Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹7.7 LAccepted-AOC 00 VILL RATI KA NAGLA SIKANDRA RAO ROAD INDUSTRIAL HATHRAS UTTAR PRADESH 204212 | HATHRAS | UTTAR PRADESH | 204212 | L1 | Accepted-AOC Being Lowest | |
| 2 | L2₹9.4 L+₹1.4 L (16.9%)Rejected-Finance | L2 | Rejected-Finance Being not lowest | |
| 3 | L3₹9.5 L+₹1.5 L (18.2%)Rejected-Finance 02 JAMEEWAR COMPLEX RING ROAD HANUMAN NAGAR GONDIA MAHARASHTRA 441614 | GONDIA | MAHARASHTRA | 441614 | L3 | Rejected-Finance Being not lowest |
Tender Value
₹9 L
EMD Value
₹18,000
Closing Date
11 Jul 2023, 2:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
AGE (I) Manauri Prayagraj
AGE (I) Manauri Allahabad-212212
REPAIR/MAINT OF LT DISTRIBUTION NETWORK, PANELS, CABLES AND OTHER CONNECTED ITEMS AT OLD PROJECT AREA UNDER AGE (I) AF MANAURI
2023_MES_602153_1
9083/E8
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
Manauri
As per Tender Documents
7 documents required · 7 mandatory
₹500
AGE (I) AF Manauri
₹18,000
Yes
20 Sept 2023
9 Jun 2023
12 Jul 2023
9 Jun 2023
11 Jul 2023
22 Jun 2023
Amount
Excavation in trenches not exc 1.5 m wide and not exc 1.5 m in depth for pipe line, etc getting out in soft/ loose soil and levelling of bottom surface to required level complete and as directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm complete and as directed.
Removal of surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
Supply, laying and spreading of dry (Ganga) sand, free from organic impurities for cushioning as in trenches 8cm depth below cable and 15cm above cable and punned to 10cm depth complete all as specified & directed. Note:- Punned thickness shall be considered for measurement purpose.
M&L brick sub class 'B' bricks laid dry, flat, length equal to width of brick over sand cusioning in trenches for cable protection complete all as specified and directed.
Labour only for reuse of serviceable bricks obtained from serial Item No 1.00 complete all as specified and directed.
M&L for cutting /boring to plinth protection / hard standing / road etc in suitable depth to across the GI pipe size upto 80 mm dia of bore for drawn through XLPE under ground cable for giving mechanical protection to cable complete all as directed. Note: Quoted rate shall be included the cost of required material for repairing to disturbed surface complete all as per existing at site.
M&L in replacement to GI tubing light grade 80 mm dia of bore with all fitting laid in trenches across the road or fixed with pole/ surface of wall etc as site with required fixing accessories complete all as specified and directed. Make: Tata / Jindal / Swastik
S&F in replacement galvainesd water tubing light grade 50 mm dia of bore fix with pole/ surface of wall / laid in trench etc as site using 02 Nos clamp made out by GI strip in size 25x4 mm with nut bolt and washer etc complete all as specified and directed.
Dismantling of ACSR/ AAC conductor of any type and size from over head line complete all as specified and directed.
Dismantling of GI wire/ conductor of any type and size from over head or other situation complete all as specified and directed.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 240 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands including taking out/down old unserviceable cable complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 95 Sqmm (earthed) laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 70 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 50 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands including taking out/down old unserviceable cable complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 3.5 core 25 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands including taking out/down old unserviceable cable complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 2.00 core 16 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands including taking out/down old unserviceable cable complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Supply, laying, jointing, connecting and testing XLPE insulated PVC sheathed cable 1100V grade, conforming to IS-7098 (Part-I) of 1988, screened PVC bedded, armoured electric power cable, heavy duty multi-stranded aluminium conductor grade cross section area 2.00 core 06 Sqmm (earthed), laid in trenches / fixed on walls/poles, passing through pipes, etc. including connecting up to DBs, etc. with required lugs, end terminal / cable glands including taking out/down old unserviceable cable complete all as specified and directed. Note: Excavation and earthwork will be measured and paid separately under respective items of BOQ.
Labour for re-laying, connecting, jointing, thembling using in suitable size and cramping etc to serviceable XLPE insulate LT cable in all specification (240/95/70/50/25/16 sqmm) including brick (re-use) and sand (Provided fresh) etc all as per existing complete with other site required works complete all as specified and directed. Note: Excavation and Sand cushioning shall be measured and paid separately under respective items of BOQ.
Taking down old unserviceable garden light and S&F LED Bollard 10 watt in inverted pyramid tropod type LED Bollard with soft 360 light, IP 65 protection, resistant to corrosion with better optic for uniform distribution with all accessories prewired and including connecting up with twin core twisted flexible copper conductor cable complete with PCC work suitable size complete all as specified and directed. Make: Crompton Greaves Cat part No LBLSN-10CDL / Philips / Havells / Surya / Bajaj
M&L for PCC 1:4:8 type D2 (using 40 mm graded crushed stone aggregates) as in foundation bed and above ground including necessary form work and finishing the exposed surface even and smooth without using extra cement complete all as specified and directed.
Taking down old unserviceable sheet metal enclosure box and S&F MCB Sheet metal box two pole with MCB SPN 06 Amp 10 kA 240 volts suitable for bollard light fitting including all connection complete all as specified and directed.
M&L for tree trimming cut away dead or excess branches from trees or shrubs to maintain clearance along with over head power lines using climbing equipment and collecting the debris for disposal and removing broken limbs from electric wires by using hooked extension poles complete all as specified and as directed. Notes: Span is taken as distance between two adjacent poles.
Supply, install, testing and commissioning (in replacement) LT panel size 90cmx80cmx40cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement including inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired duly powder coated with comprising of the following complete all as specified and directed.
Supply, install, testing and commissioning (in replacement) LT panel size 90cmx80cmx40cm enclosures cubical weather and vermin proof totally enclosed made out of 3.15 mm thick CRCA sheet machine pressed of suitable size to operate on 3 phase 4 wire system 415 Volts, 50HZ double door with front and rear openable with locking arrangement including inner shutters for mounting switch gear etc, bottom gland plate with sufficient numbers of circular cable entry holes, including PCC work, prewired duly powder coated with comprising of the following complete all as specified and directed.
Taking down old unserviceable DB and S&F Busbar chamber TPN current capacity 63 Amp 04 way horizontal type, total enclosed with porcelain Insulator and colour coated tinned copper bus bar with suitable size of legs including PCC work fixing on ground or on wall/pole with suitable size of clamp, Nut, bolts, suitable size of thimbles for connection etc. complete all as specified and directed. Make: Havells / L&T / Standard / ABB / Indoasian
S&F in replacement LT cable junction box dust and water proof made out of PVC non metallic sheet FRP type, factory made, size of box 250mmx200mmx100mm deep with swivelling cover and locking clamp, MS clamps and nuts, bolts, for fixing the box on steel tubular pole, consisting of aluminium bus bar strip(04 Nos) of size 150mmx30mmx3mm, mounted on pole complete all as specified and directed. Make: Sintex CAT Part No GS-JB2520 / Henson / Legrand.
M&L for Earthing (in replacement) complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick surrounded with charcoal and salt, buried directly in ground (earth pit not less than 2.25m deep below ground level) with top edge of plate not less than 1.5m below normal ground level connected to galvanized earth lead using GI earth strip in size 32x6 mm means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical Plate No 3 of MES SSR Part-I connected to main switch board or main control board and testing on completion including provision of earth wire protected by galvanized iron 15 mm dia light grade pipe and watering pipe shall be 20 mm bore light grade including all excavation and earth work in any type of soil, PCC pit with pre-cast RCC cover, charcoal/salt, funnel etc complete all as specified and directed.
Notes for Item No. 28.00 :- (i) The concrete pit shall be PCC 1:3:6 type C-1(using 20mm graded crushed stone aggregate), 40 mm thick pre cast cover slab of RCC (1:2:4) type B-1(using 20mm graded crushed stone aggregate) reinforced with 8mm TMT bars @ 10 cm C/C on both sides with suitable cast iron handle shall be provided in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I. (ii) Item includes the cost of 7.50m GI pipe for protection of earth wire/strip. Any variation in length shall be adjusted through deviation order. (iii) Item includes cost of 7.50m earth lead wire/strip. Any variation in length shall be adjusted through deviation order. (iv) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself and the extra cost of additional length of watering pipe, bends, elbow etc shall be deemed included in the unit rate.
Supply, jointing, commissioning and testing in replacement heat shrinkable end termination / straight through jointing kit suitable for 1100 volt grade (earthed) cable for outdoor type with jointing material and required accessories suitable for underground XLPE cable of size 4 Core x 95/120 Sqmm (earthed) complete all as specified and directed. Make: Denson / 3M / Raychem
Supply, jointing, commissioning and testing in replacement heat shrinkable end termination /straight through jointing kit suitable for 1100 volt grade (earthed) cable for outdoor type complete with jointing material and required accessories suitable for underground XLPE cable of size 4 Core x 185/240 Sqmm(earthed) complete all as specified and directed. Make: Denson / 3M / Raychem
S&F in replacement adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 630 Amps, rated ultimate shortcircuit breaking capacity 36 kA Icu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts, Ics=100% Icu with extended copper terminals including taking out existing unserviceable / burnt MCCB from site complete all as specified and directed.
S&F in replacement adjustable thermal and adjustable magnetic setting based MCCB 4 Pole 250 Amps, rated ultimate shortcircuit breaking capacity 35 kA Icu at 415 V (kA rms thermal & magnetic adjustable type, 415 volts, Ics=100% Icu with extended copper terminals including taking out existing unserviceable / burnt MCCB from site complete all as specified and directed.
Note :- (i) Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material. The contract amount shall be arrived at after deduction of Schedule of Credit from the total quoted amount in BOQ. (ii) Make of material shall be as per mentioned in Particular specifications or Appendix 'B' to Particular specifications as approved by AGE (I) AF manauri if not mentioned in BOQ.
M/S Garg Sons
M/S R S Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .