Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.6 LAccepted-AOC 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L1 | Accepted-AOC Lowest and Reasonable | |
| 2 | L2₹7.8 L+₹20,880 (2.74%)Rejected-Finance H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | L2 | Rejected-Finance Other than Lowest | |
| 3 | L3₹9.4 L+₹1.8 L (23.1%)Rejected-Finance 1ST FLOOR GURJEET MARKET DHANGU ROAD | L3 | Rejected-Finance Other than Lowest | |
| 4 | L4₹21.3 L+₹13.7 L (180.6%)Rejected-Finance | L4 | Rejected-Finance Other than Lowest |
Tender Value
₹12.4 L
EMD Value
₹24,720
Closing Date
22 May 2023, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
CWE (AF) Jammu
Headquarters, CWE (AF) Jammu Near Gurdwara Sahib and Mandir Airforce Station Satwari, Jammu Pin 180 003
REPAIR / MAINTENANCE OF EXTERNAL ELECTRIC SUPPLY DISTRIBUTION SYSTEM AND ALLIED WORKS AT AF STATION DALHOUSIE
2023_MES_590308_2
CWEAFJ-03/2023-24
Open Tender
Civil Works
Item Rate
180 days
Dalhousie
Please refer NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE (AF) Pathankot
₹24,720
Yes
24 Jun 2023
2 May 2023
24 May 2023
2 May 2023
22 May 2023
8 May 2023
Amount
Drop out fuse unit, expulsion type for out door air break gang oprated switch, single pole mounted on and including insulators for 11 KV working pressure fixed to and including MS channel with nuts, bolts and washer etc synthetic bounded fuse tube complete with line capcity suitable for current carrying capacity upto 100 Amps all as directed including taking down old one all as specified and as directed.
Vertical type Air Break Switch, Gang Operated, tripple pole, mechanically operated, outdoor type, with all fittings and accessories mounted on and including HT 11 KV porcelain insulators and steel channel frame, GI operating rod 25 mm dia of suitable length to worked from ground, including locking arrangements, suitable for 11000 volts, 400 Amps current rating complete including taking down existing one all as specified and as directed.
Pin type Insulator porcelain, vitreous, white, brown or green including one galvanized mild steel spindle two GI washers and one nut of size 150 mm height 150mm dia suitable for 11000 volts HT grade complete including taking down of old unserviceable items complete all as specified and as directed.
Disc type insulator 145 mm height 255 mm dia suitable for 11000 volts HT grade porcelain vitreous white, brown or green including galvanized mild steel sectional straps 38X5mm, insulator bolts dia 20mm, washers and nuts including taking down old unserviceable items complete all as specified and as directed.
Lightning Arresters suitable for 11000 Volts, expulsion type complete with all fittings, transmission class, discharge capacity 65 KA complete including taking down old unserviceable items complete all as specified and as directed.
Aluminium Conductor Steel Reinforced (ACSR) including binding to insulator with suitable size of binding wire and size of conductor Weasel (6/1 x 2.59 mm), Squirrel (6/1 x 2.11mm) or Ferret (6/1 x 3.00 mm) and maintaining proper sag as per IE rule including taking down old conductor of any type /size and removing from site, complete all as specified & directed. Note : Jumper on cut-out point / Two Pole Structure / Four Pole Structure shall be provided with PVC insulated sleeve. The Quoted Rate shall be deemed to include this aspect.
Galvanized steel wire 4 mm dia for earth wire/ guard wire on HT poles stretched without kinks, bend and binding with wire including fabrication of cradles hexagonal/ rectangular guards, spacers, road crossing etc. including taking down old wire of any type shape, size and removing from site, complete all as specified & directed.
Cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, drilling holes for bolts, in any shape or size as indicated or directed and also inclusive of two coats of aluminium paint over one coat of red oxide primer including dismantling / taking down old unserviceable structural steel all as specified and as directed.
Disconnecting the electric supply from the existing RMU / VCB / Transformer / HT Poles and meggering the HT underground cable for its IR value and ensuring the serviceability by HT megger, locating the faults by HT fault finding instrument for any distance and reconnecting the HT cable complete all as specified and as directed. Notes : 1. Earth work in excavation including returning filling in and removal of surplus spoil will be carried out under this item. The Quoted Rate shall be deemed to include this aspect. 2. Jointing Kit and HT underground Cable shall be measured and paid separately under respective item.
Cable Jointing Kit for 11 KV (Earthed) grade cable for Straight Through Heat Shrink type joint complete with jointing material and accessories suitable for 3 Core 70 to 95 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Cable Jointing Kit for 11 KV (Earthed) grade cable for Straight Through Heat Shrink type joint complete with jointing material and accessories suitable for 3 Core 120 to 185 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for Indoor Termination Heat Shrink type Joint complete with jointing material and accessories suitable for 3 core 70 to 95 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 02 / 04 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for Indoor Termination Heat Shrink type Joint complete with jointing material and accessories suitable for 3 core 120 to 185 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 02 / 04 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 70 to 95 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2/4 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core 120 to 185 Sqmm XLPE armoured aluminium conductor cable including cutting and removing existing unserviceable joint, excavation near 2/4 pole structure / HT Panel board / Transformer and taking out loop cable from trench and refilling the trench with excavated material all as specified and as directed.
Unbinding from insulators ACSR conductor any size of HT over head line for repairs, re-stretching of ACSR conductor to achieve proper sag as per IE Rules and rewinding to the insulators using aluminium / GI wire all as required at site or directed. Note : Distance between two poles irrespective of number of lengths of conductor shall be considered as a one span.
Cutting and trimming of trees and branches to clear the over head line in the arc of HT/LT over head line feeders and removal of the trimmed branches of trees complete all as specified and directed. Notes : 1. Any ACSR conductor damaged during the cuttings of trees / branches shall be repaired and jointed / fixed by the contractor, to the entire satisfaction of Engr-in-Charge, without any extra cost and nothing extra shall be admissible from the department on this account what-so-ever. 2. The cutting / trimming of tree branches shall be done to at least 3.00 metre radius of OH line. 3. The unit of measurement is 'SPAN' i.e. distance covered between two adjacent poles.
Painting to Four Pole Structure made out of Steel Tubular HT poles, 11m long including cross arms, channels, angle iron support, bracings, clamps etc. with two coat of aluminium paint superior quality of approved make on surfaces exposed to view above PCC benching including preparation of old painted surfaces by scrapping etc. complete including making 30 cms wide strips (total 05 Nos) with white and black paint alternatively and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and as directed.
Painting to Two Pole Structure made out of Steel Tubular HT poles, 11metre long including cross arms, channels, angle iron support, bracings, clamps etc. with two coat of aluminium paint superior quality of approved make on surfaces exposed to view above PCC benching including preparation of old painted surfaces by scrapping etc. complete including making 30 cms wide strips (total 05 Nos) with white and black paint alternatively and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and as directed.
Painting of steel tubular HT Poles, 11metre long including cross arms, channels, angle iron support, bracings, clamps etc. with one coat of aluminium paint superior quality of approved make on surfaces exposed to view above PCC benching including preparation of old painted surfaces by scraping etc. complete including making 30 cms wide strips (total 05 Nos) with white and black paint alternatively and writing pole numbers. of 2 inches bold letters with black paint after painting, complete all as specified and as directed.
Danger Notice Plate fabricated of 1.6mm white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps bolts and nuts of approved size, for HT, 25cm x 20cm size complete all as specified and as directed. Note : The letters shall be in local language i.e. English, Hindi & Urdu all as directed at site.
Anti climbing device, spikes type, fabricated out of MS bars (Round, Square or flat) 12 mm dia round bar made out of 40x6 mm MS flat including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole spike welded to flat iron bolt, nuts washers including one primer coat, one under coat and two finishing coats of silver aluminium paint including preparation of surfaces complete all as specified and as directed.
Earthling complete with galvanised steel earth plate electrode 60cm x 60cm x 6.0mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and including GI Strip 25 x 4mm as earthling lead, by means of bolts, nuts, check nuts and washers of galvanised iron all as shown in Electrical Plate No 5 of MES SSR Part-I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C-1 Chamber, with CI cover, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs complete all as specified and directed with earth resistance not more than 1.0 Ohms complete all as specified and as directed. Note : In case earth resistance is more than 1.0 Ohms, the contractor will redo the earthing at no extra cost to the government.
Earthing complete with Copper earth plate electrode 60cm x 60cm x 3.15 mm thick, buried directly in ground (earth pit not less than 2.25 meter deep below ground level) with top edge of the plate not less than 1.5 meters below normal ground level, connected to and including Copper Strip 20 x 3 mm as earthing lead, by means of bolts, nuts, check nuts and washers of copper all as shown in electrical plate No 5 of MES SSR Part I and testing on completion including excavation and earth work in any type of soil, PCC (1:3:6) type C1 chamber, with CI cover, funnel with wire mesh, GI watering pipe 20mm dia medium grade and lugs all as specified and directed with earth resistance not more than 1.0 Ohms complete all as specified and as directed. Note : In case earth resistance is more than 1.0 Ohms, the contractor will redo the earthing at no extra cost to the government.
Earth continuity conductor or main earthing lead fixed to walls on batten or recess or chases or buried in ground or drawn in conduit / pipes or fixed to poles or any other indicated situation for loop earthing etc. as required 25 x 4mm galvanised iron strip complete all as specified and as directed.
Earth continuity conductor or main earthing lead fixed to walls on batten or recess or chases or burried in ground or drawn in conduit/pipes or fixed to poles or any other indicated situation for loop earthing etc. as required 20 x 3mm copper strip complete all as specified and as directed.
Carrying out Calibration of HT VCB Switchgear 800 / 630 / 400 Amps, and 11 KV HT RMU SF6 VCB breaker all as per OEM instructions after taking proper shut down and disconnecting the cables from panel and VCB Breakers, calibration of over fault relay, earth fault relay, checking of alignment of VCB isolating contacts, servicing of operating mechanism including tripping and closing system of the breakers, dehydrating, decarbonising of panel, bus section & circuit section including incoming / outgoing cable and necessary HT insulation at joints. Removing perished monoplus compound cleaning and re-insulating with HT taps wherever necessary, with and including replacement of burnt out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers etc., under the supervision of authorised dealer/ representative, and refixing the panel in its original position and testing entire satisfaction of Engr-in-Charge.
Notes : 1. The quoted Rate shall be deemed to include visiting and inspection of VCBs / RMU by Technician / Mechanic and supply and replacement of minor spares etc. 2. Any burnt out / defective items like moving / fixed contacts, tripping coils, earth fault relay etc., will be measured and paid separately under respective items of BOQ.
Breaker Epoxy Body suitable for VCB trolley as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Tulip Contact 630A suitable for VCB trolley as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Socket Contact 630 / 800A suitable for VCB trolley as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Vacuum Interrupter Assembly with Flex connection suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Shunt Trip Coil 24Volts DC (OG 835) / 220V AC (OG 870) suitable for VCB as per existing make and model 11 KV, 400 / 630 /800 Amps complete all as specified and as directed.
Motor Charge Spring Mechanism assembly complete fitted with close/ trip Coils (Mention Trip, close and motor voltage) Motor with Gear Assembly 110V AC/220V AC, Gear Box for Motor with Gear Assembly (Bosch make) 110V AC / 220V AC, Ratchet wheel Assembly all as specified and directed. Suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Solenoid Mechanism (SX-15) with coils and Auxiliary Switch (Mention Trip and Close Voltage) suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Auxiliary switch 12-way suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Carriage Assembly for breaker complete with Lead Screw with Bevel Gear, Lifting Nut (Brass) Pinion Assembly, Lifting Shaft Bush, Modified Bell Crank suitable for VCB as per existing make and model 11 KV, 400 / 630 /800 Amps complete all as specified and as directed.
Secondary Plug and Socket set Board Assembly (28 WAY) suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Shutter Busbar – Red & Yellow suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Disconnecting the electric supply from the existing VCB and disconnect the existing unserviceable / Brunt current transformer set (Set of Three Phase) from VCB panel and supply & Fixing and testing in replacement new resin cost current transformer set (Set of 3 Phase) 11000 Volts HT copper wounded with mild steel parts 100/5 +5 Volts single phase class 0.5 of air cooled accuracy dry type VA15, VK ≥ Core 1 R at 75 C as per IS-2705, IEC-60044 connection with panel, properly after installation and testing etc. complete all as specified and as directed.
Disconnecting the electric supply from the existing VCB and disconnect the existing Potential transformer set (set of 3 Phase) indoor type with panel and supply & Fixing and testing in replacement new resin cost Potential transformer set (set of 3 Phase) 11000 Volts HT copper wounded with Ratio 11000 Volts/110 Volts burden 100VA-3V class-I 50 HZ , HSV-12 Volts secondary voltage 110 dry type as per sample, properly connection with HT panel after installation and testing etc. complete all as specified and as directed.
Breaker control switch (TNC) Trip, Neutral, Close (32 / 40A / 660V AC) suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Push to Trip Knob (Red & Green) Assembly With spring & Housing suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Power Pack of capacity 100 VA complete with all accessories input voltage 110VAC 50C/S Three Phase and Output 24 V DC suitable for VCB as per existing make and model for 11 KV, 400 / 630 /800 Amps complete all as specified and as directed.
Charge-free indicator Assembly with spring suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
HRC Fuse-Pt HT Side (VTF-11, 3A / VTF 6.6, 3A) suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Isolating Contact Flat Type - 800 / 630A suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Hand Charge spring mechanism (SPX) with coils (Mention Trip & Close Voltage) suitable for VCB as per existing make and model 11 KV, 400 / 630 / 800 Amps complete all as specified and as directed.
Three Phase Voltmeter 11 KV digital type suitable for VCB 11 KV Panel, 400 / 630 / 800 Amps complete all as specified and as directed.
Three Phase Ampmeter 11 KV digital suitable for VCB panel, 400 / 630 / 800 Amps complete all as specified and as directed.
Phase Indicator of red, yellow, blue, green 230V or 110Volts suitable for VCB 11 KV, 400 / 630 / 1200 Amps complete all as specified and as directed.
Air Break (Aux) Controller relay, 24Volts DC as per existing make and capacity / Model for VCB 400 / 630 / 800 Amps capacity, Suitable for type VCB : VMX / UNIVAC complete all as specified and as directed.
Charging Motor 230 Volts DC / AC for VCB 400 / 630 / 800 Amps capacity, Type : VMX / UNIVAC complete all as specified and as directed.
Over current and earth fault relay Auxiliary universal supply 18-52 V AC / DC operated, Digital I/P + O/P (Make : CG / L&T / ABB) self powered CGI 14N/14C suitable for VCB for VCB 800 / 630 / 400 Amps capacity complete all as specified and as directed. Note : Fixing of protection relay shall be carried out through O.E.M's Engineer / Technician only.
Release / Closing Coil 12V/24V DC to 220V DC for VCB 800/630/400 Amps capacity, Type : VMX / UNIVAC complete all as specified and as directed. Note for Serial Item No 27 to 55 : The spares shall be measured and paid only when required at site during servicing of VCBs complete all as specified and as directed.
Dehydration, filtration, heating and refilling of old Transformers Oil after testing the same for dielectric strength not less than 45 KV (RMS) complete all as specified and as directed. Notes : 1. Dehydration and filtration can be carried out at site by dehydration machine otherwise the same shall be got done from the manufacturing workshop of transformers complete all as specified. 2. Contractor shall ensure no wastage of transformer oil is done. 3. Safety of transformer during filtration shall solely be the responsibility of contractor and any damaged caused to transformer during the operation of filtration shall be made good by contractor at his own and no claim for any expenditure on this account shall be entertained during execution of work or later stage.
4. Contractor shall ensure that the conservator tank are full before starting the dehydration. 5. Testing of transformer oil for BDV and acidity as per IE rules all as specified and directed. 6. Test results shall be submitted to Engineer-in-Charge equipment wise.
Supply and top up of Transformer Insulating Oil HV grade having die-electric strength not less than 45 KVA (RMS) at 2.5mm gap complete all as specified and as directed.
Disconnecting / dismantling carefully primary & secondary HT/LT connection from Transformer for servicing of capacity 63 KVA to 160 KVA complete, Opening the Transformer, safely collecting Transformer Oil, taking out core of transformer by disconnecting the same from HT/ LT bush rods, Checking / Repair / Replacement of HT / LT Bush, Cork Sheet etc. assembly of Transformer after carrying out the repair work and making all HT / LT connections with respective bush rods complete all as specified and as directed. Notes : 1. The quoted Rate shall be deemed to include :- (a) Visiting and inspection of Transformer of Technician / Mechanic. (b) Installation of Transformer on locations as directed by Engineer in Charge on existing HT Pole Structure/ Plinth and making all HT / LT and earth connections including testing the transformer complete.
(c) Necessary tools and plants and transportation to workshop and return back at site using Vehicle, Hydra / Crane etc. 2. Burnt out / defective items, if any, will be measured and paid separately under respective items.
All as per the description of Serial Item 58 here-in-before but of capacity 200 KVA to 400 KVA complete all as specified and as directed.
Supply and replacing of Ceramic Bush insulators with brass spindle rod complete with cork sheet gasket, washers, nuts and check nuts on HT side as per existing size, shape and specification for 11/0.433 KV transformer (Outdoor / Indoor type) of capacity not exceeding 160 KVA complete all as specified
Supply and replacing of Ceramic Bush insulators with brass spindle rod complete with cork sheet gasket, washers, nuts and check nuts on HT side as per existing size, shape and specification for 11/0.433 KV transformer (Outdoor / Indoor type) of capacity 200 KVA to 400 KVA complete all as specified
Supply and replacing of Ceramic Bush insulators with brass spindle rod complete with cork sheet gasket, washers, nuts and check nuts on LV side as per existing size, shape and specification for 11/0.433 KV transformer (Outdoor / Indoor type) of capacity not exceeding 160 KVA complete all as specified.
Supply and replacing of Ceramic Bush insulators with brass spindle rod complete with cork sheet gasket, washers, nuts and check nuts on LV side as per existing size, shape and specification for 11/0.433 KV transformer (Outdoor / Indoor type) of capacity not exceeding 200 KVA to 400 KVA complete all as specified and as directed.
Supply and replacing of Cork Sheet Gasket of 6 mm thick size/shape for top cover of transformer upto capacity 63 to 400 KVA complete all as specified and as directed.
Supply & Fixing in replacement Air Breather Assembly of metallic body complete filled with fresh blue coloured silica gel suitable for indoor/out door type transformer of capacity 63 KVA to 400 KVA complete all as specified and as directed.
Supply and replacing of fresh Silica Gel in Breather Assembly of transformer all as specified and directed.
Spray Painting of Indoor / Outdoor type Transformer, of capacity upto 100 KVA, with one coat of weather proof grey synthetic enamel paint after cleaning / removing dust, rust or carbon etc. including writing MES No / SM No complete all as specified and as directed.
Spray Painting of Indoor / Outdoor type Transformer, of capacity 150 KVA to 400 KVA, with one coat of weather proof grey synthetic enamel paint after cleaning / removing dust, rust or carbon etc. including writing MES No / SM No complete all as specified and as directed.
Disconnecting / dismantling carefully primary & secondary HT / LT connection of unserviceable/ serviceable out door/indoor type Transformer upto 400 KVA complete its foundation/substation and safely shifting one sub station to another sub station as directed by Engr-in-Charge and reconnection of cabling, earthing, install testing and commissioning of the Transformer complete all as specified and as directed. Note : Cost of necessary Tools and Plants such as Vehicle, Hydra / Crane etc. should be deemed to be included in the unit rate quoted.
M&L for complete rewinding of unserviceable off load burnt transformer of HV copper coil and LV copper coil using proper size DPC super enamelled copper winding wire of appropriate gauge and grade, with insulation material suitable for 11/0.433 KV transformer capacity upto 250 KVA including repair/replacement of damaged core also taking out carefully burnt unserviceable copper winding of coils & core complete all as specified and directed. Notes : 1. Cost of necessary tools and plants and transportation to workshop and return back at site using Vehicle, Hydra / Crane etc. shall be deemed to be included in the unit rate quoted. 2. Safety of Transformer during repair shall solely be the responsibility of contractor and any damaged caused to transformer during the operation of repair or in transportation shall be made good by contractor at his own and no claim for any expenditure on this account shall be entertained during execution of work or later stage.
3. The bidder shall arrange Joint Inspection at Work shop with MES Rep (JE E/M /AGE E/M). 4. Installation of Transformer on locations as directed by Engr-in-Charge on existing HT Pole Structure/ Plinth and making all HT / LT and earth connections including testing the Transformer on full load for three hours and on 10% extra load for two hours complete all as directed.
All as per the description of Serial Item No 70 here-in-before but capacity 300 KVA to 400 KVA compete all as specified.
Carrying out calibration of Air Circuit Breaker 630 Amps, over fault relay, earth fault relay, checking of alignment of ACB isolating contacts, servicing of electronic operating mechanism including tripping and closing system of the breakers, dehydrating, decarbonising of panel, bus section & circuit section removing perished monoplus compound cleaning and re-insulating with LT taps wherever necessary, and including replacement of burnt out/defective spares like tension springs, torsion springs, nut bolts, washers of suitable size, lingers etc., under the supervision of authorised dealer / representative, and refixing the ACB breaker in its original position and testing entire satisfaction of Engineer -in- Charge .
Supply and fixing 11000 Volts HT Dropout Fuse element 10A to 60Amps all as specified and directed.
Supply and laying / spreading for loose filling of Hard core of broken stone or boulders of gauge 40 to 80mm at Electrical Sub Station 04 Pole / 02 Pole Structure complete all as specified and as directed.
High voltage PVC insulating Mat 3 mm thick to withstand the current leakage upto 11 KV laid in HT electrical installation by using company recommended adhesive, ISI Marked, CM/L : 8963811, conforming to IS:15652 complete all as specified and directed.
PCC (1:4:8) type D-2 using 40 mm graded stone aggregate as in coping of HT Poles 04 / 02 Pole structure / Single poles including necessary form work where required and fair finishing to the exposed surfaces and two coat of White wash including dismantling work all as specified and directed.
Supply and mounting on wall with necessary fixing arrangement Sign Board 3.00 m x 1.00 m x 0.30 m fabricated with aluminium frame with acrylic sheet duly written "11 KV SUB STATION AGE B/R (AF) DALHOUSIE" with bold letters reflective tape on acrylic sheet as approved by Engr-in-charge including 02 Nos, 04 feet 20 watts LED Tube light fitting wiring with 1.5 Sqmm size copper conductor and making connections all as specified and directed.
Dismantling bent / tilted HT Electric Poles any type 11 metre long including taking down by demolishing the PCC/coping and re-erecting the Pole in true vertical position including all necessary electric connections and T&P complete all as directed. Notes : 1. Quoted Rate shall include cost of Excavation, disconnecting of conductor, cross arms and insulators etc. 2. The PCC for foundation and coping shall be measured and paid seperately.
Excavating in trenches, not exceeding 1.5metre wide and not exceeding 1.5metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Excavating in trenches, not exceeding 1.5metre wide and exceeding 1.5metre depth but not exceeding 3.0metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick any type of soil, complete all as specified and directed.
Removing excavated soils to a distance exceeding 50m but not exceeding 100m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Cement concrete type D-2 1:4:8 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type C-2 1:3:6 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, complete all as specified and directed.
Cement concrete type B-1 1:2:4 (using 20mm graded crushed stone aggregate) as in coping of poles, complete all as specified and directed.
Stay tightening for HT / LT Pole any type using necessary T&P as required on site and as directed.
Stay assembly set complete with accessories like stay rod / strand / plate, Loop type insulator, clamps, excavation, concreate etc for LT / HT pole any type using necessary T&P as required on site and as directed.
Tubing GI light grade 50mm bore for cable protection laid in ducts, fixed to wall or poles including fixing arrangement all as required and directed.
M/s Shakti Electric Works
Vijay Kumar Contractor and Engineers
dinesh enterprises
Bidder Name
Vijay Kumar Contractor and Engineers
dinesh enterprises
M/s Shakti Electric Works
M/S SATPAL & BROTHERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .