| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.1 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹16.4 L+₹5.9 L (56.2%)Rejected-AOC | L2 | Rejected-AOC Other than Lowest Bidder | |
| 3 | L3₹16.9 L+₹6.4 L (61.5%)Rejected-AOC | L3 | Rejected-AOC Other than Lowest Bidder | |
| 4 | L4₹17.9 L+₹7.4 L (70.5%)Rejected-AOC | L4 | Rejected-AOC Other than Lowest Bidder | |
| 5 | L5₹18.4 L+₹8.0 L (75.8%)Rejected-AOC | L5 | Rejected-AOC Other than Lowest Bidder |
Tender Value
₹20 L
EMD Value
₹40,000
Closing Date
5 Nov 2022, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Garrison Engineer (South) Jaipur
Garrison Engineer (South) Jaipur Military Engineer Services Kalyan Marg, Jaipur302006
REPAIR AND MAINT OF LT OH/UG CIRCUIT AND SWITCH GEARS PANNEL BOARD AND OTHER CONNECTED ACCESSORIES AT ZONE-III AREA UNDER GE (S) JAIPUR
2022_MES_555351_1
GE (S)/J-40P /2022-23 8742/E8
Open Tender
Civil Works
Item Rate
210 days
Jaipur
Class E and category b(i)
9 documents required · 9 mandatory
₹500
GE (S) Jaipur
₹40,000
Yes
2 Dec 2022
10 Oct 2022
7 Nov 2022
10 Oct 2022
5 Nov 2022
24 Oct 2022
Amount
Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for laying of cable etc and getting out in soft/loose soil complete.
Excavation in trenches for n.exc 1.5 metre wide and exc 1.5 m but n.exc 3.0 m in depth for foundation etc or for laying of cable/poles etc and getting out in soft/loose soil complete.
M & L Sand cushioning to under ground cable with river bed fine sand and punning to provide a required cover as specified.
M & L Bricks for protection cover to under ground cable (with old size sub class ‘B’ bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed by Engineer-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 Cm in depth complete.
Removing of surplus excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50metre above the starting point as directed.
Dismantling of old existing prestressed cement concrete poles complete of any size including PCC foundation and necessary excavation & earth work and making good to distubed surfaces as directed by Engineer-in-Charge complete.
Dismantling of existing stay assembly of any type & size complete including excavation and earth work and demolition of concrete and making good to distubed surfaces as directed by Engineer-in-Charge complete.
Dismantling/taking out old u/s LT UG cable from trench/ on walls/poles/ducts etc of size 16 Sqmm 2 core, 16 sqmm 4 core, 25 sqmm 3.5 core and/or 25 sqmm, 4 core as specified.
-ditto- as per item No 9.00 but cable size of 35 Sqmm, 3.5 core to 95 Sqmm 3.5 core complete as specified.
-ditto- as per item No 9.00 but cable size of 120 Sqmm 3.5 core complete as specified.
M&L pre-stressed cement concrete poles, 9.0 metre long with minimum cross section 102 mm x 172 mm at top and minimum cross section 102 mm x 279 mm at bottom, class-10, conforming to IS-1678 including all accessories (cross arm, insulator, conductor etc) complete all as specified and directing.
M&L stay assembly complete with accessories as shown in electrical plate No. 1 of MES SSR part I, including stay rod of 20 mm dia, MS stay plate 300 mmx500mmx6mm & GI stay wire of 7/8 SWG, bow, PCC 1:3:6 of suitable length as required.
Supply and lay tube GI of size 40 mm bore Light grade fixed on poles, walls and ceiling etc. with all fittings for protection of cable (Clamps for fixing shall be measured and paid seperately)
-ditto- as per item No 14.00 but 50 mm bore light grade pipe complete.
-ditto- as per item No 14.00 but 80 mm bore light grade pipe complete.
Labour for boring under road/drain by manual/machine method for inserting GI tubing up to 100 mm dia for cable protection all as specified and directed by EIC.
Earthing complete with galvanized steel plate electrode 60cmx60cmx 6.3mm thick buried directly in ground earth pit not less than 2.25 meter deep below normal ground level with top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead GI strip 25x4mm by means of bolts, nuts, check nuts and washer of galvanized iron or steel all as shown in electrical plate No 5 of SSR Part-I connected to continuous earth wire on pole all as specified and testing on completion, including provision of earth wire protected by 40mm dia GI light grade protection pipe from test Point to main board and 20mm GI medium grade watering pipe funnel, PCC earth pit and RCC cover charcoal, salt and GI wire including excavation and earth work etc complete all as directed at site. ( Note : PCC Chammer shall be constructed atleast 1.5 mtrs away form the earth electrode of the earth pit and pipe for watering shall be provided in slanting manner).
Trimming of tree branches in vicinity of OH electric supply line (any Nos of conductor) pole/street light pole/solar modules all around 3.0 m clearance each direction (vertical/horigontal) in between poles (each span approx not less than 3.0 m length) & depositing at places n exc 50m all as directed by Engineer-in-Charge.
Supply, laying, connect and commission LT under ground cable XLPE insulated, screened PVC bedded, galvanised steel strip armoured, heavy duty with multi stranded aluminium conductor, 1100 volts grade (ISI marked) laid in trenches, ducts, pipes or fixed on pole etc of size 95 Sqmm, 3.5 Core.
-ditto- as per item No 20.00 but 70 Sqmm, 3.5 Core
-ditto- as per item No 20.00 but 50 Sqmm, 3.5 Core
-ditto- as per item No 20.00 but 35 Sqmm, 3.5 Core
Scrapping & preparation of old steel surface of LT Panel of any type and M&L for painting the same with two coats of synthetic enamel paint by spray of approved colour complete all as specified and directed by Engineer-in-Charge.
Supply and fix heat shrinkable straight through jointing kit complete with accessories suitable for XLPE armoured aluminium conductor cable 1.1 KV grade of following size
50 to 70 Sqmm 3½ Core
95 to 150 Sqmm 3½ Core
Supply and fix heat shrinkable end jointing kit (indoor/outdoor) complete with accessories suitable for XLPE armoured aluminium conductor cable 1.1 KV grade of following size
50 to 70 Sqmm 3½ Core
95 to 150 Sqmm 3½ Core
Disconnecting & taking out the existing Unserviceable MCCB from panel and S&F new MCCB 63 amp, 16/18 KA breaking cap of suitable frame size, 4 Pole, 415 V, 50 Hz, 3 phase, adjustable type including extension terminals and Ics=100%Icu connecting using suitable fasteners, modification/fabrication if any complete all as required at site, as specified and directed.
-ditto- as per item No 27.00 but 125 amp, 16/18 KA complete.
-ditto- as per item No 27.00 but 160 amp, 35/36 KA complete.
-ditto- as per item No 27.00 but 200 amp, 35/36 KA complete.
-ditto- as per item No 27.00 but 250 amp, 35/36 KA complete.
S&F of LT Danger notice plate of 1.6 mm thick mild steel sheet 20x15 cm size, vitreous enamelled white with letters, figures and conventional skull and bones in signal red colour and fixed with suitable MS clamps, bolts and nuts including taking down complete all as specified and directed.
Disconnecting & taking out the existing Unserviceable LT panel and S&F new out door (Kiosk type) type factory made LT panel, weather & vermin proof MS CRCA sheet housing 3.15 mm thick, CPRI tested, IP - 54, powder coated over a coat of primer, double door, front & rear openable type, mounted on 40x40x6 mm angle iron frame, floor mounted type with one MCCB, 4 pole, 200 Amp, 35/36 KA, 415 volts, thermal release, adjustable type (Ics=100%Icu) as incomer and Aluminium bus bar 400 Amp of length not less than 60 cm, 4 pole duly drilled with holes for cable connections, after due approval of panel drawing including PCC pedestals of suitable size, removal of old unsv panel, making good the area complete all as specified and directed by Engr-in-charge.
Disconnecting & taking out the existing Unserviceable LT panel board and Supply, install, testing and commissioning (including CPRI type test certified) factory made LT feeder pillar box (KIOSK) out door type, floor mounted,compartmantalised and IP-54 suitable for 415 Volts 3 phase 4 wire, 50 Hz AC supply system, all as specified and directed, having bus bar chamber. The panel shall be dust and vermin proof, made of 3.15mm CRCA MS sheet and with base frame of 40x40x6mm angle iron , powder coated, having front and rear openiable hinged double door shuters with aprons for cable entry and locking arrangement complete :- Incoming (a) MCCB 400 amps, 4 pole, 50 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. Make:Legrand/ABB and equ (b) Bus bar electrolytic grade copper and supported on Non-hygroscopic, non carbonising, corrosion resistance SMC insulators 500 Amp, 4 pole, not less than 60 cm long mounted on insulators. (c) Digital Load manager multy functional energy meter having facility to measure true RMS value, KWH, neutral current, for quadrant energy, max demand (KW, KVA, Kvar & Amp), CT operated 415 volts, 50 Hz AC supply including CTs. -01 set. (d) On load changeover switch of 400 Amps 4 pole. (d) LED indicating lamps (R, Y & B) -01 Set. Outgoing (a) MCCB 200 amps, 4 pole, 30 KA (Icu = 100% Ics), with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 Nos. (b) MCCB 100 amps, 4 pole, 30 KA , with adjustable thermal over load release with earth fault protection. 50 Hz, 415 volts grade - 02 No.
S&F Bus bar electrolytic grade aluminium of 25×6 mm, mounted on insulators including drilling holes including disconnection & reconnection of cables from existing panel complete all as specified and directed.
S & F On-load change over switch, 4 pole, 415 volts, 200 amp suitable for existing panel including taking down the unsv c/o switch, disconnecting and reconnecting all electrical connections, modification/fabrication if any complete all as specified and directed.
S & F in repair Off-load manual change over switch 4 pole, 415 volts, 100 amp in sheet steel enclosure, factory made including disconnecting and reconnecting all electrical connections complete all as specified and directed.
Repairs & Maintenance of APFC panel of capacity 25 KVAR to 150 KVAR including replacement of wiring with copper conductor cable with lugs etc calibration of relay, digital meter complete. Note : Unserviceable Spare Parts will be measured & paid separately supply only under respective items of Schedule ‘A’.
Supply only power capacitor 5 KVAR cylindrical type suitable for existing APFC panel complete incl removal of old unsv capacitor all as specified and directed by Engr in Charge.
-ditto- as per item No 39.00 but 10 KVAR
Supply 5 KVAR capacitor duty contactor , AC coil complete all as specified and directed by Engr in Charge.
-ditto- as per item No 41.00 but 15 KVAR
Supply APFC relay 12 stage with suitable CT complete all as specified and directed by Engineer in Charge.
Supply auxilary contactor of any suitable type complete all as specified and directed by Engr in Charge.
M & L PCC (1:3:6) type C-2 using 40 mm graded stone aggregate for foundation of stay assembly / struts / poles etc.
M & L for PCC (1:2:4) type B-1 using 20 mm graded stone aggregate as in coping including form work to RCC pole complete as specified.
M&L for fault locating machine for fault finding on requirement for LT/HT cables of any type/size complete all as specified and directed by Engr-in charge. Note :- One number of fault as located/found shall be measured as one Job/Unit for payment.
S&F cable route indicator, cast iron 10 cm dia with 25x25x4 mm angle iron 0.8 m along the LT/HT cable trench including painting and grouting in ground in PCC 1:2:4 type B1 using 20 mm graded aggregate complete all as specified and directed by Engr in Charge.
Laying only LT UG cable 120 sqmm x 3.5 core. Note:- (i) Cable shall be provided under Sch 'B' free for fixing/laying complete with all electrical connections testing as specified and directed by Engr-in-Charge. (ii) Excavation/earth work will be meaasured & paid seperately under relevant item and no change in existing alligment of cable with prior written approval of GE.
M/S TRADE LINKERS
M/s Prakash Enterprises
LAKSHMI ASSOCIATES
M/s Radhey Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .