Executive Engineer (E), BSNL Elect Divn Kolhapur
BSNL Electrical Division, Third Floor, City Telephone Exchange, Near Pudhari Press Office,Kolhapur416002
Rate Contract for maintenance of Engine Alternator at various TE Bldgs and BTS sites under Solapur SSA
2022_BSNL_121590_3
e20/EEE/BSNL/KPR/22-23
Open Tender
Electrical Works
Item Rate
365 days
Solapur
Please refer Tender documents.
14 documents required · 14 mandatory
₹590
Yes
BSNL Kolhapur
₹48,983
Yes
24 Nov 2022
17 Oct 2022
17 Nov 2022
17 Oct 2022
16 Nov 2022
17 Oct 2022
Amount
Attending breakdown call and rectification of EA 7.5 KVA to 62.5 KVA set faults including providing minor spares if reqd such as connecting copper wires, removing air from fuel pump, control fuse, ferrules, lugs i/c minor works etc etc alongwith testing & commissioning etc. complete as required . (Note:- Allowed only once per site per fault. For subsequent visit to attend the DG set to provide the items hereunder will not be paid separately. It is assumed that all items as below shall be carried out by firm in first visit only). The distance for the visit shall be measured from the subDivision Head Quarter.
Upto 50 KM
From 51 KM to 100 KM
Above 100 KM
Carrying out 'B' Check servicing of following capacity E/A sets located at various T.E. Bldg / BTS under under Kolhapur SSA including replacement of old engine oil, fuel filter, lubricating oil filter etc. by new as per manufactures recommendation including arranging vehicle, transportation, manpower, tools and tackles, testing etc. as required. (Oil, filters shall be manufacturer recommonded specs) (Note: This item includes visit charges, nothing extra on this account shall be paid)
7.5 KVA to 20 KVA
22.5 KVA to 25 KVA
30KVA to 40 KVA
45KVA -63 KVA
Supplying & filling of coolent in radiator of water cooled EA set etc as required.
Supplying & fixing following spare parts alongwith removing of old items etc.complete as required.( Make- Recommended by manufacture/BSNL makes only. ) (Note :- The agency shall consider suitable credit for recovered spares while quoting rates )
A) Above 7.5 KVA TO 32.5 KVA
Repairs of self starter i/c replacement of spares / winding etc as required
Repairs of charging alternator i/c replacement of spares / winding etc as required
Fuel pipe steel braded with banjo bolt ( feed pump to fuel filter )
Fuel pipe steel braded with banjo bolt ( Pre filter to tank unit )
Fuel pipe steel braded with banjo bolt ( Fuel filter to FIP )
Automatic voltage regulator (AVR)
Fuel Pump and Injectors servicing and caliberation only from authorised dealer with test report
V belt ( A46)
V belt ( A56)
B) Above 32.5 KVA TO 62.5 KVA
Repairs of self starter i/c replacement of spares / winding etc as required
Repairs of charging alternator i/c replacement of spares / winding etc as required
Fuel pipe steel braded with banjo bolt ( feed pump to fuel filter )
Fuel pipe steel braded with banjo bolt ( Pre filter to tank unit )
Fuel pipe steel braded with banjo bolt ( Fuel filter to FIP )
Automatic voltage regulator (AVR)
Fuel Pump and Injectors servicing and caliberation only from authorised dealer with test report
Repairing of Engine Alternator sets by supplying & fixing following spare parts alongwith removing of old units etc.complete as required.( Make- Recommended by manufacture/BSNL makes only.)
a) SMPS 12 volt, 10 Amp Battery Charger
b) 88 Ah, 12 volt Battery
c) 150 Ah, 12 volt Battery
Supplying and Fixing of Super Capacitor module for DG set Starting complete with connections , testing and commissioning complete as required.
d-i) 120 F, 12 volt
d-ii) 180 F, 12 volt
e) 15 W 40 Lubricating oil for topping up in EA set ( Only recommeded make )
f) Set of end socket with copper lugs for DG starting battery
g) S/F of 2 nos 35 sqmm copper flexible lead (approx.1.0 Mtr) for DG starting battery
h) ON/OFF push button
i) Starting switch with key
j) Radiator Hose kit
k) Mains/DG contactor
l) Stop solenoid
m) 63 amps. ratings , TPN MCB, “C” curve,10 KA breaking capacity
n) Hour Meter
Overhauling & Reconditioning of radiator of up to 32.5 KVA DG set which includes Dismantling the complete radiator fan assembly from the engine, dismantling radiator assembly, transporting to workshop, pressure testing, tracing the leakage in the tube, attending & repairing of leakages, brazing, welding damaged sections, cleaning of all fins with air pressure, cleaning of rusted portion of radiator, Servcing & cleaning of whole radiator, providing anti rust coating, hydraulic pressure testing, and refixing of radiator assembly , tesing & trial run of DG set etc. complete as required.
Overhauling & Reconditioning of radiator of above 32.5 KVA to 62.5 KVA DG set which includes Dismantling the complete radiator fan assembly from the engine, dismantling radiator assembly, transporting to workshop, pressure testing, tracing the leakage in the tube, attending & repairing of leakages, brazing, welding damaged sections, cleaning of all fins with air pressure, cleaning of rusted portion of radiator, Servcing & cleaning of whole radiator, providing anti rust coating, hydraulic pressure testing, and refixing of radiator assembly , tesing & trial run of DG set etc. complete as required.
Dismantling,Shifting and transportation of following DG set with accoustic enclosure/RTU, DG set without enclosure, Control Panel and all other associated accessories including loading, unloading at both ends, hiring of vehicle, arranging manpower, tools and tackles, lifting arrangement by hydra/crane etc. complete as required.
a) Upto 30 KM
b) From 31KM to 60 KM
c) From 61 KM to 120 KM
Installation,Testing and commissioning of E/A sets alongwith accoustic enclosure/RTU, DG set without enclosure on existing foundation/ location and fixing existing earthing strip , welding the silensor strip,cable connections with earthing complete with testing & trial run test on existing load for 3 hrs etc complete as required.( Note The diesel / consumable for trial load test shall be supplied by BSNL )
a) Upto 20KVA
b) 20 KVA to 32.5KVA
c) 45 KVA to 62.5 KVA
Supplying and Laying of one number PVC insulated and PVC sheathed / XLPE armoured aluminium conductor power cable of 1.1 kV grade of following size in folllowing manner etc. as required. a) 3.5x 25 sqmm ( ISI Mark)
a) on wall surface as required.(clamped with 1mm thick saddle)
b) In hume /RCC/Metal pipe as required
c) In air / on pole alongwith 6 SWG GI wire with clamping.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
Supplying & laying 6 sq. mm. multistrand copper conductor flexible cable for neutral earth connection i/c Providing & fixing copper lugs etc as reqd (Make : Havells/ polycab/ss) (ISI mark) (For Engine Neutral earthing)
Supplying and laying of 40 mm. Dia. "A" Class G.I. pipe atleast 300mm deep from ground level including excavation,repairing with cement concrete,finishing,curing etc as required.
Providing and making locking arrengement to existing salient canopy door complete with welding of MS sections/ Fixing hinges / steel aldrops with providing lock having 3 set of keys including drilling holes fixing of roofing bolts, nuts and washers etc.as required.
SHII ( Credit for dismantailed material)
Suitable credit to the old dismantled battery of following capacity
i) Upto 88 AH
ii) Above 88 AH to 150 AH
JAYSHREE SALES & SERVICES
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .