Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.3 CrAccepted-Finance 8 TOWNSHEND ROAD KOLKATA 700025 | KOLKATA | KOLKATA | WEST BENGAL | 700025 | ₹2.3 Cr | L1 | Accepted-Finance LOWEST BIDDER |
| 2 | L2₹2.4 Cr+₹9.0 L (3.93%)Rejected-Finance 258 A LAKE TOWN BLOCK B | ₹2.4 Cr+₹9.0 L (3.93%) | L2 | Rejected-Finance 2ND LOWEST BIDDER |
| 3 | L3₹3.3 Cr+₹1.0 Cr (44.0%)Rejected-Finance 86 TOLLYGUNGE CIRCULAR ROAD KOLKATA WEST BENGAL 700053 | KOLKATA | KOLKATA | WEST BENGAL | 700053 | ₹3.3 Cr+₹1.0 Cr (44.0%) | L3 | Rejected-Finance 3RD LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹5.3 L
Closing Date
13 May 2023, 4:30 pmClosed
Superintending Engineer, SWEC, PWD
OFFICE OF THE SUPERINTENDING ENGINEER (P.W.D) South-Western Electrical Circle PWD Compound, Midnapore, Paschim Medinipur
Construction of Integrated District Court Complex at Jhargram within Jhargram Court compound in the district of Jhargram ----Air conditioning work at Main Building and ADR Building.
2023_WBPWD_500758_1
WBPWD/SE/SWEC/NIQ46/2022-23
Open Tender
ELECTRICAL WORKS ORG
Item Rate
60 days
JHARGRAM
Please refer Tender documents.
3 documents required · 3 mandatory
₹5.3 L
O/O of SE, SWEC,PWD, PWD Compound, Midnapur
14 Jun 2023
31 Mar 2023
15 May 2023
31 Mar 2023
13 May 2023
18 Apr 2023
10 Apr 2023
Amount
Sub Head 1 : High Static Pressure Ductable Split Air Conditioner Unit
Supply & Delivery of Ceiling Suspended Ductable type Split Airconditioners having Microprocessor Based Control System and the following specification
Nominal Cooling Capacity -22 TR
No of IDU - 1 No
No of ODU - 2 No.
Compressor - 1 Nos Hermetically Sealed Scroll Compressor for each ODU.
Refrigerent - R 410A /R407C/R-22
Condenser & Cooling Coil : Copper coil
Power Supply : 415V, 50 Hz, 3 Ph AC (with applicable tolarance)
Suitable for operation in 50 Degree Centigrade Ambient Temperature
Make - Carrier/ Voltas/ Blue Star/ Mitsubishi Electric / Hitachi/ Daikin
Supply & Delivery of Ceiling Suspended Ductable type Split Airconditioners having Microprocessor Based Control System and the following specification
Nominal Cooling Capacity -17 /16.5 TR
No of IDU - 1 No
No of ODU - 2 No.
Compressor - 1 Nos Hermetically Sealed Scroll Compressor for each ODU.
Refrigerent - R 410A /R407C/R-22
Condenser & Cooling Coil : Copper coil
Power Supply : 415V, 50 Hz, 3 Ph AC (with applicable tolarance)
Suitable for operation in 50 Degree Centigrade Ambient Temperature
Make - Carrier/ Voltas/ Blue Star/ Mitsubishi Electric / Hitachi/ Daikin
Supply & Delivery of Ceiling Suspended Ductable type Split Airconditioners having Microprocessor Based Control System and the following specification
Nominal Cooling Capacity -11 TR
No of IDU - 1 No
No of ODU - 2 No.
Compressor - 1 Nos Hermetically Sealed Scroll Compressor for each ODU.
Refrigerent - R 410A /R407C/R-22
Condenser & Cooling Coil : Copper coil
Power Supply : 415V, 50 Hz, 3 Ph AC (with applicable tolarance)
Suitable for operation in 50 Degree Centigrade Ambient Temperature
Make - Carrier/ Voltas/ Blue Star/ Mitsubishi Electric / Hitachi/ Daikin
Supply & Delivery of Ceiling Suspended Ductable type Split Airconditioners having Microprocessor Based Control System and the following specification
Nominal Cooling Capacity -8.75 TR
No of IDU - 1 No
No of ODU - 1/2 No.
Compressor - 1 Nos Hermetically Sealed Scroll Compressor for each ODU.
Refrigerent - R 410A /R407C/R-22
Condenser & Cooling Coil : Copper coil
Power Supply : 415V, 50 Hz, 3 Ph AC (with applicable tolarance)
Suitable for operation in 50 Degree Centigrade Ambient Temperature
Make - Carrier/ Voltas/ Blue Star/ Mitsubishi Electric / Hitachi/ Daikin
Installation Testing and Commissioning of Ductable Split AirConditioners by making scaffolding arrangement as per site condition, Supply of necessary Refrigerant, connecting Control & power cabling & other necessary materials to complete the job.
22 TR Ceiling Suspended Ductable type Split AC
17/16.5 TR Ceiling Suspended Ductable type Split AC
11 TR Ceiling Suspended Ductable type Split AC
8.75 TR Ceiling Suspended Ductable type Split AC
Sub Head 2 : Refrigerent Piping
Supply, Installation, testing and commissioning including vaccumiazation and Nitrogen testing of following nominal sizes of soft/hard drawn copper refrigerant piping for the system, complete with fittings, with suitable adjustable ring type hanger supports, jointing/brazing including accessories, insulated with XPLE Class-O tubular insulation/with Class-O closed cell elastometric nitrile rubber tubular sleeves sections of specified thickness as given below for Suction and Liquid lines, all accessories as per specifications etc. as required :
12.7 mm dia (OD) with tube thickness 1.2 mm with 9 mm thick insulation
15.86 mm dia (OD)with tube thickness 1.2 mm with 9 mm thick insulation
19 mm dia (OD) with tube thickness 1.2 mm with 9 mm thick insulation
28.58 mm dia (OD) with tube thickness 1.2 mm with 9 mm thick insulation
Supply & Installation of 6mm Nitrile Rubber insulated PVC / HDPE pipes of following sizes with fitting, accessories, bends, elbows, tees, flanges, U-trap, wall sleeves, hangers, supports, anchors etc for draining condensate water from indoor unit to the nearest drain point.
25 mm Dia
32 mm Dia
Sub-Head 3 - Ducting
Supply, installation, balancing and commissioning of fabricated at site GSS sheet metal ( Make-Tata Steel/Sail/Jindal ) rectangular/ round ducting complete with neoprene rubber gaskets,elbows,splitter dampers, vanes, hangers, supports etc as per approved drawings and specifications of following sheet complete as required
Thickness 0.55 mm sheet
Thickness 0.71 mm sheet
Duct tharmal insulation by supplying and fixing of 9mm thickness duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete as per specifications and as required.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills with aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Grills with louvers but without volume control dampers complete as required
Supplying & fixing of powder coated extruded aluminium Supply air Diffuserswith aluminium volume control dampers as per specifications.
Supplying & fixing of powder coated extruded aluminium Return Air Diffusers with louvers but without volume control dampers complete as required
Supply, installation, testing and commissioning of GI Mechanical Fire damper complete with neoprene rubber gaskets, nuts, bolts, screws linkages, flanges etc, as per specifications for stand by units
Supply, installation, testing and commissioning of Flexible Canvas Connection as per direction of the EIC.
Supplying, fixing, testing & commissioning of fresh air provision as per direction of the EIC incl. filter, motorised damper, bird screen etc complete as required.
SITC of Variable air volume box to control the air delivery volume complete with actuator, thermostat, corded remote and linkages. Make - Honeywell / Systemair / JCI / Trane/ Diakin / Trox /Johnson
S&F 230 V UV Lamp with mounting arrangement & necessary wiring as required.
Sub-Head 4-- Misceleneous Items
Supply, fabrication & fixing 3 Nos. M.S. u-channel of 6mm thick of size (75 mm x 40 mm x 40mm) of 1 mtr length for making platform for installation of outdoor unit of ductable split AC incl. drilling 2 Nos. holes in each channel including cutting holes the wall & grouting the same with Cement concrete (1:11/2 :3) etc. fabricated with horizontal angle of 50mm x 50mm X 6mm 6mm of 2 Mtr length including supporting angle 50mm x 50mm x 6mm in each platform in outer edge for transmitting the load centrally through 2Nos.(50mm x 50mm x6mm) Angle inserted into the exiting wall. The platform should be baricated with verticle angle of 25mm x 25mm x 6mm of 1 mtr. length, abricated on the surface of each Horizontal channel & Angles & interconneed by 25mm x 25mm x 5mm MS patti. Area of platform is 3Mtr. x 1 Mtr.
Supply, laying and termination of 1.1 kv grade following size PVC insulated PVC sheathed unarmoured Copper Cable (make:-Finolex/RR Kable/Polycab/Havells/Gloster)
4C X 1.5 SqMM
4C X 2.5 SqMM
Fabrication & erection of boxing for covring the indoor units made of 50mmX 25 mm Aluminium channel with 3 mm thick indoor type ACP (Aludecor/Alstrong) sheet including trap door, duly insulated for maintanance & painting as per direction of EIC
Chargs for lifting of IDU & ODU units incl. scaffolding arrangement as per requirement all complete as per direction of EIC
Supply & fixing of Motorised Fire damper made out of 18 SWG GI Sheet [ Make System air / Premire /Caryaire/airmaster ]
S&F of Actuator with control panel for Fire Damper.
Sub Head 5 : Room Air Conditioner Hi-wall split
Supply & Delivery of Hi-wall Split Air Conditioner having following specification.a. ISEER - As per 3 Star/2018-19 of BEE/BIS b. IS compliance - IS 1391 c. Refrigerant - R410A/R32 d.Compressor - Rotary/Scroll e.Evaporator & Condensor Coil : Copper f.Operating Outdoor Temparature = 50ºC and above
Power Supply - 230V,50Hz ( +Tolerrance as per applicable standard)The scope of work is also includes supply of following (i) Necessary refrigeration copper line with nitrial rubber insulation - 3 mtr (ii) necessary copper cable ( FRLS type - Make Finolex/RRKable/Polycab/Havells/Gloster) - 3mtr. The RACs should have the following Capacity -
[Make: Mitsubishi Electric / General / Daikin / Hitachi]
Installation, Testing & Commissioning of Indoor & Outdoor unit of above Hi wall split AC machine after making hole in wall etc as per direction of EIC including Supply of required Refrigerant, S&F of necessary fixing arrangement for indoor and 40 x 40 x 5 mm MS angle iron frame for outdoor unit, duly painted, laying and making connection of refrigeration pipe, power cable, drain pipe etc as per direction of the EIC.
S&F of additional following items for length exceeding 3 mtr for complete installation and commissioning of aboove AC machines.
(i) Supply & Fixing of extra refrigerant pipe with insulation foam insulation (as requisite dia for suction and liquid line )
(ii) 3 core PVC insulated FRLS grade copper cable of requisite size ( make : Finolex/RR Kable/Polycab/Havells/Gloster)
Supply & Fixing of PVC drain pipe (make approved by EIC)
TERMS & CONDITIONS
1. Rate should be quoted inclusive of all prevailing Taxes & Duties
2. The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them.
3.Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/submission of bill.
4. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
GATES
Lyric International
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .