| Sl No | Description | Qty | Unit | Shree Ram Enterprises L2 | S and G Constructions L3 | DURGAI ELECTRICALS L1 |
|---|---|---|---|---|---|---|
| 1.00 | Material and labour for filtration and dehydration of transformer oil by dehydration machine to achieve the die-electric strength/ insulation value of minimum 60 KV at standard gap of electrodes 2.5 mm for one minute in various capacity of transformers 33/11KV and 11/0.433KV including insulation testing of oil with help of suitable equipments before and after dehydration including BDV Test complete all as specified and directed. | 5,500 | Ltrs | 20 ₹1,10,000 | 15 ₹82,500 | 7 ₹38,500 Lowest |
| 1.10Note: (i) Contractor will have to arrange the dehydration machine and transformer oil dielectric strength testing equipment as mentioned and same shall be deemed to be included in the item rate quoted. (ii) Test result of transformer oil before and after dehydration is required to be submitted by the contractor duly signed by all concerned. (iii) The contractor shall ensure that the conservator tanks are full to its level before commencement of dehydration process. (iv) Additional quantity of transformer oil if any required for making the oil level up to the requirement in transformer shall be measured and paid separately as supply and filling but its cost of heating shall be deemed to be included in the rate quoted for above item. | ||||||
| 2.00 | Supply and fill new EHV grade insulating transformer oil complete with minimum BDV not less than 60 KV all as specified and as directed. | 1,550 | Ltrs | 215 ₹3,33,250 | 165 ₹2,55,750 | 160 ₹2,48,000 Lowest |
| 3.00 | Material and labour for testing and calibration of 11KV VCBs indoor/outdoor type along with control panel and control wiring, protection system and relays system (relay to tripping coil auxiliary switch male and female housing cut outs etc) , checking of quality of vacuum interrupter, insulation resistances, static contact resistance, Testing ( IR value, Ratio test, Polarity test) and connection verification of 11 KV Current transformer( Set of three) by PRIMARY INJECTION KIT ,and Testing and calibration of relay( set of two Over current and one earth fault) by SECONDARY INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs. complete all as specified and as directed. | 10 | Each | 9,000 ₹90,000 Lowest | 10,000 ₹1,00,000 | 10,000 ₹1,00,000 |
| 4.00 | Disconnecting, opening of VCB of any description and any make of rating 11 KV 400/800 Amps capacity for servicing / overhauling, taking out and removing unserviceable / defective parts including cleaning & servicing, greasing, oiling of the parts etc and replacement of unserviceable parts with new one, reassembling the VCB after overhauling/ servicing and its testing complete all a specified and directed.
Note:
(i) Replacement of unserviceable parts shall be measured and paid for separately under appropriate item of Sch 'A' item no 5 to 19 as supply only but fixing charges of the parts replaced /repaired is deemed to be included in these item.
(ii) Servicing shall be got carried out by the authorised rep of the VCB manufacturer and the service engineer will submit a service report for each VCB.
(iii) Any item not included in CA and required for successful operation of the panel will be provided by the contractor & same shall deemed to be included rate quoted. | 6 | Each Job | 12,000 ₹72,000 | 9,000 ₹54,000 Lowest | 10,000 ₹60,000 |
| 5.00 | Supply only Vacuum circuit breaker main mechanism assembly complete with all accessories all as specified and as directed. | 1 | Each | 15,000 ₹15,000 | 60,000 ₹60,000 | 7,000 ₹7,000 Lowest |
| 6.00 | Supply only Vacuum Interrupter for indoor VCB | 1 | Each | 9,900 ₹9,900 Lowest | 22,000 ₹22,000 | 12,000 ₹12,000 |
| 7.00 | Supply only Isolating contact assembly 400/800 Amps | 2 | Each | 7,500 ₹15,000 | 10,500 ₹21,000 | 3,000 ₹6,000 Lowest |
| 8.00 | Supply only Tripping Coil assembly 30 Volts DC | 2 | Each | 4,500 ₹9,000 | 2,500 ₹5,000 Lowest | 3,000 ₹6,000 |
| 9.00 | Supply only Close Coil assembly 30 Volts DC | 2 | Each | 4,500 ₹9,000 | 2,200 ₹4,400 Lowest | 3,000 ₹6,000 |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
16 Aug 2025, 6:00 pmClosed
COL SAIKAT DE CWE NAVY VASCO
CWE NAVY VASCO VASCO DA GAMA GOA 403802
REPAIR / ROUTINE MAIN OF 11 KV STEPPED DOWN TRANSFORMER INSTALLED AT NAY (G) BSF UNITS , MAGZINES ETC INCLUDING HT CABLE AND OTHER CONNECTED WORKS AT NORTH SIDE OF RUNWAY UNDER GE (NW) VASCO
2025_MES_721409_1
85976
Open Tender
Civil Works
Item Rate
Vasco
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE (NW) Vasco
₹80,000
Yes
1 Sept 2025
18 Jul 2025
18 Aug 2025
18 Jul 2025
16 Aug 2025
2 Aug 2025
Amount
Material and labour for filtration and dehydration of transformer oil by dehydration machine to achieve the die-electric strength/ insulation value of minimum 60 KV at standard gap of electrodes 2.5 mm for one minute in various capacity of transformers 33/11KV and 11/0.433KV including insulation testing of oil with help of suitable equipments before and after dehydration including BDV Test complete all as specified and directed.
Note: (i) Contractor will have to arrange the dehydration machine and transformer oil dielectric strength testing equipment as mentioned and same shall be deemed to be included in the item rate quoted. (ii) Test result of transformer oil before and after dehydration is required to be submitted by the contractor duly signed by all concerned. (iii) The contractor shall ensure that the conservator tanks are full to its level before commencement of dehydration process. (iv) Additional quantity of transformer oil if any required for making the oil level up to the requirement in transformer shall be measured and paid separately as supply and filling but its cost of heating shall be deemed to be included in the rate quoted for above item.
Supply and fill new EHV grade insulating transformer oil complete with minimum BDV not less than 60 KV all as specified and as directed.
Material and labour for testing and calibration of 11KV VCBs indoor/outdoor type along with control panel and control wiring, protection system and relays system (relay to tripping coil auxiliary switch male and female housing cut outs etc) , checking of quality of vacuum interrupter, insulation resistances, static contact resistance, Testing ( IR value, Ratio test, Polarity test) and connection verification of 11 KV Current transformer( Set of three) by PRIMARY INJECTION KIT ,and Testing and calibration of relay( set of two Over current and one earth fault) by SECONDARY INJECTION KIT including all other functional tests of the VCB, C&R panel and CTs, PTs. complete all as specified and as directed.
Disconnecting, opening of VCB of any description and any make of rating 11 KV 400/800 Amps capacity for servicing / overhauling, taking out and removing unserviceable / defective parts including cleaning & servicing, greasing, oiling of the parts etc and replacement of unserviceable parts with new one, reassembling the VCB after overhauling/ servicing and its testing complete all a specified and directed. Note: (i) Replacement of unserviceable parts shall be measured and paid for separately under appropriate item of Sch 'A' item no 5 to 19 as supply only but fixing charges of the parts replaced /repaired is deemed to be included in these item. (ii) Servicing shall be got carried out by the authorised rep of the VCB manufacturer and the service engineer will submit a service report for each VCB. (iii) Any item not included in CA and required for successful operation of the panel will be provided by the contractor & same shall deemed to be included rate quoted.
Supply only Vacuum circuit breaker main mechanism assembly complete with all accessories all as specified and as directed.
Supply only Vacuum Interrupter for indoor VCB
Supply only Isolating contact assembly 400/800 Amps
Supply only Tripping Coil assembly 30 Volts DC
Supply only Close Coil assembly 30 Volts DC
Supply only Motor & Gear assembly 110V AC and 220 AC
Supply only TNC switch for 11 KV VCB Panel
Supply only Connector strip 16 way
Supply only Spout Incoming side
Supply only Spout Outgoing side
Supply only Digital type power factor indicator meter
Supply only Digital type Ammeter/voltmeter
Supply only Earth fault and overload relay of suitable as per existing
Supply only Indication lamp LED type suitable for 230 Volts AC 50Hz and 110/30 Volts DC supply.
Supply in repairs including installation, testing and commissioning of Micro processor base relay (02 O/C + 01 EF) for 11 KV VCB panel , rating 5 Amps, Auxiliary supply 20-110 Volt DC complete all as specified and as directed. Note:- (i) Necessary addition/ alteration to existing VCB front panel such as cutting/welding of front size of panel board/position if required including necessary modification of wiring shall be carried out at site by the contractor without any extra cost. (ii) The digital relay shall have following protections (a) Phase over current protection (b) earth fault protection (c) Over voltage (d) Breaker failure indication (e) Auxiliary power supply 24-110 V DC
Supply, installation, commissioning and testing of cast resin type 11KV current transformer having ratio 100+50/5+5A as per IS: 2705 having protection core class 5P10, burden of 15VA and metering core class CL1.0 and burden of 15VA, breaking capacity of 13.1 KV for 1.0 second and disconnecting and taking down unserviceable current transformer of any description and in any position and all as specified and directed.
Supply, installation, commissioning and testing for 11KV single phase indoor oil cooled PT of ratio 11KV/RT 3/10V/RT 3/110/RT 3 class 0.5-3, burden 100VA, insulation level 35/75 KV, voltage factor 1.2 cont and 1.9 for 30 sec, conforming to IS-3156 and disconnecting and taking down unserviceable voltage transformer of any description and in any position complete all as specified and directed.
Supply in repairs including install ,testing and commissioning of Power pack unit input voltage 180-250 Voltage and out put voltage 24 Volt DC having 4-digit digital Volt & Ampere meter, High resolution D/A, A/D converter , Digital interface as standard function etc. complete all as specified and as directed including taking out unserviceable battery bank unit.
Excavation in trenches n.exc 1.5M wide & n.exc 1.5m in depth for laying & removing of cable any sizes and getting out in hard/dense soil all as specified.
Returning filling in excavated earth work including spreading, leveling, watering and well ramming in layers n.exc 25cm thick in any strata
Removing excavated soil to a distance n.exc 50m, depositing where directed at a level n.exc 1.5M above the starting point
Supply and filling in and speeding clear sand for cushioning and covering the under ground cables in trenches and punning to provide required cover complete all as specified in SSR Part-I and as directed. Note: Punned thickness i.e. 18 cm shall be measured & paid.
Supply and lay un-reinforced precast concrete cable covers, class HV , type- I with peak, size 300mm x 180mm x 40mm, all as specified and as directed.
Supply & lay in trench/on wall in repairs GI tubing light grade 100 mm dia for road crossing and cable protection complete all as specified and as directed.
Material and labour for PCC 1:4:8 type D-2 using 40 mm graded stone aggregate including use and waste of form work of concrete for pole and stay foundation complete all as specified and as directed.
Material and labour for PCC 1:3:6 type C-1 using 20 mm graded stone aggregate including use and waste of form work for pole coping complete all as specified and as directed.
Material and labour for graded coarse aggregate (broken stone or boulders) of size 40 mm in substation yard for laying all as directed and specified.
Supply & Lay , testing and commissioning XLPE cable , PVC insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty with aluminium conductor 11000 Volts grade (earthed), 3 core 120 sqmm laid in trenches / floor / duct / fixed on poles / through GI tubing in different locations / areas complete all as specified and as directed.
Supply & Lay , testing and commissioning XLPE cable , PVC insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cable, heavy duty with aluminium conductor 11000 Volts grade (earthed), 3 core 95 sqmm laid in trenches / floor / duct / fixed on poles / through GI tubing in different locations / areas complete all as specified and as directed.
Taking out old serviceable ACB of capacity 400 to 1200 amps 415 volts AC 50 HZ at various sub station and carry out necessary servicing , greasing to fixed and movable parts , cleaning complete internally and testing after reinstallation.(Note:- Any damage occurs during servicing will be borne by the contractor ).
Supply and fix charging motor 110V AC/DC, 220V AC/DC of suitable size for ACB of capacity 400 to 1200 Amps complete all as specified and as directed.
Material and labour new stay assembly complete comprising of stay clamp , stay wire , stay insulator , stay grip , thimble , bow , stay rod 20 mm dia and stay plate etc as shown in electrical plate No -01 ( loop insulators , stay clamps , excavations and earth work shall be measured and paid separately under respective items) including dismantling old stay assembly including connecting items and all as specified and as directed.
Material and labour for Earthing complete with copper earth plate electrode 600 x 600 x 3.15 mm thick buried directly in ground earth pit not less than 2.25 mtr deep below normal ground level with top edge of the plate not less than 1.5 mtr below normal ground level connected to copper strip size 20 x 3 mm thick by mean of nuts/bolts, check nuts and washers of brass as shown in electrical plate No. 5 of SSR part-I including necessary excavation and earth work, GI Pipe 15 mm bore light grade for watering with funnel, wire mesh and protection to earthing strip shall be provided with GI pipe light grade 32 mm dia up to 7.5 mtr from the earth plate electrode and refilling of soil including adequate quantity of charcoal dust and common salt mixed with 10% garden soil and 10 Kg bentonite powder, PCC pit chamber in PCC 1:3:6 type C-1 with 40 mm thick Precast RCC cover slab 1:2:4 type B with 8 mm dia TMT bar and handle with lifting hooks including testing any type complete including removing old earthing and all as specified and as directed.
Material and labour for Earthing complete with GI earth plate, electrode,600x600x6.0 mm thick buried directly in ground (earth pit not less than 2.25m deep below normal ground level) filled with common salt and charcoal and connected to GI earth strip 32x 6 mm thick dia by means of GI nuts, bolts, & washers as shown in electrical plate No. 5 of SSR Part-I and Connected to earthing test point all as specified and including necessary PCC earth pit chamber of 1:3:6 and chamber cover of 50mm thick PCC 1:2:4 with 6mm dia mild steel reinforcement of 10 cm c/c spacing both ways in lieu of CI cover, watering arrangement shall be made with GI pipe light grade of 20mm dia including funnel and protection to earth lead shall be provided with GI pipe light grade 40 mm dia unto 7.5 from the earth plate electrode & refilling of soil etc including necessary excavation & earth work in any strata and PCC chamber all as specified and directed by Engr-in-Charge including demolish existing earth pit taking out old materials.
Supply& Fix in repairs including installation of 11 KV outdoor type gang operated air break switch triple pole mechanically operated mounted on insulator and steel frame, with operating mechanism worked from ground level for current rating up to 200 amps complete all as specified and as directed. (cost of GOD includes cost of GI Pipe required for operation and these rates bases on reputed manufacturer
Repairing / Servicing the air break isolating switch 11 KV 200 Amps by replacing the defective major spares including provn of worn out bolts nuts etc, applying petroleum jelly on moving/ fixed contacts all as specified and as directed. Note :- Major spare shall be measured & paid separately under relevant items of item No. 42(i)
Supply only Air break switch spares
(a) Male contact/moving Contact Blade
(b) Female contact/Fix Contact Jaw
(c) Tinned copper Flexible jumper 200A
(d) MS jumper carrier
(e) Back Connector plate
(f) Petroleum Jelly
Supply and fix in trench/on wall in repairs GI tubing light grade of size 80 mm dia for road crossing and cable protection of the following sizes as in repairs :-
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable straight through joint heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured AI conductor cable of size 50 sqmm to 95 sqmm complete all as specified and as directed.
Supply and fix in trench/on wall in repairs GI tubing light grade of size 80 mm dia F54:K54for road crossing and cable protection of the following sizes as in repairs :-
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured AI conductor cable of size 120 sqmm to 185 sqmm complete all as specified and as directed.
All as per item no 44 here in before but of Size 50 to 95 sqmm.
Supply and fix cable jointing kit for 11 KV(Earthed) grade cable indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 .sqmm to 185 sqmm complete all as specified and as directed.
All as per item no 46 here in before but of Size 50 to 95 sqmm.
Supplying and laying synthetic Rubber insulated mats 2.5 mm thick for voltage up to 11 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m, complete all as specified and as directed.
Cutting and trimming tree branches n.exc 50 mm dia in size obstructing lamination of street light and touching line complete all as specified and as directed.
Cleaning around any E/M installations/ pole structures including removing all grass and other vegetations with roots complete all as directed and removing the rubbish to a distance not exceeding 50 mtr and depositing where directed.
Material and labour for cleaning and preparation of steel surfaces of existing dull painting of transformer outdoor type including radiators, cooling ducts, vent pipes, condenser etc and applying two coats of synthetic enameled paint (heat resistant type) according to IS colour code by spray machine including writing MES /SM No. in capital letters of suitable size on body for capacity up to 250KVA transformer outdoor/indoor complete all as specified and as directed
All as per item No: 51 but capacity above 315 KVA and upto1000 KVA.
Material and labour Superior quality blue colour silica jell for breather unit and fill up the oil, to maintain the exact value grade for transformer of capacity up to 500 KVA, including taking down unserviceable complete as specified.
All as per item No: 53 but capacity above 600 KVA and up to 1000 KVA.
Supply and fix in repairs breather unit of transparent PVC Material including its replacement for transformer of capacity up to 500 KVA.
All as per item No: 557 but capacity above 500 KVA and up to 1000 KVA.
Supply and fix in repairs HV bushing with insulator, studs nut & washers suitable for 11 KV/433V HV side of transformer 100 KVA to 150 KVA
All as per item No 57 above but 200 KVA to 250 KVA Transformer
All as per item No 57 above but 315 KVA to 400 KVA Transformer
All as per item No 57 above but 500 KVA to 630 KVA Transformer
All as per item No 57 above but 750 KVA to1000 KVA Transformer
Supply and fix in repairs LV bushing with insulator , studs nut & washers suitable for11 KV/433V LV side of transformer of Capacity 100KVA to 150 KVA
All as per item No 62 above but 200 KVA to 250 KVA Transformer
All as per item No 62 above but 315 to 400 KVA Transformer
All as per item No 62 above but 500KVA to 630 KVA Transformer
All as per item No 62 above but 750KVA to1000 KVA Transformer
Servicing and repairing/ carrying out maintenance of 11KV/433V transformer including the following works up to 250 KVA capacity (a) Removing from platform and disconnecting electrical connection from HT and LT side including transporting the transformer to work shop. (b) Dismantling the transformer, drain out transformer oil, lift the cover, coil assembly keep up the assembly in oven up to the preparation of inside chambers by cleaning inside, scraping complete all around old parts of the transformer. (c) Material and labour for two coats of oil resistance painting internal (inside transformer) over a coat of red oxide primer. (d) Cleaning the core iron sheet laminations assembly by oil complete, removing the carbon sediments, dust in the coil and core gently without making any damage to coil and core. (e) Re-assembling all dismantled parts including provision of new gasket ,nut,bolts,refilling with transformer oil and transporting back to original location including electric connection testing and commissioning complete. (f) Necessary plate work including welding for preventing oil leakage if any. Note :- i) Oil filtration, supply of new oil will be measured separately. (ii) All petty parts including nut, bolts, gasket minor welding are deemed to be included the rate quoted (iii) The rate for transport and lifting of transformer by crane should be deemed to be included in the rate quoted.
All as per item No 67 above but 315 to 500 KVA Transformer
All as per item No 67 above but 630 to 1000 KVA Transformer
Material and labour for rewinding of transformer, including dismantling, drain out transformer oil and removing the core coil assembly from transformer remove the weak /unserviceable HT coil assembly rewinding with correct gauge super enameled copper wire including drying, baking etc complete and remove the secondary coil assembly remove the insulation rewind with fresh coil and re-insulated. Assembling the primary and secondary coil in core, re-assembling the transformer complete refill with transformer oil, install, test and commissioning complete of following capacity all as specified and as directed.
(a) Transformer up to 250 KVA Capacity
(b) Transformer 315 KVA to 500 KVA Capacity
(c) Transformer 630 KVA to 1000 KVA Capacity
All as per item No. 71 here in before, but for 430 V LT side limbs for following capacities :-
(a) Transformer up to 250 KVA Capacity
(b) Transformer 315 KVA to 500 KVA Capacity
(c) Transformer 630 KVA to 1000 KVA Capacity
Notes for Item Sl Nos. 70&71 : (i) Additional oil required for top up of transformer after filtration shall be measured and paid for separately. (ii) Rewinding of limb shall be carried out only after the inspection of Transformer by the Departmental authority at Authorized maintenance work shop. (iii) Cost for transportation and lifting of Transformer shall be measured and paid separately.
Material and labour for Transportation and lifting of Transformer 11KV/433V of capacity up to 500 KVA including loading and unloading by suitable capacity crane to workshop for repair as per SI Item Nos 70&71 above in a load carrier vehicle from Electrical installations at INS Hansa area to workshop and returning back to site at its existing installation place all as specified and as directed.
All as per item no 72 here in before but for transformer 11KV/433 V of capacity above 500 KVA to up to 1000 KVA.
Supply and fix DO fuse elements Rating 11 KV capacity 05 Amps.
Supply and fix DO fuse elements Rating 11 KV capacity 10 Amps.
Supply and fix DO fuse elements Rating 11 KV capacity 20 Amps.
Supply and fix DO fuse elements Rating 11 KV capacity 30 Amps.
Supply and fix D.O fuse element Rating 11 KV capacity 40 Amps.
Supply and fix D.O fuse element Rating 11 KV capacity 50 Amps.
Material and labour for preparation of old cement coated surface, cleaning the surface of the RCC Pole (HT) above the ground level including coping area with 2 coats of ACC exterior emulsion paint over a coat of cement primer after preparation of surface and all as specified and as directed.
Material and labour for Painting of 2 pole structure including preparation of old cement coated surface,angles,cross arms & painting of RCC poles with two coats of ACC exterior emulsion paint over a coat of Cement primer and painting of angle, cross arms, and connecting accessories with one coat of red oxide primer and two coats of aluminium paints all as specified and as directed.
All as per item no 81 here in before but for 4 pole structure
All as per item no 81 here in before but for 8 pole structure as required.
Material and labour for polymer Post / disc / pin insulator of 11 KV capacity carefully and re-fixing the same in the new cross arms / structure including replacement of new hardware such as GI spindle, nut, bolt and washers complete all as directed
Supply, install, testing and commissioning of HT Feeder pillar Box outdoor type 11KV 50 HZ 3 Phase of suitable size not less than (1500x1500x1200 mm) duly powder coated with copper bus bar of 60x5 mm including suitable insulators. It comprises following accessories such as totally enclosed self supporting structure / cubicle, fully compartmentalized type, weather proof, suitable for outdoor type, bottom cable entry with suitable cable glands ,CRCA steel sheet of thickness 3.15 mm with suitable angle iron frame work and legs of ISA 50x50x5 mm, with four legs grouted to PCC (1:2:4) type B1, foundation block with suitable mounting arrangement for bus bars with sloping canopy at top, double hinged doors at front with suitable locking arrangement, sheet will be treated under 8 - tank metal treatment process, complete all as specified and directed.
Supply and fix in repairs for epoxy insulator suitable for 11 KV reel type inside HT feeder pillar box outdoor type including replacement of new nut, bolt and washer on bus bar and base complete all as specified and directed.
Danger notice plate of 1.6mm thick mild steel sheet, vitreous enameled white, with letters, figures and conventional skull and bones in signal red colour and fixed with M.S. clamps, bolts and nuts of approved size, for HT, 25x20cm size
Supply and fixing cable route indicator made out of PCC 1:2:4 of size 20cmx20cmx90cm dully painted with red colour by two coat of enamel paint and writing MES No details of HT cable with white paint on all sides complete all as directed.
Supply and fix in repairs lightning arrester expulsion type complete with all fittings transmission class, discharge capacity 65 kilo amps, suitable for 11 KV all as directed
Carry out materials /mechinaries, labour for fault finding of 11 KV HT under ground cable length 1.5 KM in case of cable fault such as short circuit/burn out/ earth fault etc complete all as specified and directed.
Supply and fix control relay for charging motor 110V AC/DC, 220V AC/DC of suitable size for ACB of capacity 100 to 1200 Amps complete all as specified and as directed.
Supply only rubber hand gloves of 11 KV grade ISI marked.
Supply only fiber glass discharge rod in three sections and aluminium head with complete accessories suitable for 11 KV of 20 feet height.
Supply and fix in repairs sealed maintenance free battery 2 Volts 100 Amps for UPS supply including necessary connections complete all as directed.
Supply and fix MS Galvanised Chain link fencing including line wires any mesh, size and type to any type standard , rails, straining blots etc. including provision of binding wire.
Material and labour in Providing reinforced cement concrete type B-l, 1:2:4 (20 mm graded aggregate) in precast posts, fencing posts, straining or terminal posts, struts etc. for fencing, average sectional area n exc 100 sq. cm, with or without chamfered angles and flat, splayed, rounded or mitred tops as directed and fixed
Supply and fix in repairs Galvanaised Iron cross arms channel, bracing, support, clamps etc fabricated structured steel, sections, including nuts, bolts, washers etc and cutting to required length beat to any shape drilling holes, fixed on poles or jointed by means of elect welding complete including painting with 2 coats of aluminum paint over a coat of red oxide primer after preparation of surfaces including taking down / dismantling the old items complete all as directed.
Charges for testing of faulty transformer by conducting required tests and submit report to the dept, following tests to be carried out by contractor through experts :- checking of all connections, verify the high voltage and low voltage cables are correctly terminated and all connections are in accordance, Insulation testing, Tap changer operation, incoming and outgoing voltage, silica gel in breather, oil level in conservator, check oil leakage and submit the report of the faulty transformer all as specified and as directed.
Shree Ram Enterprises (BID ID -3387956)
S and G Constructions (BID ID -3396132)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .