500
Municipal Corporation Bharatpur
Exempted
8 Sept 2021
23 Jul 2021
17 Aug 2021
23 Jul 2021
16 Aug 2021
23 Jul 2021
Amount
SITC of MGPS of medically grade as per BSEN-13348 with third party certification from Lloyds/TUV degreased (ie free from oil, grease and partivulate matters) seamless copper pipe confirming to ASTM B88 and all copper joining done by brazing with AWSA5.8, classification BCuP-5 or BS 1845 following procedure in accordance with ASTM B828 after purging with nitrogen. All pipe cutting shall be carried out with a radial pipecutter and copper pipe fitting's shal comply with B4 alloy designation. Adequate support shall be provided while laying pipeline testing shall be done at 17 bar and after testing pipe shall be painted with two coat of enamel paint as per colour codification as per ISO 7396-Part-1 2016.
SITC of non lubricated ball type GM Isolation Valve with adapter & PTFE Seat havng quarter turn handle opening of following sizes suitable for flow capacity 1500 LPM at 4.7 bar with maximum allowable pressure of 30 bar and suitable for working temperature ranging - 20'C to 130'C. Valve should be CE approved / CE certified. For 12 MM OD pipe
For 15 MM OD pipe
For 22 MM OD pipe
For 28 MM OD pipe
SITC of Gas outlet points (AR-4), (AR-7) and vacumm (8.7 psig) for dispensing medical gases (oxygen/air/vaccum) at point of use confirming to BSEN ISO 9170-1: 2008. The Gas outlet are quick connect for different gas source and should accept only respective adapters as required. (oxygen 192+ vaccum 192)
SITC of BPC (back pressure compensated) flow meter with humidifer made of nickel plated body double jacketed with flow gradations marked on it. Desired flow will be setteled through roatary knob. Flow range should be between 0 to 15 Ipm & work should be executed as per direction of engineer n charge.
SITC of suction unit (suction controller and collection jar) with posibility to configure required capacity capacity collection jar and should meets the requirements as per BSEN ISO 10079-3:2009 the unit must designed to operate with the vacucum regulator suitable for 0-14.7 psig with flow rate 0-55 Lmp (min) for operating temperature - 18'C to 50'C with ON/OFF facility. The collection jar should be transparent, made of high quality polycarbonate that can be autoclaved at 121'C for 20 minutes for reuse and provided with auto stop to avoid over spill and contamination of the suction source when the jar collection reached optimized level, the complete unit supplied with filter to protect the source and pipe line from bacterial contamination. 600 ml Capacity collection Jar
SITC of automatic gas control panel for oxygen/nitrous oxide control panel cover made for M.S duly powder coated. Compact and fully automatic manifold control system for oxygen services easy to maintain and use Designed with both safety and continuity of flow supply at a constant pressure via two banks of bottled gas cylinders with following status monitoring A- Bank in use (Green Indication) B- Empty bank (Red Indication) Control Panel should have built in LED display to indicate Normal, High & Low line pressure. It should have facility to test all above indicators working perfectly. The control Panel should include pressure gauge to indicate the gas pressure of each header and pipe line distribution pressure. Capable to provide a distribution flow rate in excess of 1200 LPM. The control panel should incorporate manual bypass system in case of failure of shifting mechanism. It should be of CE certified product.
SITC of Oxygen/Nitrous Oxide Manifold System (8,8)with tal pipes NRV-manifold system comprise of bank of 8+8 cylinders (Bulk cylinder of D type) capacity manifold high pressure copper pipe of size 1/2"ID x14 swg (approx 2.0320 mm) & high pressure fitting made of high tensile strength brass be used to connect the cylinders to the header assemblies with 16 no's non return valves & 16 no's high pressure flexible tail pipe is made of copper pipe of 1/3"x16 swg (approx. 1.6256 mm) the manifold is hydraulically tested at 225 kg/cm2 pressure it is also degreased and is to be offered duly wrapped in a polythene bag make CE Approved/CE.Note: Providing of Cylinders is in the scope of Hospital / EndClient.
SITC of Vacuum pump of single stage capacity 4235 lpm/149 cfm (piston displacement) The pump should be suited for maximum working pressure of 29 inch mercury (730 mm mercury) The pump should be fitted with MS channel frame complete having vibration isolators with 1 Nos. silencers at vacuum pump discharge end. The pump should be air cooled 1 sets of isolation valve on return valve and filter should be provided with pumps. Drive Assembly The electrical drive for vacuum pump should consist of suitable TEFC induction motor operating at 1440 RPM and connected through a V-belt. The motor should be suited for 415 V+10% 50 HZ.3 Phase AC supply capacity : 10 HP of a reputed make vacuum switch vacuum switch of 0-760 mm range should be provided it should have both NO/NC contracts and suitable for 230 V 50 Hz . AC supply. The vacuum switch should be housed in weather proofcasing with 3/8"BSP gas service connection at the bottom of the assembly. Vacuum Filter 1 Nos vacuum filters with drain valve. This filter should be non-ferrous and in line. including making PCC foundaton and fixing withbolts, anti vibration pad and making connections complete as required.
SITC of hot dipped galvanized ( inside and outside) Air receiver tank (as per IS: 7938-1976 and upto date amendment ) for compressed air system to dampen out pulsatin and condense and trap the moisture in the compressed air and also to let oil and other impurities settle down before air passes into the piping with safety valve Drain Valve Pressure gauge and fusible plugs of 1000 litres capacity complete as required including making PCC foundation and fixing with bolts and making connections complete as required.
S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, makingconnection etc. as required. 25mm x 3mm G.I. ( Hot Dipped ) Strip
Kamtech Associates Pvt. Ltd.
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .