Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.2 LAccepted-AOC 28 DOCTOR LANE | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹6.3 L+₹16,404 (2.66%)Rejected-Finance | L2 | Rejected-Finance Bidder is not L1 | |
| 3 | L3₹6.9 L+₹75,222 (12.2%)Rejected-Finance 49 1 ISWAR GUPTA ROAD KOLKATA 700 028 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700028 | L3 | Rejected-Finance Bidder is not L1 |
Tender Value
Refer Docs
EMD Value
₹15,399
Closing Date
25 Nov 2024, 2:00 pmClosed
Executive Engineer-I,CKHED,PWDte.
Central Kolkata Health Electrical Division, P.W.Dte. P-5, CIT Road, 2nd Floor, Moulali, Kolkata 700 014.
Special Repair and Renovation work of Electrical Installation at 63, A.P.C Road Campus, Kolkata -700009 of D.N.De Homoeopathic Medical College and Hospital.
2024_WBPWD_765632_1
WBPWD/EE-I/CKHED/eNIT-71/24-25
Open Tender
ELECTRICAL WORKS ORG
Item Rate
45 days
D.N.De Homoeopathic Medical College Hospital.
Please refer Tender documents.
3 documents required · 3 mandatory
₹15,399
P-12, CIT ROAD.KOLKATA-14
11 Apr 2025
28 Oct 2024
27 Nov 2024
28 Oct 2024
25 Nov 2024
5 Nov 2024
5 Nov 2024
Amount
A. SPNDB, TPNDB, VTPNDB etc.
Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. (Make: Legrand/L&T) [Ref : D-9/13]
Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment (Make:Legrand/L&T) [Ref.- D-10/14]
Supplying and fixing double door sheet steel (16SWG), powder coated cable end box for TPN DB horizontal / vertical enclosure with IP-42/43 protection, on angle iron frame on wall & mending good the damages to original finish with nuts bolts etc incl. provision for earthing attachment. [Ref.- D-12/16]
4 /6 Way HTPN
Supplying and fixing 240/415 V MCB Isolator on din rail of existing DBs and necessary connection. (Make: Legrand/L&T) [Ref.- D-5/6]
Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Make: Legrand/L&T) [Ref.- D-6/7]
6-32A, SPMCB
B. Separate Socket Switch Board
Supply & Fixing 240 V, 4 nos. 6 A, 3 pin Modular type plug socket with 4 nos. 6A Modular type switch (Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series), 16A Modular switch type MCB (C-Curve) and Indicator without plug top on 2 row 18 Module GI Modular type switch board with 2 row 18 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc. (For computer board) [Ref.- E-18/12]
Supply & Fixing 240 V, 2 nos. 6 A, 3 pin Modular type plug socket with 2 nos. 6A Modular type switch (Make:- Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series), without plug top on 6 Module GI Modular type switch board with 6 Module top cover plate flushed in wall incl. S&F switch board and cover plate and making necy.connections with PVC Cu wire and earth continuity wire etc.(For mobile charging point and water purifier point) [Ref.- E-17/1(b)+3(a)+4(a)]
Supply & Fixing 240 V, 16 A, 3 pin Modular type plug socket with 16A Modular type switch (Make:- Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series), without plug top on 4 Module GI Modular type switch board with top cover plate flushed in wall incl. S&F switch board and cover plate and making necy. connections with PVC Cu wire and earth continuity wire etc. (For Gyeser) [Ref.- E-18/9(b)]
C. Distribution Wiring & Point Wiring
Distn. wiring in 3 x 1.5 sq. mm single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make:- Finolex/ Havells/ Polycab/ RR Kabel/ Gloster) in 19 mm bore, 3 mm thick polythene pipe complete with all accessories embedded in wall to light/fan/call bell points with Modular type switch (Make:- Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series) fixed on Modular GI switch board with top cover plate flushed in wall incl. mending good damages to original finish. 2 x 1.5 (Ph. & N) and 1 x 1.5 as ECC. [Ref.- E-20/1(iii)]
Averag run - 8 Mtr.
Distn. wiring in 3 x 1.5 sq. mm single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make:- Finolex/ Havells/ Polycab/ RR Kabel/ Gloster) in 19 mm bore, 3 mm thick polythene pipe complete with all accessories embedded in wall to 240 V 6A 5 pin plug point incl. S&F 240 V 6 A 3 pin Modular type plug socket & Modular type switch (Make:- Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series) incl. S&F earth continuity wire, fixed on 4 Module GI switch board with 3/4 Module top cover plate flushed in wall incl. mending good damages to original finish. [Ref.- E-20/3]
On Board
Average run 4.5 mtr
Supplying and Drawing 1.1 KV single core stranded 'FR' PVC insulated & unsheathed single core stranded copper wire (Make:- Finolex/RR Kabel/PolyCab / Gloster/ Havells) of the following sizes in the prelaid polythene pipe and by the prelaid GI fish wire and making necy. connection as required [Ref : E-9/1]
3x22/0.3 (1.5 sqmm)
2x36/0.3 (2.5 sqmm) + 1x22/0.3 (1.5 sqmm) as ECC
2x56/0.3 (4 sqmm) + 1x36/0.3 (2.5 sqmm) as ECC.
2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC
4x80/0.4 (10 sqmm) + 2x84/0.3 (6 sqmm) as ECC
Cutting Channel of size (40 mm x 40 mm) on masonry wall by Electric operated cutting machine incl. supplying & fixing heavy gauge 19 mm, 3 mm thick Polythene pipe by means of anchoring chemical (Hilti/Sika) and GI 'U' hooks of 8 SWG incl. supplying and drawing 18 SWG GI wire as Fish wire and mending good damages to original finish by using own tools and tackles. [Ref : E-3/6(a)]
19 mm dia 3 mm thick polythene pipe without earth continuity wire
Supplying & Fixing sheet metal inspection box (16 SWG) of the following sizes flushed in wall by housing the same after cutting brick wall incl. making earthing attachment, painting and mending good damages to building works. [Ref : E-4/11(b)(c)]
150 mm x 100 mm x 65 mm
175 mm x 100 mm x 65 mm
Supply & Fixing bakelite / perspex top cover on existing switch board by Brass screws after making housing for switch by cutting bakelite / perspex cover and making necessary connections as required. [Ref : E-4/12(b)(c)]
150 mm x 100 mm x 65 mm
175 mm x 100 mm x 65 mm
Finishing of the PVC insulated wire ends by socketting with pin/ring type copper sockets and insulated tapes etc., including supplying sockets, tapes. [Ref : F-5/9]
3 x 1.5 sq. mm
2 x 2.5 sq. mm + 1 x 1.5 sq. mm
2 x 4 sq. mm + 1 x 2.5 sq. mm
2 x 6 sq. mm + 1 x 4 sq. mm
4 x 10 sq. mm + 2 x 6 sq. mm
D. Indoor Lighting
S&D of Single LED Tube light fitting along with 1 no. MAS LED (PC body) Tube 1200mm delivering minimum 100 lumen/watt [Make:- Philips, Batten Cat No.- TMC100 1xTLED 13-20w WH & Tube light Cat No.- 18W 865 T8 I – 2100lm or Crompton, Batten Cat. No.- IGP161LT8-16 1 x T8 & Tube light Cat No.- LTB-20-865-(2)].
S&D of Twin LED Tube light fitting along with 2 nos. MAS LED (PC body) Tube 1200mm delivering minimum 100 lumen/watt [Make:- Philips, Batten Cat No.- TMC100 2xTLED 13-20w WH & Tube light Cat No.- 18W 865 T8 I – 2100lm or Crompton, Batten Cat. No.- IGP162 LT8-16 2 x T8 & Tube light Cat No.- LTB-20-865-(2)]
S&D of 240V,1-Ph.,50Hz 10W White colour LED Bulb (Make : Philips / Crompton)
Fixing only single/twin fluorescent light fitting suspended 25 cm bellow the ceiling with 2 No. 20 mm dia EI conduit (14 SWG) supports fixed with “L” type MS clamp whose one side fixed on ceiling with sutable size 4 nos. fastener and other side connected with the conduit with suitable size of bolts and nuts incl. S&F EI conduit, “L” type (125mmx125mm) 6mm thick and 25mm with MS clamps and connecting the length of PVC insulated wire and mending good damages to original finish and painting etc. by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [Ref : C-2/17]
Fixing only single / twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener. [Ref : C-2/14(b)]
Fixing only lamp to batten point. [Ref : C-2/11]
Extra for suspension exceeding 25 cm with S&F additional 2 no. 20 mm dia EI conduit (14 SWG) supports & necy. PVC insulated wire and painting etc. as required by 2x24/0.20 mm (1.5sqmm.) flexible copper wire of 1.10 mt. length. [Ref : C-2/16]
E. Ceiling Fan, Exhaust Fan, Air Circular Fan etc.
S&D of 240V,1-Ph., 48" (1200mm) sweep, high speed AC ceiling fan, the capacitor of fan must be P-2 type brust proof & must have safety wire directly linked from fan hook to stator of fan. including safety wire and complete with all accessories like blade, canopy, downrod etc. (Make:- Crompton Riviera Hi Speed/ Orient-Quassar/ CG Aura metallic) Colour:- Brown/ Metallic Ivory Cherry.
S&D of 240V,1-Ph.,50Hz, 18''(450mm) Sweep, full metal body with metal blades Wall Bracket Type Heavy Duty Air-Circular Fan. [Make:- Crompton 450mm ACVORTEX18WM/ Usha 450MM DOMINAIRE WALL FAN/ EPC]
S&D of 240V,1-Ph.,50Hz, full metal body with metal blades AC Exhaust Fan complete with all accessories. [Make:- EPC]
9'' [40Watt, 1370RPM]
Supplying & Fixing MS fan clamp of two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting – (As per Drawing no. 475 of PWD Specification Book – May 1991) [Ref : D-14/29]
Supply & Fixing 240V, Modular Socket (2 Module) type fan regulator (Step type) (Make:- Legrand, Model- Arteor or Myrius/ Anchor, Model- Woods/ Havells, Model- Oro Series) on existing Modular GI switch board with top cover plate incl. making necy. connections etc. [Ref : E-18/10]
Fixing only ceiling fan complete with blades, canopy, fork, rubber bush etc. incl. S&F connecting wire for down rod upto 30 cm incl. painting the rod with approved paint and making necessary connection as required by 2x1.5 sqmm flexible copper wire. [Ref : C-3/21(a)]
Engraving the deptt. number with 10 mm lettering on the body of fan upto 10 letters incl. hifen, stroke or stop. [Ref : C-3/24(a)]
Extra for additional one letter incl. hifen, stroke and stop. [Ref: C-3/24(b)]
Painting upto 10 letters of the engraved number with approved black /red paint as required. [Ref : C-3/26(a)]
Extra painting for additional one letter of the engraved number with hifen, stroke etc. with black or red paint. [Ref : C-3/26(b)]
Fixing only cabin fan on wall/ceiling by S&F rag bolts, nuts & washers (6 mm dia x 62 mm long) or as reqd. incl. S&F 24/0.20 PVC insulated flexible copper wire 0.5 mt. length. [Ref : C-4/29]
Fixing only exhaust fan after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection for exhaust of following diameter: [Ref : C-4/28(a)]
Supply & Fixing Al. louver shutter on wall with necy. bolts & nuts (6 mm dia x 62 mm long) [Ref : D-14/32(a)]
23 cm Exhaust fan (9")
F. Miscellaneous
Supplying & Fixing 240 V AC/DC superior type Ding-Dong Call Bell (Anchor) on HW board incl. S&F HW board. [Ref : D-13/20(a)]
G. Earthing
Earthing with 50 mm dia ISI-Medium GI pipe 3.64 mm thick x 3.04 Mts. long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. below the ground. [Ref : G-1/2(a)]
Excavation of soil for installation of Earth Electrode and filling & ramming. For Morrum Soil [Ref : G-1/1(b)]
Extra for treatment of soil by using salt & charcoal or coke for plate electrode [Ref : G-2/3(b)]
Extra for providing masonery enclosure on the top of the earth electrode of overall size 86.36 cm x 86.36 cm x 46 cm deep (below Ground level) complete with cemented brick work(1:6) of 25 cm width duly plastered with cement morter (inside) CI hinged inspection cover of size 36.56 cm x 35.56 cm with locking arrangement, GI reducer including drilling of 46 nos. 12 mm dia holes on the GI pipe. [Ref : G-2/3(a)]
Supplying & fixing earth busbar of galvanized (Hot Dip) MS flat 50 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as required. [Ref : G-2/4(c)]
Connecting the equipments to earth busbar including S & F GI (Hot Dip) wire of size as below on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required and mending good damages. Stranded GI wire-7/14 SWG [Ref : G-2/5(b)]
Connecting the equipments body to earth busbar including S & F 25 mm x 6 mm galvanised (Hot Dip) MS flat on wall/floor with GI saddles as required and connection to equipments incl. drilling holes, with bolts, nuts, washers etc. [Ref : G-3/5(d)]
H. Outdoor Lighting
Fixing only outdoor / street light type fluorescent light fitting or MV light fitting complete with all accessories to be fixed /projected from the wall of the building incl. making holes/providing clamping arrangement & necy. GI reducer as required. S&F 40 mm GI pipe (ISI-Medium) quality 1.5 mts. average length having suitable bend S&F necy. length of 1.5 sqmm PVC insulated single core stranded annealed copper wire and making connections as required and mending good damages to wall incl. painting etc. [Ref : C-3/18]
Supplying & Fixing GI waterproof type looping cable box size 200x150x100 mm deep having 4 mm thick comprising of one 250 V 15 A kit-kat fuse unit, one NL on porcelain insulator, one compression type brass cable gland for upto 2- core 16 sqmm PVC/A cable and having lined with rubber gasketted GI top cover with brass machine screws etc., earthing terminal with lug, on steel tubular pole near base, including S&F 40x6 mm thick, MS clamps with bolts, nuts etc. including painting with anticorrosive paint. [Ref : H-5/5]
S&D of 240V,1-Ph.,50Hz LED street light delivering minimum 110 lumen/watt including IP66 protection and complete with all accessories. [Make:- Philips City Star Street Light, Cat No.- BRP331 LED54 CW R5N PC PSU S1 V1 or Cromptom RAPTOR PRO, Cat No.- CRP-409-45-57-SL-GL-NSG]
Supply and fixing of 1 phase timer control box for controlling AC machines made following accessories with IP - 42/43 protection with front door locking arrangement with all connection on angel iron frame on wall as per instruction of EIC.
a) 2+10 way size double door SPN MCBDB--1 No. (LK)
b) 240/415V, AC 32A, 2P Power contactor type MNX22-2P (Make-LK) - 1 No.
c) Daily & weekly programmable basis Digital Timer Switch, min switching time 1 min, ON/OFF programs- 1 no.(LK Cat no. - 67DDT0)
d) 240/415V, 40A, DP MCB Isolator (Make:Legrand) 1 no
e) 3 way Auto manual toggle switch--1 no.
f) ON/OFF LED indicator - 1 set
g) ON/OFF push button - 1 set.
h) Interconnection by 2.5 sqmm Cu wire--3 mtr.
Supply & Laying of 1.1 kV grade 2 Core 10 Sqmm XLPE/PVC insulated armoured Al. LT cable after cutting floor/pavement/wall/ and making holes incl., embedding the cable at an average depth of 75 mm in floor/pavement/wall etc. and mending good the damages to original finish incl. removing the rubbish. [Make : Finolex/Polycab/Havells/Gloster/RR Kable/ KEI/ Mescab)
Supplying and fixing compression type gland complete with brass gland, brass ring & rubber ring for dust & moisture-proof entry of XLPE/PVC armoured cables as below [Ref : F-4/7(a)]
For 2 Core 10 Sqmm
Finishing the end of following XLPE/PVC armoured cables by crimping method incl. supplying and fixing solderless socket (Dowels make), tapes, anticorrosive paste & jointing materials [Ref : F-5/8(b)]
2 core 10 sqmm cable
Rate should be quoted incl. of all taxes and cess.
Defect Liability period : 1 year
JISCO METALAS (BID ID -5769370)
Electromech Engineers Co-Operative Society Ltd. (BID ID -5750476)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .