Loading…
India Infra Updates on WhatsApp
Join the Tenderkart WhatsApp channel for India Tender Updates
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance BLOCK A PROPERTY NO 104 BRAN APARTMENT GANGA NAGAR BULANDSHAHR | BULANDSHAHR | BULANDSHAHR | UTTAR PRADESH | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
Tender Value
₹34.8 L
EMD Value
₹35,000
Closing Date
2 Nov 2023, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Superintending Engineer, EDC, Hapur
Superintending Engineer, EDC, Hapur
Sudharadikaran of line in area of EDD-I Hapur and Garh
2023_PVVNL_845796_2
77(W)/EDCH/2023-24
Open Tender
Electrical Works
Lump-sum
Hapur
enclosed
3 documents required · 3 mandatory
₹3,540
SE, EDC, Hapur
₹35,000
2 Nov 2023
26 Oct 2023
2 Nov 2023
26 Oct 2023
2 Nov 2023
26 Oct 2023
Amount
FOR SUDRADHIKARAN OF ELECTRICITY LINE AND SUB-STATIONS (14 NOS. WORKS) AND OTHER ASSOCIATED WORKS, IN ADDITIONAL BUSINESS PLAN, IN THE AREA OF EDD-I HAPUR AND GARHMUKTESHWER, UNDER EDC., HAPUR. (All work will be completed as per sanctioned estimate).
Carriage of line material (Like: 11KV Insulator, Disc, conductor, XLPE cable etc.) from Electricity Store Center, Hapur to site of work with loading and unloading at both ends on Kachha Packka road.
Carriage of ST Pole 11 mtrs. Long from Electricity store center, Hapur/J.E. Store to site of work with loading and unloading at both ends on Kachha Packka road.
Erection & Fixing of ST Pole 11 mtr. long in 11 KV line after digging of suitable pits including fixing of requisite accessories as per RESPO Drawing/Norms by providing F-Bracket made of M.S. Flat of size 50x6 mm, Cross Arm holding Clamps made of M.S. Flat of size 50x6 mm with proper size nuts and bolts.
Grouting & fixing of stay rods (20x1800)mm including all work of excavation, cement concrete in size (0.60x0.60x0.30)m in ratio 1:4:8 cement, sand, 40mm brick ballast as per drg. Including back filling, proper ramming etc and fixing tightening & nozzling of stay wire with stay rod with the poles of required tension as per drawing as per RESPO Drawing/Norms by providing all grouting material and stay clamp made of M.S. Flat of size 50x6mm with proper size bolts & nuts & loops. (including cost of stay set complete.)
Earthing of supports with MS earth Rod of (20x2500)mm long including excavation of pit and driving M.S. Rod 3.0 M apart from support and 0.5m below the ground level and connection below the earth electrodes with the help of G.I. wire & earthing lugs as per RESPO Drawing/Norms by providing proper size nuts & bolts.(including cost of earth Rod complete.)
Grouting of ST/PCC supports in CC 1:4:8 (Cement, sand & 40mm brick ballast) Grouting will be done in the block of size (450x450)mm x1/6th of full length of the support, up to ground level, 300mm plinth above the ground level with CC 1:3:6 (Cement, core sand and Stone grit) with mufting as per drawing, work includes back filling & proper ramming by providing all required grouting materials.
Providing and installation of Battery Set (24 V, 150AH) and completion work properly as per RESPO Drawing/Norms.
Providing and installation of Battery Charger (24 Volt) and completion work properly as per RESPO Drawing/Norms.
Providing and Fixing of Line Isolator 33KV and completion work properly as per RESPO Drawing/Norms.
Providing and Fixing of Bus Isolator 33KV and completion work properly as per RESPO Drawing/Norms.
Providing and Fixing of Lightening Arrestor 33KV and completion work properly as per RESPO Drawing/Norms.
Providing and Fixing of PG Clamp completion work properly as per RESPO Drawing/Norms.
Erection & Fixing of DO 03Phase Fuse set on ST/PCC Pole by providing all required materials, including cost of Fuse set.
Earthing of neutral & body of Transformers/ VCBs By Boring and lowering of G.I. Pipe size 32 mm dia… into the ground up to water level 120 fit. With the lower end of solid copper cone approx. 225mm long and 750 gm. in weight shall be provided and screwed in pipe as well as bringing out a continuous copper wire 6 SWG from the cone up to the ground surface where it will be bolted to the M.S. earth strip for T/F neutral connection, the earth strip will be welded to the G.I. pipe and neutral earthing support.
Providing & Fixing Chemical earthing of Transformers Equipment the ground surface where it will be bolted to the M.S. earth strip for connection the earth strip will be welded to the earthing and neutral support, as per RESPO/Norms.
Providing of stay wire 7/10 SWG for completion of proper work as per RESPO Norms.
Providing of G.I. wire 4 MM/ 6/8 SWG for completion of proper work as per RESPO Norms.
Erection & Fixing of 33KV Pin insulator on existing 33KV pole/DP etc, bry providing all required materials, as per RESPO/Norms.
Erection & Fixing of 33KV Post insulator on existing 33KV pole/DP etc, bry providing all required materials, as per RESPO/Norms.
Erection & Fixing of 33KV Polymer Disc insulator on existing 33KV pole/DP etc, bry providing all required materials, as per RESPO/Norms.
Making and filling of 33KV Cable Jointing Kit 3x300Sqmm, Outdoor type duly plumbing and taping of suitable XLPE Cable, providing, fixing and crimping of proper size good quality lugs, including cost of jointing kit, lugs and tape etc., as per RESPO Norms.
Making and filling of 11KV Cable Jointing Kit 3x300Sqmm, after duly plumbing and taping of suitable XLPE Cable, providing, fixing and crimping of proper size good quality lugs, including cost of jointing kit, lugs and tape etc., as per RESPO Norms.
Making and filling of 11KV Cable Jointing Kit 3x185Sqmm, outdoor type, after duly plumbing and taping of suitable XLPE Cable, providing, fixing and crimping of proper size good quality lugs, including cost of jointing kit, lugs and tape etc., as per RESPO Norms.
Making and filling of 11KV Cable Jointing Kit 3x185Sqmm, Indoor type, after duly plumbing and taping of suitable XLPE Cable, providing, fixing and crimping of proper size good quality lugs, including cost of jointing kit, lugs and tape etc., as per RESPO Norms.
Laying of Trenchless 11 KV XLPE Cable 3x185Sqmm., undergound (155x2=310 Double Circuit) into HDPE Pipe, spare cable shall be left in the loop shape at both ends as per RESPO/Norms., including providing of required material and HDPE Pipe etc.
Laying of Trenchless 11 KV XLPE Cable 3x300Sqmm., undergound (80x2=160 Double Circuit) into HDPE Pipe, spare cable shall be left in the loop shape at both ends as per RESPO/Norms., including providing of required material and HDPE Pipe etc.
Laying of 11 KV XLPE Cable 3x185Sqmm, after digging of earth making trench, by providing brick at three sides of cable and filling of soil and sand in cable trench, including cost of all material and labour.
Laying of 11 KV XLPE Cable 3x300Sqmm, after digging of earth making trench, by providing brick at three sides of cable and filling of soil and sand in cable trench, including cost of all material and labour.
Road Restoration Charges for Footpath and completion work properly as per RESPO/Norms.
Fabrication, erection and fixing of V-Type 11KV X-Arm angle 65x65x6mm as per RESPO Drawing/Norms, including cost of the same and by providing required clamps, nuts and bolts.
Fabrication, erection and fixing of V-Type 33KV X-Arm angle 65x65x6mm as per RESPO Drawing/Norms, including cost of the same and by providing required clamps, nuts and bolts.
Providng & Fixing of MS Channel 100x50 mm as per RESPO/Norms.
Laying of ABC Cable (3x20+1x95+1x16) Sqmm., and completion of work properly as per RESPO/Norms, including providing of required material like clamps, nuts bolts etc.
Laying, Stringing and final sagging of ACSR Dog Conductor after binding from Insulator, as per RESPO/Drawing Norms.
Removal of old & damaged scrap HT Cable 80 KG and bundling of the same
Removal of old & damaged scrap ACSR Weasel Conductor 500 KG and bundling of the same
Removal of old & damaged scrap STP and opening of all accessories.
Carriage of old and damaged scrap STP Pole from Site of work to JE Store/ESC Hapur with loading and unloading at both ends.
Carriage of old and damaged scrap HT Cable-80Kg, Weasel-500 Kg., from Site of work to JE Store/ESC Hapur with loading and unloading at both ends.
Jumpering work properly as per RESPO/Norms.
Vivek Electricals
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .