Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.2 LAccepted-Finance | ₹1.2 L | L1 | Accepted-Finance Accepted being L1 |
| Sl No | Description | Qty | Unit | COOL CONTROL CORPORATION L1 |
|---|---|---|---|---|
| 1.01 | Replacement of faulty 630A triple pole MCCB (EE make) in existing MV panel with new 630A triple pole MCCB minimum 36kA breaking capacity with thermal magnetic release alongwith spreader terminals including making necessary addition alteration work in existing compartment, cutting, welding, drilling holes, painting etc and making connections with panel busbar complete as required. (L&T make model DN3 630D/ SS make ) | 1 | Job. | 54,600 ₹64,428 |
| 1.02 | Provision of 250A four pole MCCB in existing MV panel minimum 36kA breaking capacity with thermal magnetic release alongwith spreader terminals including making necessary addition alteration work in existing compartment, cutting, welding, drilling holes, painting etc and making connections with panel busbar complete as required. (L&T make model DN2 250D/ SS make ) | 1 | Job. | 39,400 ₹46,492 |
| 1.03 | Providing, Supplying & fixing 3.5 core 70 Sq.mm Aluminium condr XLPE insulated armoured cable with interconnection between busbar and MCCB complete as reqquired (approx 7mtr length). (ISI Marked) | 1 | Job | 9,250 ₹10,915 |
Tender Value
₹1.2 L
EMD Value
₹2,321
Closing Date
9 Dec 2025, 4:00 pmClosed
Executive Engineer (Electrical)
O/o Executive Engineer (Electrical) BSNL Electrical Division 1st Floor, Bhopal House, Lalbagh Lucknow
Operation and Comprehensive Maintenance of electro mechanical services at T.E. Mahanagar, Lucknow. SH Repairing/ Replacement of faulty MCCBs in existing MV panel in transformer sub station
2025_BSNL_257679_1
74/TEDL/BSNL/2025-26, Dated 28/11/2025
Open Tender
Electrical Works
30 days
LUCKNOW
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
A.O. (Cash), O/o The GMTD, BSNL, Lucknow
₹2,321
23 Mar 2026
2 Dec 2025
10 Dec 2025
2 Dec 2025
9 Dec 2025
2 Dec 2025
Replacement of faulty 630A triple pole MCCB (EE make) in existing MV panel with new 630A triple pole MCCB minimum 36kA breaking capacity with thermal magnetic release alongwith spreader terminals including making necessary addition alteration work in existing compartment, cutting, welding, drilling holes, painting etc and making connections with panel busbar complete as required. (L&T make model DN3 630D/ SS make )
Provision of 250A four pole MCCB in existing MV panel minimum 36kA breaking capacity with thermal magnetic release alongwith spreader terminals including making necessary addition alteration work in existing compartment, cutting, welding, drilling holes, painting etc and making connections with panel busbar complete as required. (L&T make model DN2 250D/ SS make )
Providing, Supplying & fixing 3.5 core 70 Sq.mm Aluminium condr XLPE insulated armoured cable with interconnection between busbar and MCCB complete as reqquired (approx 7mtr length). (ISI Marked)
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx