Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹8.9 LAccepted-AOC 39 SR LAYOUT MAIN ROAD NAL WING TUNNEL ROAD MURUGESH PALYA BANGALORE 560 017 | BENGALURU URBAN | KARNATAKA | 560017 | L1 | Accepted-AOC LOWEST QUOTED HENCE ADMITTED | |
| 2 | L2₹11.4 L+₹2.5 L (28.1%)Rejected-AOC | L2 | Rejected-AOC NOT LOWEST QUOTED HENCE NOT ADMITTED |
Tender Value
Refer Docs
EMD Value
₹24,000
Closing Date
2 Dec 2022, 6:00 pmClosed
Col Manoj Negi
CWE AF North Bangalore Bellary Road JC Nagar Post Bangalore 560006
SPECIAL REPAIR/ REPLACEMENT OF ALUMINIUM WIRING INTO COPPER WIRING INCLUDING FTL INTO LED FITTING AT VARIOUS LOCATION AT CHAFB
2022_MES_559468_1
87467CWEAFNBAN
Open Tender
Civil Works
Item Rate
180 days
GE (AF) BANGALORE
AS PER NIT
6 documents required · 6 mandatory
₹500
Yes
GE (AF) BANGALORE
₹24,000
Yes
20 May 2023
22 Oct 2022
9 Dec 2022
22 Oct 2022
2 Dec 2022
18 Nov 2022
24 Oct 2022 - 1 Nov 2022
Amount
Taking down carefully copper/aluminium point wiring (light,fan, socket or power ) complete including its connected fitting/fixtures (ie holder, bulk head fittings, ceiling roses, fan regulators, switch , switch socket combination, FTL fitting, ceiling fans etc) and making good disturbed surfaces of wall roof etc complete all as specified and directed.
M & L Point wiring complete with 1100 volts grade single core, PVC insulated FRLS cable with multi-stranded copper conductor of size 1.5 sq mm nominal area, passing through heavy grade PVC conduit of suitable size concealed in stone wall, with all necessary fittings, duly earthed with one run of single core PVC insulated FRLS cable with multi stranded copper conductor of size 1.5 sqmm nominal area green in colour as continues earthing wire connected to common earth dolly including 1.6 mm thick fabricated CI/MS sheet terminal box concealed mounting in the wall for mounting switches,switch socket combination, fan regulators etc.covered with 3mm thick electroplated bakelite sheet top cover for housing switches, sockets, regulators etc. complete for one light/ fan/bell point controlled by one single pole 5 amps switch all as specified and as directed. (a) One light point controlled by one single pole 5 Amps switch.
All as per item No : 02 above. (b) One fan point controlled by one single pole 5 Amps switch.
All as per item No : 02 above. (c) One switch socket out let point 5 Amps on same board with other switches.
All as per item No : 02 above. (d) One switch socket out let point 5 Amps on independent board
Supply and fixing inreplacement Piano type switch single pole 5 Amps one way 230 volts all as specified and as directed
Supply and fix inreplacement socket outlet 5 pin, 5 Amps, flush type, universal complete all as specified and directed.
M & L Point wiring complete with 1100 volts grade single core, PVC insulated FRLS cable with multi-stranded copper conductor of size 2.5 sq mm nominal area, passing through heavy grade PVC conduit of suitable size,concealed in stone wall with all necessary fittings , duly earthed with one run of single core PVC insulated FRLS cable with multy stranded copper conductor of size 2.5 sqmm nominal area green in colour as continues earthing wire connected to common earth dolly including 1.6 mm thick fabricated CI/MS sheet terminal box concealed mounting in the wall , covered with 3mm thick electroplated bakelite sheet top cover for housing 15 A switches, 15A sockets all as specified and as directed.
All as per serial item No 8 above but for 4 sqmm copper conductor cable pvc insulated unsheathed copper earth continuity conductor.
Supply and fixing inreplacement switch 15A flush type universal pattern 230 v all as specified and as directed
Supply and fixing inreplacement socket outlet 5 pin multi purpose 5/15 Amps flush type all as specified and as directed
Supply and fix inreplacement ceiling rose surface bakelite 65x25mm, two to three termimals complete all as specified and directed.
Supply and fixing inreplacement electronic fan regulator socketed step type upto 100 watts with 5 step speed control for fans any sweep 1200 mm/1400 mm. all as specified and as directed
Supply & fix ceiling fan complete and with all accessories including rod of required length except fan regulator 230 V,1200 mm sweep. BEE 5 star rated taking down unserviceable ceiling fan from existing locations and deposit to MES store all as specified
Supply and fixing inreplacement LED lights fitting 1x 20W, 220V,AC decorative box type with driver, holder includingLED tube light connecting up with three core flexible copper conductor cable of suitable size from ceilingrose complete all as specified and directed.
Supply and fixing inreplacement LED luminaire 600 mm x 600 mm,35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed.
Supply and fixing water heater storage type single phase 230 volt 25 ltrs capacity and grouting 4 nos nut & bolts 90 mm long 12mm dia on wall for fixing completetaking down unserviceable water heater from existing locations and deposit to MES store all as specified
M & L inreplacement sub main wiring with Two single core PVC insulated cable with copper conductor FRLS multistranded 1100 volts grade 2x6sqmm in and including heavy grade PVC conduit concealed in stone wall and its accessories with fixing arrangements including 4 sqmm PVC insulated multistranded copper earth continuity conductor and connecting to main earth dolly complete all as specified and directed. Note : One run of earth continuity conductor,one run of PVC conduit and two run of copper conductor together taken as one length for measuring unit length.
All as per serial item No 18 above but for 4x10 sqmm copper conductor cable 6 sqmm pvc insulated unsheathed copper earth continuity conductor.Note : One run of earth continuity conductor,one run of PVC conduit and four run of copper conductor together taken as one length for measuring unit length.
Supply and fix inreplacement sheet metal enclosure double door type for DBs for TPN, fixed complete all as specified and directed.
Supply and fix inreplacement miniature circuit breaker (MCBs) TPN, 415 volts, 10KA, 100 Amps c series complete all as specified and directed.
Supply and fix inreplacement sheet metal enclosure double door type for DBs for mounting of MCB for 240V, 12 way with 200 Amps rated Bus bar, single pole & neutral, fixed complete all as specified and directed.
Supply and fix inreplacement miniature circuit breaker (MCBs) SPN, 240 volts, 10KA, 63 Amps c series complete all as specified and directed.
Supply and fix inreplacement miniature circuit breaker (MCBs) single pole, 240 volts, 10KA, 6 to 32 Amps C series complete all as specified and directed.
Supply and fix inreplacement Surge protection device Type 1+2 AC single pole and neutral, 1P+N 20kA N complete all as specified and directed.
Supply and fix inreplacement RCCB double pole 30mA 40Amps complete all as specified and directed.
Supply and fix inreplacement earth continuity conductor GI wire 4mm dia for earthing complete all as specified and directed.
M & L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less'than 1.5 metres below normal ground level, connected to galvanised earth wire of size 4 mm Dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 5 connected to earthing test point all as specified or indicated including testing on completion all as specified
Supply and fixing inreplacement suspension LED light fitting, 36watt classic styling with cutting edge technology to provide quality illumination and superior optical control. Use of direct/ indirect LED light engines makes it excellent choice for low heightceiling applications and areas where ceiling uniformity and indirect lighting is important (secondarysuspension kit included). including connecting up with twin core flexible copper conductor cable all as specified and as directed.
Suuply and fix inreplacement medical grade copper pipe 15mm dia incl fittings for Oxygen, Air and Vaccum complete all as specified and directed.
Suuply and fix inreplacement medical grade copper pipe 12 mm dia incl fittings for 52 Nos drop points (Oxygen-02 Nos, Air-01 Nos and suction-01 Nos) complete all as specified and directed. Make : Maxflow
Suuply and fix inreplacement medical grade isolation ball valve 15 mm with end fittings for Air and suction complete all as specified and directed.
Suuply and fix inreplacement medical grade butterfly ball valve 12 mm with end fittings for oxygen drop points complete all as specified and directed.
Suuply and fix inreplacement bed head panels (4-5 ft long) with Gem 10 type gas outlet-04 Nos (Oxygen-02 Nos, Air-01 Nos and suction-01 Nos) electric sockets 5 Amp 5 Pin-04 Nos, electric socket 5/15 Amp-02 Nos incl extendable inspection lamp 10w LED with control switch extendable up to 02 mtrs complete all as specified and directed.
Suuply and fix inreplacement caliberated BPC oxygen flow meter with humidifire bottle and Gem 10 type pipeline adapter CE certified complete all as specified and directed.
Suuply and fix inreplacement wall mounted suction unit with 600ml collection jar and Gem 10 type probe & PVC tube CE certified complete all as specified and directed.
SREE VARU ELECTRICALS
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .