Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹31.7 LAccepted-AOC | L-1 | Accepted-AOC Being the lowest bidder | |
| 2 | L-2₹33.6 L+₹1.7 L (5.31%)Rejected-AOC | L-2 | Rejected-AOC Not being the lowest bidder |
Tender Value
Refer Docs
EMD Value
₹66,400
Closing Date
3 Mar 2021, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
LT COL SANGRAM SINGH
GE Kaluchak Pin-900673 C/o 56 APO
PROVN OF POWER FACTOR IMPROVEMENT PANEL 02 SUBMERSIBLE PUMPING SET CEILING FANS LED LIGHT FITTINGS SPL REPAIRS REPLACEMENT OF EXISTING STREET SECURITY LIGHTS WITH LED LIGHTS AND REPAIRS TO LT CABLE AT KALUCHAK RATNUCHAK AND BD BARI MIL STN UNDER GE
2021_MES_417479_1
GE/KC/NIT-68/2020-21
Open Tender
Miscellaneous Works
Item Rate
180 days
Kaluchak
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE Kaluchak
₹66,400
Yes
29 Apr 2021
30 Jan 2021
5 Mar 2021
30 Jan 2021
3 Mar 2021
15 Feb 2021
30 Jan 2021 - 13 Feb 2021
60 days
Amount
Excavation in trenches not exceeding 1.5 mtr wide and not exceeding 1.5 mtr in depth and getting out in any type of soil for foundation of pole, stay, taking up or laying of cable etc, complete all as specified & directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in the cost of excavation.
Returning, filling in (soil), including spreading, leveling, watering and well ramming in layers not exc. 25cm, complete all as specifed & directed.
Removing excavated material to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point, complete all as specified & directed.
Sand cushioning to under ground cable, laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete punned to 18cm, complete all as specified and directed. Note:- Punned thickness of sand will be measured and paid.
Brick well burnt locally available sub class 'B' laid over sand cushioning for mechanical cable protection in trenches with width of brick perpendicular to the length of cable, complete all as specified & directed.
Galvanised iron tube 40mm bore light grade (ISI marked) for cable protection to poles/under floor/under roads/alongwith walls complete including MS clamps of flat iron 25x3mm duly painted, GI nuts, bolts and washers & sealing of pipe ends with approved sealing compound, complete all as specified & directed.
Cutting of road for passing cable through roads including resurfacing of disturbed road surface with premixed carpet, WBM etc of existing specifications to match with original, complete all as specified and directed. Note : Due care shall be taken while deciding cable route for excavation. However any damage to Signal, BSNL, MES cable water/sewage pipe or any other service while excavation will be made good by the contractor and cost of the same for jointing material & labour is deemed to be included in this item.
PVC insulated weather proof twin core 2.50 sqmm (nominal area) aluminium conductor cable, 1100 volts grade, drawn in & including PVC conduit of suitable size with clamps (3 Nos), nuts, bolts etc from junction box to street light connection, complete all as specified & directed.
Pole mounted distribution box powder coated for street light made of CRCA sheet of 3mm thick, dust and vermin proof, outdoor type of size 300mm x 260mm x 165mm with arrangement of incoming and outgoing feeder comprising of TPN aluminium bus bar of capacity 32 Amp 415 volts, single MCB SP, 230 V, 10 Amp 10 KA (in accordance with IS/IEC 60898-1), fixed on porcelain insulators, making holes on strips for connecting cables, fixed to street light pole with and including 2 Nos MS clamps made of FI 25x5mm with nut, bolt & washer duly painted with two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer , complete all as specified & directed. Note : Wiring from DB to light fitting shall be measured & paid saperately under respective item of Sch 'A'.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm 4 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Intergral LED security light luminaire 90W LED, 230 volts made up of pressure die-cast aluminium housing with toughned glass and high power LEDs and secondry lenses with IP66 protection, efficacy 110 lumens/watt, external 10KV, 440 volt Surge Protection Device and inbuilt 4KV surge protection device, IP67 potted isolated driver with operating range 90V to 340V AC CCT 5700K, LED life -1 lakh burning hours, fixture should withstand 320 volt upto 48 hrs, auto cut off >320 volts & restart, 440 Volt sustain upto 8 hrs, NABL acreddited LM79 report. mounted on GI bracket fixed on PCC/Steel pole, making connection with PVC copper conductor cable of 1.5 sqmm, complete all as specified & directed. Make. Crompton Greaves : Cat Part No. LSTP-90-CDL-M or equivalent model of make specified in List of Makes/ Manufacturers/ Producers here-in-after.
Supply, hanging and testing of 1200mm sweep, 230 volts, AC ceiling fans, 2 star BEE rated energy efficient ceiling fan conforming to IS:374-2019, having 3 blades alongwith copper wound stator (capacitor start) with minimum air delivery 210 cubic metre per minute, power consumption not more than 50 watt, top speed minimum 370 RPM or higher, speed control by 5 step electronic regulator including capacitor, down rod, canopy, making connection with three core flexiable copper cable of 1.50 Sqmm upto ceiling rose, complete all as specified & directed. Make : Havells/ Crompton Greaves/ Bajaj/ Usha
Street light bracket made out of 40mm bore medium grade pipe of 1.50m length, bent to required shape, fixed on PCC/Steel pole with 02 Nos. clamps of flat iron (40 x 6mm), nuts, bolts and washers including painting with two coats of aluminium paint over a coat of red oxide zinc chrome primer, complete all as specified & directed.
Steel tubular swaged poles in vertical position swaged type 410-SP-31, 9 Mtr long, ISI marked complete with 6mm thick mild steel base plate, finial taper plug, bolts, nuts washers and screws as required duly painted with two coats of aluminium paint over a coat of red oxide primer above ground level including painting throughout internally & below GL (externally) with two coats of bituminous paint, numbering of poles with cut stencil lettering in size 6mm thick and 50mm high and yellow and black strips of size 30cm width each with synthetic elamel paint upto 1.5m above coping etc, complete all as specified and directed. Note:- 1. Earth work and PCC will be measured and paid seperately under appropriate items.
PCC 1:4:8 type D-2 using 40mm graded crushed stone aggregate as in foundation of poles etc including necessary form work, complete all as specified & directed.
PCC 1:2:4 type B1 using 20mm graded crushed stone aggregate as in coping of pole etc including necessary form work, complete all as specified & directed.
LED tubelight fitting 1 x 20W inverter batten type fitting, 4 feet long, aluminium extruded housing, IP-20 rated, voltage 230 volts (operating range 140 volts to 270 volts), 50 Hz, system wattage 20 watt ±10%, system current not less than 102mA, power factor more than 0.95, system lumen efficacy 100 lm/watt CCT 6500K, CRI more than 80, THD less than 30%, driver efficiency more than 85% with all accessories pre-wired and making connection with three core PVC insulated overall sheathed flexiable copper cable of size 0.75sqmm from ceiling rose to light fitting, complete all as specified & directed.
Supply, installation, commissioning and testing of BEE star rated submersible pump set conforming to IS:8034:2002 (ISI marked) with Amdt No.1 (with upto date ammendments) suitable for bore size 100/150mm, and 65/80mm dia discharge pipe, not less than 8 stage (as per manufacturers design) discharge capacity not less than 600 LPM at 98 metre head, motor rating 20 HP, pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor conforming to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 rpm synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply.
The motor shall be provided with suitable size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/bolts/washers etc as required at site, complete all as specified & directed. Make of Pump and Motor: Kirloskar Cat Part No.KS6D-2016 or equivalent of Crompton /KSB Note : All testing arrangement of pumpset should be made avalible by contractors for which rates deemed to be included in quoted rate.
Supply, installation, commissioning and testing of BEE star rated submersible pump set conforming to IS:8034:2002 (ISI marked) with Amdt No.1 (with upto date ammendments) suitable for bore size 100/150mm, and 65/80mm dia discharge pipe, not less than 8 stage (as per manufacturers design) discharge capacity not less than 600 LPM at 86 metre head, motor rating 17.5 HP, pump in multistage construction with radial or mixed flow impellers coupled with water filled squirrel cage induction motor 3 phase 415 volts, stainless steel motor casing, pump impellers made of bronze (material of main parts of pump set shall be as per clause 6.2 of IS:8034-2002 with upto date ammendments) for use in borewells for handling clear water having motor conforming to IS 9238:1995 with amdt 1&2 (with upto date ammendments) of wet type for continuous rating operating at 2900 rpm synchronous suitable for 415 volts ,+/- 6% 3 phase AC supply.
The motor shall be provided with suitable size 3 mtr length PVC copper cable flexible insulated and PVC sheathed 3 core flat type of ISI marked and supplied by OEM including providing suitable MS clamp made from 10mm thick MS plate of 50mm width total length of MS clamp shall be 375mm to 425mm apprx with suitable drill holes two nos on each side alongwith suitable nuts/bolts/washers etc as required at site, complete all as specified & directed. Make of Pump and Motor: Kirloskar Cat Part No.KS6D-1814 or equivalent of Crompton /KSB Note : All testing arrangement of pumpset should be made avalible by contractors for which rates deemed to be included in quoted rate.
Supply, installation, commissioning and testing of factory manufactured CPRI approved APFC Panel (Automatic & Manual operation) with 7% aluminium reactor of capacity 50 KVAR (Output) @ 440 Volt AC interconnection with LT Panel/ Transformer (outdoor/ indoor) with appropriate size of electric power cable 1.1KV. The stage rating shall be 3 x 10KVAR + 1 x 20 KVAR. The APFC Panel shall be fully type tested at an independent laboratory and shall comply with IEC: 61439-1&2 and IEC:61921, IS:16636-2017. The degree of protection of enclosure system of the APFC Panel shall be min IP-54 (Outdoor) in accordance with IEC 60529. The capacitor bank shall be internet of things (IoT) enabled and communicable / integrable with BMS. The APFC Panel shall be Outdoor type confirming to IS 13341:1992 & IS13440:1993 floor mounted design fabricated out of 3.15mm CRCA Sheet treated through chemical with 8 tank process method of degreasing, derusting and phosphating powder coating (60-80 microns) painted in SIEMENS GREY (RAL 7032) shade powder coating paint, weather, dust and vermin proof suitable for humidity
upto 95% and having four nos iron legs made of MS angle 50x50x6mm thick, 60cm long angle iron below frame with front door and side/back opening having locking arrangement prewired with copper conductor PVC insulated wire size 2.5 Sqmm/ extension strips and connected with suitable size thimbles & lugs. The legs duly embedded in ground 45cm in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate. Cable entry from bottom, transparent acrylic sheet/ bakelite sheet will be provided for shrouding. Average daily temperature +35 degree celcius max, Ambient temperature -5 degree celcius to 40 degree celcius, maximum altitude 2000M. The APFC Panel shall be comprising of the followings:-
(C) PF Regulator / APFC Relay : Advanced Range PF Regulator / microprocessor based APFC relay (VARPLUS LOGIC OF SCHNEIDER) having 6 steps with a LCD Display, voltage range: 90V-550V, 50Hz/60Hz, CT Input:1A/5A with a built in RS 485 communication port .The PF Regulator shall be of certified design confirming to IEC:61326. Make : ABB/ Schneider/ Siemens/ L&T (D) Accessories for 20KVAR - 1 STEPS (i) Capacitor Units: The capacitor unit (1 No) shall be metalized polypropylene film with Zn/Al alloy for 20KVAR(1x22.4KVAR) at 440Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof. Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un, 8h every 24Hour. The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T
(ii). Short Circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA. The MCCB shall be of certified design MCCB 63A TP 36KA T/M based release with O/L & S/C Protection-01 No confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 63A - 01 No rated for 230 volts AC and shall be 3 pole type and employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor : Harmonics blocks reactors (01 no) Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 20 KVAR AT 440 VOLTS) and shall be of iron cored type . The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (E) Accessories for 10KVAR -3 STEPS (i) Capacitor Units : The capacitor unit (03 NOS) shall be metalized polypropylene film with Zn/Al alloy for 10KVAR (1x11.3KVAR) at 440 Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof .Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un,8h every 24Hour.
The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T (ii). Short circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA . The MCCB shall be of certified design MCCB 25A TP 36KA T/M based release with O/L & S/C Protection--03 nos confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 25A -03 Nos rated for 230 volts AC and shall be 3 pole type and shall be employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor: Harmonics blocks detuned reactors -03 nos Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 10 KVAR AT 440 VOLTS) and shall be of iron cored type. The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (F). Ventilating fans of required size shall be provided to dissipate the heat produced by the capacitor bank components like the capacitor units, reactors, contactors, breakers etc. The capacitors banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted alongwith the offer.
Supply, installation, commissioning and testing of factory manufactured CPRI approved APFC Panel (Automatic & Manual operation) with 7% aluminium reactor of capacity 60 KVAR (Output) @ 440 Volt AC interconnection with LT Panel/ Transformer (outdoor/ indoor) with appropriate size of electric power cable 1.1KV. The stage rating shall be 4 x 10KVAR + 1 x 20 KVAR. The APFC Panel shall be fully type tested at an independent laboratory and shall comply with IEC: 61439-1&2 and IEC:61921, IS:16636-2017. The degree of protection of enclosure system of the APFC Panel shall be min IP-54 (Outdoor) in accordance with IEC 60529. The capacitor bank shall be internet of things (IoT) enabled and communicable / integrable with BMS. The APFC Panel shall be Outdoor type confirming to IS 13341:1992 & IS13440:1993 floor mounted design fabricated out of 3.15mm CRCA Sheet treated through chemical with 8 tank process method of degreasing, derusting and phosphating powder coating (60-80 microns) painted in SIEMENS GREY (RAL 7032) shade powder coating paint, weather, dust and vermin proof suitable for humidity
upto 95% and having four nos iron legs made of MS angle 50x50x6mm thick, 60cm long angle iron below frame with front door and side/back opening having locking arrangement prewired with copper conductor PVC insulated wire size 2.5 Sqmm/ extension strips and connected with suitable size thimbles & lugs. The legs duly embedded in ground 45cm in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate. Cable entry from bottom, transparent acrylic sheet/ bakelite sheet will be provided for shrouding. Average daily temperature +35 degree celcius max, Ambient temperature -5 degree celcius to 40 degree celcius, maximum altitude 2000M. The APFC Panel shall be comprising of the followings:-
(C) PF Regulator / APFC Relay : Advanced Range PF Regulator / microprocessor based APFC relay (VARPLUS LOGIC OF SCHNEIDER) having 6 steps with a LCD Display, voltage range: 90V-550V, 50Hz/60Hz, CT Input:1A/5A with a built in RS 485 communication port .The PF Regulator shall be of certified design confirming to IEC:61326. Make : ABB/ Schneider/ Siemens/ L&T (D) Accessories for 20KVAR - 1 STEPS (i) Capacitor Units: The capacitor unit (1 No) shall be metalized polypropylene film with Zn/Al alloy for 20KVAR(1x22.4KVAR) at 440Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof. Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un, 8h every 24Hour. The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T
(ii). Short Circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA. The MCCB shall be of certified design MCCB 63A TP 36KA T/M based release with O/L & S/C Protection-01 No confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 63A - 01 No rated for 230 volts AC and shall be 3 pole type and employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor : Harmonics blocks reactors (01 no) Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 20 KVAR AT 440 VOLTS) and shall be of iron cored type . The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (E) Accessories for 10KVAR - 4 STEPS (i) Capacitor Units : The capacitor unit (04 NOS) shall be metalized polypropylene film with Zn/Al alloy for 10KVAR (1x11.3KVAR) at 440 Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof .Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un,8h every 24Hour.
The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T (ii). Short circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA . The MCCB shall be of certified design MCCB 25A TP 36KA T/M based release with O/L & S/C Protection--03 nos confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 25A -01 Nos rated for 230 volts AC and shall be 3 pole type and shall be employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor: Harmonics blocks detuned reactors -01 nos Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 10 KVAR AT 440 VOLTS) and shall be of iron cored type. The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (F). Ventilating fans of required size shall be provided to dissipate the heat produced by the capacitor bank components like the capacitor units, reactors, contactors, breakers etc. The capacitors banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted alongwith the offer.
Supply, installation, commissioning and testing of factory manufactured CPRI approved APFC Panel (Automatic & Manual operation) with 7% aluminium reactor of capacity 100KVAR (Output) @ 440 Volt AC interconnection with LT Panel/ Transformer (outdoor/ indoor) with appropriate size of electric power cable 1.1KV . The stage rating shall be 3x10KVAR + 1 X 20 KVAR + 1 X 50 KVR. The APFC Panel shall be fully type tested at an independent laboratory and shall comply with IEC: 61439-1&2 and IEC:61921, IS:16636-2017. The degree of protection of enclosure system of the APFC Panel shall be min IP-54 (Outdoor) in accordance with IEC 60529. The capacitor bank shall be internet of things (IoT) enabled and communicable / integrable with BMS. The APFC Panel shall be Outdoor type confirming to IS 13341:1992 & IS13440:1993 floor mounted design fabricated out of 3.15 mm CRCA Sheet treated through chemical with 8 tank process method of degreasing, derusting and phosphating powder coating (60-80 microns) painted in SIEMENS GREY (RAL 7032) shade powder coating paint, weather, dust and vermin proof suitable for humidity
upto 95% and having four nos iron legs made of MS angle 50x50x6mm thick, 60cm long angle iron below frame with front door and side/back opening having locking arrangement prewired with copper conductor PVC insulated wire size 2.5 Sqmm/ extension strips and connected with suitable size thimbles & lugs. The legs duly embedded in ground 45cm in PCC 1:3:6 type C1 using 20mm graded crushed stone aggregate. Cable entry from bottom, transparent acrylic sheet/ bakelite sheet will be provided for shrouding. Average daily temperature +35 degree celcius max, Ambient temperature -5 degree celcius to 40 degree celcius, maximum altitude 2000M. The APFC Panel shall be comprising of the followings:-
(C) PF Regulator / APFC Relay : Advanced Range PF Regulator / microprocessor based APFC relay (VARPLUS LOGIC OF SCHNEIDER) having 12 steps with a LCD Display, voltage range: 90V-550V, 50Hz/60Hz, CT Input:1A/5A with a built in RS 485 communication port .The PF Regulator shall be of certified design confirming to IEC:61326. Make : ABB/ Schneider/ Siemens/ L&T (D) Accessories for 20KVAR - 1 STEPS (i) Capacitor Units: The capacitor unit (1 No) shall be metalized polypropylene film with Zn/Al alloy for 20KVAR(1x22.4KVAR) at 440Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof. Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un, 8h every 24Hour. The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T
(ii). Short Circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA. The MCCB shall be of certified design MCCB 63A TP 36KA T/M based release with O/L & S/C Protection-01 No confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 63A - 01 No rated for 230 volts AC and shall be 3 pole type and employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor : Harmonics blocks reactors (01 no) Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 20 KVAR AT 440 VOLTS) and shall be of iron cored type . The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (E) Accessories for 10KVAR -3 STEP (i) Capacitor Units : The capacitor unit (03 NOS) shall be metalized polypropylene film with Zn/Al alloy for 10KVAR (1x11.3KVAR) at 440 Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof .Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un,8h every 24Hour.
The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T (ii). Short circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA . The MCCB shall be of certified design MCCB 25A TP 36KA T/M based release with O/L & S/C Protection--03 nos confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 25A -01 No rated for 230 volts AC and shall be 3 pole type and shall be employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor: Harmonics blocks detuned reactors -01 no Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 10 KVAR AT 440 VOLTS) and shall be of iron cored type. The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (F) Accessories for 50KVAR -1 STEP (i) Capacitor Units : The capacitor unit (02 NOS) shall be metalized polypropylene film with Zn/Al alloy for 50KVAR (2x28.10KVAR) at 440 Volts. The capacitors shall be encapsulated in an aluminium can. The capacitor unit shall have a rated voltage of 480Volts and shall have a maximum over current capacity of 2.5In. The capacitor unit shall have a built in 3 phase over pressure protection and shall have discharge resistors (50V in 1min) factory fitted and shall be tamper proof .Capacitance Tolerance -5% +10%. Maximum permissible over voltage 1.1 x Un,8h every 24Hour.
The capacitor unit shall be of certified design confirming to IS-13340-1993,13341-1992 & IEC-60831-1&2. Make : ABB/ Schneider/ Siemens/ L&T (ii). Short circuit and Overload Protection : Each stage of the APFC Panel shall have a suitably rated MCCB for short circuit and overload protection. The over current setting shall be adjustable & breaking capacity Ics => 36KA . The MCCB shall be of certified design MCCB 100A TP 36KA T/M based release with O/L & S/C Protection--01 no confirming to IEC 60947-1,2&3 . The Detuned Reactor (Al wound) should be equipped with Thermal switch inside the winding which should cut off the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. Make : ABB/ Schneider/ Siemens/ L&T (iii) Stage Contactor : The capacitor duty contactors shall be 95A -01 No rated for 230 volts AC and shall be 3 pole type and shall be employed for switching on and switching off operations in capacitor banks. The contactor shall be AC-3 duty type .The contactor shall be of certified design conforming to IEC 60947-1&4-1. Make : ABB/ Schneider/ Siemens/ L&T
(iv) Reactor: Harmonics blocks detuned reactors -01 no Al wound with 7% filtering factor shall be connected in series with each capacitor stage (for 50 KVAR AT 440 VOLTS) and shall be of iron cored type. The Reactor should be equipped with thermal switch inside the winding which should cutoff the respective contactor in case of over temperature. Tolerance of reactors shall not exceed +/-3% of rated value. The reactors shall be of certified design confirming to IEC 60076-6. Make : ABB/ Schneider/ Siemens/ L&T (G). Ventilating fans of required size shall be provided to dissipate the heat produced by the capacitor bank components like the capacitor units, reactors, contactors, breakers etc. The capacitors banks should be of type tested design and temperature rise test report of the capacitor bank performed at an independent laboratory should be submitted alongwith the offer.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL), connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore 'light grade' galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt etc including connected to test point and testing on completion, complete all as shown in electrical plate No 3 of SSR Part-I 2009 & as directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed.
Supplying, installing, designing, testing and commissioning of outdoor type, Cubical Kiosk Feeder Pillar Box suitable for 3 phase 4 wire, 415 volts 50 Hz supply system factory made out of 3.15mm thick CRCA sheet for with front and rear openable provided with suitable gasket to make dust/vermin proof for IP-54 as per IS:13947 degree of protection, fault rating 50 KA/1 Sec including angle iron base frame of size 50x50x6mm thick for mounting the panel board at a height of 600mm from FFL and 300mm grouted in PCC foundation (PCC 1:3:6 type C1 using 20mm graded stone aggregate), size of PCC foundation should be not less than (0.30x0.30x0.45metre) for each leg, complete all as specified, directed and comprising of the followings :-
INCOMING : (i) Incomer MCCB 4 pole, current rating 200Amp, overload adjustable 0.63-0.8-1xIn, short circuit adjustable 6-8-10-13xIn (100-200A) breaking capacity 35KA at 415V, 50Hz - 01No (ii) Digital LED Voltmeter 3 ph, class 0.5. 1 No. Make L&T - 01 No (iii) Digital LED Ammmeter 3 ph, class 0.5. 1 No. Make L&T - 01 No (iv) 3 Nos. resin cast CTs of 200 / 5 A class 1.0 accuracy and 15 VA burden. (v) 3 Nos - Phase indication LED lamps. OUTGOING (i) MCCB 4 pole, current rating 100Amp, overload adjustable 0.63-0.8-1xIn, short circuit adjustable 6-8-10-13xIn (100-200A) breaking capacity 35KA at 415V, 50Hz - 01No. (ii) MCCB 4 pole, current rating 63Amp, overload adjustable 0.63-0.8-1xIn, short circuit adjustable 6-8-10-13xIn (100-200A) breaking capacity 35KA at 415V, 50Hz - 03Nos
BUSBAR: (i)TPN Aluminium bus bar (having 50% Neutral) of minimum of 320 Amps capacity with heat shrinkable coloured sleeves and including DMC / SMC bus bar supports at required intervals for complete cross section etc. for withstanding fault level of 50KA for 1 Sec. - 1 Set
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Stay assembly with accessories as shown in electric plate No 1 of SSR Part-I 2009 such as 14mm dia 400mm long galvanised stay bow, galvanized steel stay rod 16mm dia 1000 long, mild steel galvanised steel plate 300x300x6mm, galvanized thimble, stay strand wire of size 7/4.00 mm etc, complete all as specified and directed. Note: Excavation, PCC and loop type insulator shall be measured and paid for separately under respective items.
Loop type insulator, porcelain, vitreous white/ brown or green, large size with overall dimensions 65x90mm clearance of hole 16mm, complete all as specified & directed.
PCC 1:3:6 type C2 using 40mm graded crushed stone aggregate as in foundation, filling, mass concrete, stay and similar items including necessary form work, complete all as specified & directed.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 3 meter (BGL), connected to galvanized iron earth strip 32x6mm size by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 50mm bore 'light grade' galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt etc including connected to test point and testing on completion, complete all as shown in electrical plate No 3 of SSR Part-I 2009 & as directed.
Supply, installation & commissioning in complete form as a single unit inverter Split type air conditioner (Outdoor / Indoor units & their installation) complete with cooling system to maintain the temperature for huming comfort including necessary plumbing, ducting and staging platform or stand for housing main unit with LCD wireless remote controller, electric driven, single phase of capacity 1.5 tonne (100% copper), 4 Star BEE rating, complete with all accessories and fittings, complete all as specified & directed. Make : Blue Star Cat Part No. IH418SAFU or equivalent in LG/ Samsung/ Godrej.
Supply, installation, commissioning and testing of voltage stabiliser fully automatic operation, single phase naturally air cooled, indoor type & designed for input variation between 140 volts to 280 volts with output voltage stabilised at 220 volts ( ± 9.0 %), calibration accuracy ± 3% and speed of correction 8 volts per second of capacity 5 KVA with short circuit, over current earth fault and high voltage protection, complete all as specified & directed
Sub main wiring using uniform coding of wiring with two runs of 6.0 Sqmm single core FRLS PVC insulated unsheathed cable upto and including 1100 volts grade with multistranded copper conductor drawn into and including rigid non-metallic ISI marked PVC conduit medium grade of 25mm size as required, fixed on surfaces of wall/ceiling with all fittings and fixing accessories & one run of 4.00 Sqmm FRLS PVC insulated copper conductor for earth continuity wire in green colour, complete all as specified & directed. Note:- Two runs of copper conductor 6.0 sqmm and one run of 4.00 Sqmm copper earth wire including PVC conduit will be measured and paid as one unit only.
Sheet metal enclosures single pole and neutral enclouser with a two pin and earth plug with socket complete with one double pole MCB 20 Amps, 240 volts, complete all as specified & directed.
Air termination single pointed copper rod 12mm dia and 300mm long including necessary fixing arrangements using MS clamps, nuts, bolts etc, complete all as specified & directed.
Earthing complete with copper earth plate of 600x600mm 3.15mm thick electrode buried directly in ground (preferably in vertical position) earth pit not less than 2.25 metre below normal ground level with top edge of the earth plate not less 1.5 metre (BGL), connected to copper earthing strip 20mm x 3mm by means of connected with tinted copper bolt, nuts, check nuts and washers besides braising at all joints all as directed and connected to earth test point with and including necessary earth work in any type of soil, returning filling in, removal of surplus soil etc, filling adequate qty of charcoal dust, common salt, PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, 20mm bore 'medium grade' galvanized iron water tubing fixed with funnel and wire mesh and 40 mm bore “light grade” galvanized iron protection pipe for copper earthing strip 20mm x 3mm upto 5m length,
complete all as shown in electrical plate No 3 of SSR 2009 Part-I, connected to test point, complete all as specified and testing on completion. Notes : (i) The excess requirement (if more than 7.5 Mtr) of copper strip as for connecting upto the test point will be measured and paid separately. (ii) The excess requirement (if more than 7.5 Mtr) of GI protection pipe will be measured and paid separately. (iii).Testing of earthing is to be carried out by using earth tester & test result shall be submiited as directly duly signed by contractor.
Copper strip 20 x 3mm fixed on suitable size porcelain insulator and screws/ nuts/ washers for roof conductors and down conductors above ground, complete all as specified & directed.
Galvanized iron water tubing, medium grade, 40mm bore for installation of air termination rod, complete all as specified and directed.
PCC 1:2:4, nominal mix, type B-0, using 12.5mm graded crushed stone aggregate as in blocks and the like including weathering, slightly rounded or chamfered angles and throating including necessary form work, complete all as specified & directed.
Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 3 nos. 8mm dia 25mm long hex head screw, complete all as specified & directed.
XLPE insulated, armoured heavy duty electric cable (heavy duty) with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm 3.5 core connected with suitable cable gland and aluminium lugs, laid in trenches or passing through pipes including testing after completion, complete all as specified and directed. (Earth work, brick protection and sand cushioning shall be measured and paid for separately)
Factory made epoxy powder coated distribution board vertical type, TPN, 4 ways with metal door (IP-43 protection) confirming to IS : 8623, fabricated from minimum 1.6mm thick CRCA sheet and fixed flush to wall, suitable for universal mounting including 200 Amp copper bus bar, neutral bar, standard DIN rail, earth bar, cable ties for cable management, top and bottom removable gland plates with knockouts and suitable for one MCCB 125 Amp 4P as incomer and MCBs SP/TP as outgoing, complete all as specified & directed.
MCCB of capacity 125 Amps, 4 pole, 415volt, 50Hz, rupturing capacity 35 KA (minimum) or higher, complete all as specified & directed.
MCB, single pole & neutral, 40 to 63 Amp, 50 Hz AC supply, 10 KA repturing capacity, 240 Volt, 'C' series, complete all as specified & directed.
MCB, single pole, 6 to 32 Amp, 50 Hz AC supply, 10 KA repturing capacity, 240 Volt, 'C' series, complete all as specified & directed.
On load change over switch in sheet metal enclosure, 160 Amps, 415 volts, 4 pole, modular type, positive isolation, door interlock & padlock facility, conforming to IS:13947 (Part-3); IEC:60947-3 including all connecting/ jointing materials, complete all specified & directed. Make. C&S Electric Cat Part No.E-CSCS200NM4CO or equivalent model of make specified in List of Makes/ Manufacturers/ Producers here-in-after.
M/S S K Electricals Regd
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .