Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹16.0 LAccepted-AOC 8 51 PLOT NO 6 LIC COLONY SUJATA NAGAR PENDURTHY MANDAL VISAKHAPATNAM 530042 AP | 530042 | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹16.9 L+₹55,162 (3.38%)Rejected-Finance | L2 | Rejected-Finance Not lowest Bidder | |
| 3 | L3₹19.9 L+₹3.6 L (21.9%)Rejected-Finance | L3 | Rejected-Finance Not lowest Bidder | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlishted in cat b(ii) |
Tender Value
₹19 L
EMD Value
₹38,000
Closing Date
4 Oct 2024, 6:00 pmClosed
CWE NO 02 SECUNDERABAD
HQ CWE NO 02 SECUNDERABAD MUDFORT ROAD SECUNDERABAD 500003
REPAIRS MAINT OF SOLAR FENCING ALONGWITH ALLIED WORKS OF GUARD ROOMS UNDER GE MCEME
2024_MES_672867_1
81232/E8
Open Tender
Civil Works
Item Rate
180 days
MCEME SECUNDERABAD
As per tender documents
9 documents required · 9 mandatory
₹500
GE MCEME SECUNDERABAD
₹38,000
Yes
21 Nov 2024
6 Sept 2024
10 Oct 2024
7 Sept 2024
4 Oct 2024
20 Sept 2024
Amount
Taking down the exsting fen controller and its connected accessories complete all as specified and directed by Engineer- In-Charge.
Supply and fixing Fence controlled operating voltage 12V, 75 Watt peak, Solar DC, Voltage input 12V, 100AH, DC battery back up each fence controller having energizers all as specified and directed to achieve the following parameters:- a) Nominal operating voltage shall be between 6000V to 10000V. b) The pulse interval shall be of 1.2 second. c) The pulse duration shall be less than 03 millisecond. Note :- (i) Warning and alerts shall be configured for system fault, serious breach and pulse count. ii) LCD display which displays: battery voltage, output voltage each zone, fault/alarm each zone. iii) The makes of the component / parts of solar fencing shall be as per manufacturer's requirement and shall be of same company as for as possible except batteries. iv) Battery shall be measured & paid separately Make: Silicon Solar System / Radiant Energy Technologyy
M&L Alarm device operating on 12V having audibility of 125 Db noise level, alarm must turn ON automatically at all the field controller locations when fence is damaged or voltage drop complete all as specified and direced. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Intermediate security post 25 mm Square tube x 2mm thick and hot dip galvanised to minimum 70 microns with fixed Insulators clamping riveting (1.3 M height, 10 line configuration) suitable to fix on intermediate post assembly complete all as specified and directed by Engineer- In-Charge.Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Fixed insulators made of high density polyethylene UV stabilised having a breakdown voltage of not less than 15 KV and having a shield to prevent arcing between wire and post with glossy surface to prevent accumulation of dust and facilitate cleaning, the construction and design of the insulator shall be such that it will facilitate triggering of an alarm in the event of an intruder attempting to climb, intermediate insulators shall have two wire retaining lugs that shears and breaks upon a load of 30 to 40 Kgs complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of End post assembly 1.3 M design comprising of (a) Main post: 1.3 metre high (1.0+0.3 M for grouting) 40mm Square tube mild steel pipe ISI marked 3mm thick with 70 micron hot dip galvanising, (b) Support post: 1.3 M long, 25mm Square mild steel pipe ISI marked 2mm thick with 70 micron hot dip galvanising, with suitable fixing mechanism complete all as specified and directed by Engineer- In-Charge. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Fixed insulators Clamps with 70 microns with steel riveted complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of End strain hooks hot dip galvanised upto 30 microns facilitate fixing strain insulators and tensoners complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of End strain insulators of high impact, high strength UV polycarbonate material virgin grade capable of withstanding upto 15 KV and shall not allow power leakage complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Joint clamps of Zinc Plating with silver passivation MS material, fastener shall facilitate firm connection of fence strand size upto 4mm complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Concealed fence configuration link bus bars made of 12SWG HT wire bus bar connectivity achieved by metal GI completely to offer highest security, link bus bars used for configuring/looping the power fence at end posts and corner posts complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
S&F in replacement of Wire Tighteners made of GI with Aluminium runner to facilitate tensioning of fence strands in both directions and shall have firm locking mechanism complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
Fixing only High tensile wire of 2.59mm dia with zinc coating of 280 GSM, corrosion resistant, having UTS of 140 Kg/sq.m, as per IS 398 complete all as specified and directed. Note : Wire shall be issued under Schedule 'B' free for fixing.
S&F HV double insulated cable made of two layer insulation, outer insulation of abrasion resistant HDPE and inner insulation of polypropylene, core shall be of 2.5mm galvanised steel, the diameter with inner insulation shall be 4.1mm and the diameter of the cable with both insulation shall be 7.6mm for inter connection between the fence controller and power fence complete all as specified and directed. Make:- Arrow Cable/Unicab/Finecab
M&L for PCC (1:3:6) type C-1 using 20mm stone aggregate in foundation of fencing poles including necessary formwork fair finished and finishing the exposed surfaces even and smooth without using extra cement complete all as specified and directed.
Removing, Re-Installation and commissioning tightening of the loose solar power fence (10 Lines Fence) complete all as specified and directed. Note :01 span equal to distance between two poles
Trimming of trees along the solar fence on the basis of daily wages for one person per day complete all as specified and directed by Engineer- In-Charge.
S&F in replacement of 20/25 mm dia Rigid non-metallic PVC conduit exclusive of boxes (junction/ terminal) but inclusive of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified and directed by Engineer- In-Charge. Make : Finolex/Precision/Sudhakar
Taking Up/down super earth kit with all accessories complete all as specified and directed by Engr in Charge
M&L for Super earth kit comprising of non rusting 304 grade stainless steel rod of 10mm dia inserted in moisture absorbent chemical mixture , earth kit weighing minimum 4kg, 4feet long, fastening assembly shall be of hot dip galvanised and made of stainless steel complete all as specified and as directed.
M&L in repair solar module mounting arrangement pole with mounting structure with hardware 35x35x3mm thick angular iron "H" frame , 2"dia 8 feet long pole and angle adjustment mechanism 2 core cable for solar module to fence system complete all as specifiedand directed
M&L for Power supply unit for DC power supply 12 / 18 Volt DC 3 Amps complete all as specified and directed Make: Silicon Solar System / Radiant Energy Technologyy
Suply in replacement of Battery 12Volt, 100AH maintenance free battery complete all as specified and directed. Make : Exide/ Luminous/ Amaron
Supply and replacement of outdoor console rack made of 3.15mm thick CRCA sheet suitable for extensive outdoor application compling with IP55 standard for housing fence controller, battery, automatic voltage regulator, power supply board etc with suitable power supply distribution ON OFF control switchess and internal wiring with suitable lock and key arrangement and including suitable mild steel angle iron frame including suitable PCC work complete all as specified and directed.
M&L for Digital voltmeter pocket size hand held device for measuring the fence voltage capable of displaying fenced voltage upto 10 KV, having auto turn facility when controller pulse is detected complete all as specified and directed. Make: Silicon Solar System / Radiant Energy Technologyy
M&L for LED Live light capable of flashing a thin visible momentary light with each pulse emitted by the controller complete all as specified and directed. Make : Silicon solar systems (SSS) /Radiant Energy Technology.
M&L for Lightening diverter capable of diverting stray lightening from fence to earth complete all as specified and directed. Note: Lightning diverter shall have the provision for adjusting the spark gap. Make : Silicon solar systems (SSS) /Radiant Energy Technology.
M&L for Servicing/striping off transformer 11 KV/ 0.433 KV step down capacity 63 KVA, draining out oil, preserving in container for refill, lifting the core and coil assembly, washing, cleaning dust, dirt and sludge etc., deposited on all parts, replacement of damaged/defective parts, making internal connection, servicing of tap changer and reassembling the transformer including new cork sheet, gasket, nuts, bolts and washer etc and arrest the oil leakages as required check the dielectric strength of transformer oil and refilling transformer oil, testing and commissioning complete all as specified and directed by Engineer- In-Charge.
Filtration, decarbunisation and dehydration of insulating oil of transformer in position without disrupting power supply to achieve required dielectric breaking strength of transformer oil 45 KV per min including testing and tabulate test result complete all as specified and directed by Engineer- In-Charge.
M&L for Insulating (transformer) oil conforming to IS-335 for filling, toping up of transformers duly filtered having diclectric breaking strength 45 KV for one minute complete all as specified and directed by Engineer- In-Charge.
Dismantling burnt / defective Gang Operated Switch keeping away from site , Supply & install 11 KV 3 Phase Gang operated air break switch with drop out fuses set ( consisting 12 Nos Post Insulator ) 400 amp capacity, vertical mounting with fixed and moving contacts complete with locking arrangement and fixing the gang operated switch on existing two/four pole structure including making all jumper connections with insulated leads of suitable size with line tops etc, all as specifed and directed. Make:- Jaipuria Bros/BHEL/ATLAS/PACTIL
Maintenance and repair to gen set 63 KVA, water cooled with alternator and general maintenance including changing of lub oil, coolent, diesel filter, oil filter, air cleaner, outer element, cleaning of fuel tank & required maintenance services and replacement the following parts :- (a) Lub oil changed grade 15/40. Make : Servo (b) Diesel filter element © Oil filter element (d) Water coolent. (e) Air filter inner assembly (f) Cleaning of air filter outer assembly all as per suitable existing shape, size & make.
M & L cable Jointing Kit for 11 KV (Earthed) grade cable for Outoor termination heat shrinkable joint complete with jointing material and accessories suitable for 3 core XLPE Armoured aluminium cable of size 50 Sqmm complete all as specified and directed. Make:- Finolex/Havells/Bajaj
Taking out existing unserviceable 50 Sqmm, 3 core, XLPE insulated screened, PVC Bedded, galvanised steel strip or wire armoured , electric power cables(heavy duty) with aluminium conductor, 11000 volts grade laid in trenches, ducts along the walls, through pipes, under road complete all as specified and directed
Supply and Laying XLPE insulated screened, PVC Bedded, galvanised steel strip or wire armoured, electric power cables(heavy duty ) with aluminium conductor, 11000 volts grade cross sectional area 50 Sqmm 3 Core, laid in trenches, ducts along the walls, through pipes,or fixed on pole etc complete all as specified and directed. Make:- Finolex/Havells/Bajaj
Supply, laying, testing and commissioning of LT UG cable, XLPE insulated, PVC sheathed, galvanized steel strip armoured electric power cable with stranded aluminium conductor, 1100 volts grade of size 50 sqmm 3.5 core confirming to IS:7098 (Part-I), suitable for earthed system, laid in duct/trench/along pole/wall etc including nuts, bolts, washers, saddles & screws etc and making connection, complete all as specified and directed by Engineer- In-Charge. Note : 1. The cost of Al thimbles/lugs and cable gland etc is included in quoted rate and no extra payment will be made for it. 2. Excavation, earth work, sand cushioning and brick protection will be measured and paid separately under respective items. Make:- Finolex/Havells/Bajaj
Taking out old street light of any capacity and replace with new LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65 protection complete all as specified and directed. Make:- Philips/Havells/Bajaj
Taking out old unserviceable/serviceable un-reinforced concrete PCC cable covers of any size from excavated trench of any size all as directed by the Engineer-in-Charge. Note:- Serviceable un-reinforced concrete PCC cable cover kept in safe custody for reuse at site and unserviceable un-reinforced concrete PCC cable cover will be thrown in low lying area complete all as specified and directed by Engineer- In-Charge.
M&L for factory made un-reinforced pre cast concrete cable protection cover HV class type - I with size 300mm x 180mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge.
M&L for factory made un-reinforced pre cast concrete cable protection cover LV class type - I with size 250mm x 150mm x 40mm laid across the cable (i.e. width of cover along the length of cable) for UG cable protection on the top of the sand cushioning, complete all as specified and directed by Engr-in-Charge.
Excavation in trenches in hard / dense soil not exceeding 1.5 mtr in depth and not exceeding 1.5 mtr wide and getting out including trimming of sides, for laying of cables complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning with layer of sand 8cm thick before laying of cable and 10cm after laying of cable in trenches complete all as specified and directed by Engineer- In-Charge.
Returning filling in, including spreading, leveling, watering and well ramming in layers not exc 25 cm thick,complete all as specified and directed by Engineer- In-Charge.
Removing excavated material to a distance not exc 50m and depositing where directed at a level not exc 1.5m above the starting point, complete all as specified and directed by Engineer- In-Charge.
Supply and fix ON LOAD change over switch 415V in sheet metal enclosures 4 pole of capacity 125 Amps complete all as specified and directed. Make:- Havells/Standard/C&S
Supply & Fix MCCB four pole, 100 Amps, 415 Volts, 16 KA complete all as specified and directed. Make:- Standard/Legrend/Siemens
Supply & Fix MCB four pole, 32 Amps, 415 Volts, 10 KA complete all as specified and directed. Make:- Standard/Legrend/Siemens
Earthing complete with galvanised steel earth plate electrode 60cm x60cm x6mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level ) with top edge of plate not less than 1.5m below ground level, connecting to the Galvanised iron strip 32x6mm as earthin lead, by means of nuts, bolts, check nuts and washer etc of galvanised iron and earth lead protected by provision of GI pipe medium grade 40mm bore from earth elelctrode to DBs/main switch incl provn of concrete pit in PCC , GI pipe medium grade 20mm bore pipe for watering perforated at bottom 1.75 mtr long placed on top edge of earth plate, common salt and charcoal with fixing arrangement, funnel, wire mesh and earth work in hard/dense soil, returning in and removal of surplus soil to a distance not exceeding 50mtr complete all as specified and directed. Note :- Item of Earthing includes cost of 7.5m long galvanised iron strip 25x4mm size and protection pipe of 40mm bore GI medium grade complete all as specified and directed by Engineer- In-Charge.
Supply & laying of GI pipe of 50mm size light grade complete with fittings (such as bends, elbows, tees, short pieces, connectors, caps, plugs, unions and screwed socket joints etc) laid in trenches complete all as specified and directed by Engineer- In-Charge. Make:- Tata Steel/Jindal Saw/Zenith
SANJEEV CONSTRUCTIONS (BID ID -3127772)
Srinivash Engineers (BID ID -3105792)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .