Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹1.5 CrAccepted-AOC 58 CHANDRALOK BUILDING MAYO HOSPITAL ROAD NAGPUR 440 018 | NAGPUR | MAHARASHTRA | 440018 | ₹1.5 Cr | L1 | Accepted-AOC Being L1 |
| 2 | L2₹1.5 CrRejected-Finance SHOP NO 10 BMC SHOPPING CENTRE MITHA NAGAR GOREGAON W MUMBAI 400 104 | MUMBAI SUBURBAN | MAHARASHTRA | 400104 | ₹1.5 Cr | L2 | Rejected-Finance Not Being L1 |
| Sl No | Description | Qty | Unit | Paragon Electrotechnics L1 | Shree Ayyappa Engineering L2 |
|---|---|---|---|---|---|
| 1.00 | Material and labour for disconnecting of all electrical & gas connection of split type air conditioner and taking down inner and outer unit of Split type AC of any make, size or capacity from various locations including transporting to deposit in AGE E/M store yard with all fitting and fixture complete. | 49 | Each | 300 ₹14,700 | 1,000 ₹49,000 |
| 2.00 | Supply, install, commissioning and testing of split type wall mounted Air conditioner of capacity 1.5 TR (4500 K Cal/hr) single phase, (Non CFC/HCHC) suitable for 230 Volt +10%, 50 Hz, AC supply complete with cordless remote control unit, BEE 5 star rating, EER of 3.2 and above complete comprising of following :- | 35 | Each | 42,000 ₹14.7 L | 39,200 ₹13.7 L |
| 2.01(a) Indoor unit copper coil with three speed blower fan of appropriate capacity including PCB, thermostatic control, air filter and drain for condensing water. (b) Out door unit comprising Compressor with motor, air cooled copper condenser with fan and motor and unit shall be installed out side the building/ on roof. (c) Refrigerant copper pipe for suction and discharge line with foam insulation, condensing water drain pipe & protected by suitable size of flexible PVC conduit with control valves & safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable. (d) Making good the disturbed surface to match the existing surface after plugging the hole etc. (e) PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) as in plinth suitable for installation of outdoor unit or powder coated MS bracket fixed on wall as per manufacturer's instruction with necessary grouting MS hold fastner, bolts, washers duly painted and making good to disturbed surfaces suitable for installing outdoor unit of 1.5 TR AC complete all as specified and directed. (f) Electrical cable required to connect out door unit and indoor unit to voltage stablizer inclusive in quoted rate. | |||||
| 3.00 | All as per item No. 2 here-in-before but for Split AC of capacity 2.0 TR (6000 K Cal/hr) single phase, (Non CFC/HCHC) suitable for 230 Volt +10%, 50 Hz, AC supply with cordless remote control unit, minimum BEE 5 star rating, EER of 3.2 and above | 14 | Each | 55,000 ₹7.7 L | 52,285 ₹7.3 L |
| 3.01Note for Item No. 2 & 3 : Rate quoted by contractor for the following items shall be deemed to be included in the unit rate against this item:- (a) Fixing the cooling unit with grouting nuts, cutting groove to wall for gas pipe & water drainage pipe. (b) S & F PVC pipe 15/20 mm dia transparent flexible heavy duty for water drainage pipe of required length at site. (c) Insulation of both the copper pipes with insulating material and covering the complete pipe with PVC casing & caping of size 75 x 75 mm/reqd size for mechanical protection of copper pipe complete. (d) Charging of correct qty of refrigerant gas R-22, after necessary brazing/fixing of both the outdoor/indoor unit and testing complete on load to obtain 18-24 degree celsius temperature at specified. | |||||
| 4.00 | Supply & installation refrigerator, electric driven single phase, 230 Volts, capacity 185 Ltrs or nearest capacity, single door having CFC Free refrigerant, frost free, electronic automatic temperature control, BEE certified 5 Star energy rating with inbuilt inverter technology complete all as specified and directed. | 3 | Each | 21,500 ₹64,500 | 19,260 ₹57,780 |
| 5.00 | All as per item No. 4 here-in-before but of capacity 322 Ltrs, double door, BEE 3 star rated. | 4 | Each | 44,500 ₹1.8 L | 33,170 ₹1.3 L |
| 6.00 | Supply, installation & commissioning of metal top deep freezer single phase 240 volt, 50 Hz of capacity 320 Ltrs having temperature range up to -20 degree celcious to -40 degree celcious (adjustable), temperature deviation of maximum +/- 30ºC with proper display complete all as specified and directed. | 1 | Each | 31,000 ₹31,000 | 24,342.5 ₹24,342.50 |
| 7.00 | Supply and installation of water cooler partially stainless steel, electric driven single phase having approx storage capacity of 80 Ltrs and nominal cooling capacity of 40 Ltrs/hr complete all as specified and directed. | 5 | Each | 37,500 ₹1.9 L | 32,421 ₹1.6 L |
| 8.00 | All as per item No. 7 here-in-before but of storage capacity of 120 Ltrs and nominal cooling capacity of 60 Ltrs/hr. | 3 | Each | 53,000 ₹1.6 L | 43,816.5 ₹1.3 L |
Updated dates
Tender Value
₹1.5 Cr
EMD Value
₹2.2 L
Closing Date
21 Jan 2026, 6:00 pmClosed
CWE AF NAGPUR
HQ CWE AF NAGPUR VAYUSENA NAGAR, NAGPUR 440007 MILITARY ENGINEER SERVICES
SPECIAL REPAIR TO BER MACHINERY EQUIPMENT AT AF STN AMLA
2025_MES_744377_1
80735/E8
Open Tender
Civil Works
GE AF AMLA
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
GE AF AMLA
₹2.2 L
Yes
19 Feb 2026
12 Dec 2025
24 Jan 2026
12 Dec 2025
21 Jan 2026
2 Jan 2026
Select, Excess (+), Less (-) Less (-)
Tender Inviting Authority: HQ CWE (AF) NAGPUR
Name of Work:SPECIAL REPAIR / REPLACEMENT OF BER MACHINERY / EQUIPMENT AT AFS AMLA
Contract No: CWE (AF) /AMLA / OF 2025-26
Name of the Bidder/ Bidding Firm / Company :
Sl. No. Item Code / Make Quantity Units Estimated Rate Addition / Deduction Addition / Deduction Values Currency Convertion against each Item Quoted Currency in INR / Other Currency RATE inclusive of all taxes in Figures To be entered by the Bidder Rs. P Excise Duty VAT Freight Charges ( Unloading & Stacking) Any Other Taxes/Duties/Levies Quoted Amount in Words Other Taxes 2 IIIrd Party i.e DGS&D / RITES etc Inspection Charges @0.34%+Service Tax Less for Cenvat Credit,if any respect of Supplies Under full Excise Duty Category TOTAL AMOUNT TOTAL AMOUNT TOTAL AMOUNT In Words
1 Material and labour for disconnecting of all electrical & gas connection of split type air conditioner and taking down inner and outer unit of Split type AC of any make, size or capacity from various locations including transporting to deposit in AGE E/M store yard with all fitting and fixture complete. 49 Each Excess(+) Full Conversion INR 3 Supplying, Conveying and fixing spls. Including ea item4 10 Nos
2 Supply, install, commissioning and testing of split type wall mounted Air conditioner of capacity 1.5 TR (4500 K Cal/hr) single phase, (Non CFC/HCHC) suitable for 230 Volt +10%, 50 Hz, AC supply complete with cordless remote control unit, BEE 5 star rating, EER of 3.2 and above complete comprising of following :- 35 Each Excess(+) Full Conversion INR 3 Supplying, Conveying and fixing spls. Including ea item4 10 Nos
2.01 (a) Indoor unit copper coil with three speed blower fan of appropriate capacity including PCB, thermostatic control, air filter and drain for condensing water. (b) Out door unit comprising Compressor with motor, air cooled copper condenser with fan and motor and unit shall be installed out side the building/ on roof. (c) Refrigerant copper pipe for suction and discharge line with foam insulation, condensing water drain pipe & protected by suitable size of flexible PVC conduit with control valves & safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable. (d) Making good the disturbed surface to match the existing surface after plugging the hole etc. (e) PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate) as in plinth suitable for installation of outdoor unit or powder coated MS bracket fixed on wall as per manufacturer's instruction with necessary grouting MS hold fastner, bolts, washers duly painted and making good to disturbed surfaces suitable for installing outdoor unit of 1.5 TR AC complete all as specified and directed. (f) Electrical cable required to connect out door unit and indoor unit to voltage stablizer inclusive in quoted rate.
3 All as per item No. 2 here-in-before but for Split AC of capacity 2.0 TR (6000 K Cal/hr) single phase, (Non CFC/HCHC) suitable for 230 Volt +10%, 50 Hz, AC supply with cordless remote control unit, minimum BEE 5 star rating, EER of 3.2 and above 14 Each Excess(+) Full Conversion INR
3.01 Note for Item No. 2 & 3 : Rate quoted by contractor for the following items shall be deemed to be included in the unit rate against this item:- (a) Fixing the cooling unit with grouting nuts, cutting groove to wall for gas pipe & water drainage pipe. (b) S & F PVC pipe 15/20 mm dia transparent flexible heavy duty for water drainage pipe of required length at site. (c) Insulation of both the copper pipes with insulating material and covering the complete pipe with PVC casing & caping of size 75 x 75 mm/reqd size for mechanical protection of copper pipe complete. (d) Charging of correct qty of refrigerant gas R-22, after necessary brazing/fixing of both the outdoor/indoor unit and testing complete on load to obtain 18-24 degree celsius temperature at specified.
4 Supply & installation refrigerator, electric driven single phase, 230 Volts, capacity 185 Ltrs or nearest capacity, single door having CFC Free refrigerant, frost free, electronic automatic temperature control, BEE certified 5 Star energy rating with inbuilt inverter technology complete all as specified and directed. 3 Each Excess(+) Full Conversion INR
5 All as per item No. 4 here-in-before but of capacity 322 Ltrs, double door, BEE 3 star rated. 4 Each Excess(+) Full Conversion INR
6 Supply, installation & commissioning of metal top deep freezer single phase 240 volt, 50 Hz of capacity 320 Ltrs having temperature range up to -20 degree celcious to -40 degree celcious (adjustable), temperature deviation of maximum +/- 30ºC with proper display complete all as specified and directed. 1 Each Excess(+) Full Conversion INR
7 Supply and installation of water cooler partially stainless steel, electric driven single phase having approx storage capacity of 80 Ltrs and nominal cooling capacity of 40 Ltrs/hr complete all as specified and directed. 5 Each Excess(+) Full Conversion INR
8 All as per item No. 7 here-in-before but of storage capacity of 120 Ltrs and nominal cooling capacity of 60 Ltrs/hr. 3 Each Excess(+) Full Conversion INR
9 All as per item No. 7 here-in-before but of storage capacity of 150 Ltrs and nominal cooling capacity of 150 Ltrs/hr. 2 Each Excess(+) Full Conversion INR
10 Supply and fixing voltage stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 170 V to 250 V with output voltage stabilized at 230 V with accuracy of ± 2.5% and of capacity 4 KVA complete all as specified. 10 Each Excess(+) Full Conversion INR
11 All as per item No. 10 here-in-before but of capacity of 5 KVA complete. 10 Each Excess(+) Full Conversion INR
12 Supply and fix in replacement polycarbonate modular AC box, 4 module with modular 20 Amps single pole MCB, modular socket 16 Amp, metal enclosure and heavy duty ISI marked plug top (white) 16 Amp complete all as specified and directed. 25 Each Excess(+) Full Conversion INR
13 Material and labour for concealed sub main wiring comprising of two single core, 4 Sq mm nominal cross sectional area multistranded copper conductor cable, PVC insulated FRLS grade unsheathed 1100 Volts grade drawing in and including PVC conduits and conduit fittings complete (concealed type) and one single core 4 Sq mm nominal cross sectional area in green colour copper conductor cable, PVC insulated unsheathed 1100 Volts grade as earth wire complete all as specified and directed. Note: Cutting chases and making good of disturbed surfaces shall be deemed to be including in the unit rate quoted by tenderer. 260 RM Excess(+) Full Conversion INR
14 Taking down/dismantling of old BER centrifugal pump sets of capacity 60 HP complete including motor starter of capacity 60 HP from foundation by disconnecting all electrical and water connections of pump set and depositing the same to MES store yard including transportation from pump house to AGE E/M store yard complete all as specified and directed. 2 Each Excess(+) Full Conversion INR
15 Supply, install, connecting and testing centrifugal pump set, horizontal split casing of discharge not less than 28 LPS at 90 mtrs head suitable for nominal speed 1480 RPM for lifting clear water having SS impeller, shaft & shaft sleeve made of SS-410 with pump efficiency not less than 70% directly coupled with 60 HP, 415 Volts, 50 Hz AC nominal speed 1480 RPM electric driven motor. Make of Pump: Kirloskar Model : DSM 100/36 or equivalent model in Mather & Platt / KSB/ Jyoti Ltd Specifications for motor- 60 HP, TEFC, squirell cage, 50 Hz + 5%, 415 V + 10%, Class F insulation, Ambient Temp, 3 phase, IE-3, IP-55, IS-325 with up to date amendments. Both pump and motor, mounted on and including a common steel base frame, shall be assembled by the manufacturer of the pump. Make of Motor: ABB/CGL/ KIRLOSKAR 2 Each Excess(+) Full Conversion INR
15.01 Note: (a) Pump Set shall be placed on PCC foundation (1:2:4) using 20 mm graded stone aggregate including form work etc complete all as per manufacturer's instructions and PCC shall be measured & paid separately under relevant item here-in- after. (b) Addition/ alteration of suction and delivery side of existing pipes and water connections etc shall be measured & paid separately under relevant item here-in-after (c) Rate for vibration pads, pressure gauge, air release valve & balancing valves (pointed towards earth), steel frame for pump and motor shall deemed to be included in the rate quoted.
16 Supply and laying through trench/pipe or fixed on wall using GI clamps, flat three core multistranded PVC insulated & PVC sheathed copper conductor industrial cable, 1100 Volts confirming to IS 694:1990 with ISI marking of size 25 Sqmm including connection with motor, starter with appropriate size copper thimbles complete all as specified and directed. 60 RM Excess(+) Full Conversion INR
17 Supply & fixing cast iron non return sluice valve 150 mm dia, PN -1.6 ISI marked as per IS: 5312 Part-I with gun metal seat, both ends flanged heavy duty including packing materials, nuts bolts & washers etc and testing complete all as specified and directed. 4 Each Excess(+) Full Conversion INR
18 Supply & fixing cast iron rising sluice valve, SS spindle 150 mm bore, flanged ends PN-1.6 ISI marked as per IS:14846/2000 and CI operating wheel including gasket, nuts, bolts and washers complete all as specified and directed. 2 Each Excess(+) Full Conversion INR
19 Supply and fixing cast iron foot valve 150 mm dia flanged ends swing type operation with rubber seat as per IS:4038 PN 0.2 complete all as specified and directed. 2 Each Excess(+) Full Conversion INR
20 Taking down existing panel and supply, installation, testing and commissioning of soft starter panel indoor type for, factory made box/ panel dust and vermin proof, fabricated out of 2.0 mm thick CRCA sheet, duly painted with epoxy powder coating with 10 tank process complete (CPRI tested and approved manufacturer) & grouting in PCC (1:2:4) type B-1 (using 20mm graded crushed stone aggregate), all the components of soft starter shall be placed in cabin/ compartments, the cabin/compartment shall also with opening and locking arrangement from front side, with independant earthing studs of size not less that 2.25 x 1.5 x 0.45 (H x L x W) all as specified and directed including provision of following accessories:- 1 Each Excess(+) Full Conversion INR
20.01 Incomming: MCCB 4 Pole, 415 V, adjustable type, 320 Amp with breaking capacity 36 KA-01 No. Bus Bar : Copper Bus bar 40 x 5 mm (520 Amp) rating suitable length Outgoing: (i) MCCB 3 Pole, 415 V, adjustable type, 125 Amps with breaking capacity 16 KA - 03 Nos. (one spare) front handle opearted. (ii) Line Contactor 110 Amp, 55 KW AC3. Make: Siemens 3RT2047-1A08K - 03 Nos. (iii) Digital soft starter 3 phase, 415 Volts, 50 Hz including one spare power control board of digital starter 55 KW - 03 Nos. Make: Siemens 3RW4047-1BB04 (iv) Independant control supply transformer and fast acting semiconductor fuse of suitable rating for starter protection - 03 Nos. (v) Resin cast CT 600/5A cast resin base- 01 set of 03. (vi) Push button ON/OFF, AC 415 Volts 50 Hz - 06 Nos. (vii) LED indication lamp, AC 415 Volts , 50 Hz for RYB, ON/OFF, trip - 18 Nos. (viii) Emergency push button OFF - 03 Nos. (ix) Terminal block suitable for 150 A rating with brass contacts for INPUT/OUTPUT termination with 9 ways - 03 Sets. (x) 3 Phase 3 wire copper bus bars of suitable length & section not less than 20 x 5 mm covered with coloured heat shrinkable anti track insulation tape of make Denson/ M-seal or equivalent of finished thickness not more than 1mm and fixed on epoxy base post insulator of both dia and height not less than 40mm- 01 set. (xi) Control wiring of push buttons, indicators/ protection circuits contactors, soft starter with 1.5 Sqmm multi strand copper cable, lugs and ferrules- 01 Job as per circuit design complete all as specified and directed. Note: (i) All existing and new connections of incoming/outgoing cables shall be done through appropriate size of copper thimbles. (ii) Drawing, circuit diagram and all materials / instruments etc for starter panel shall be got approved by GE before fabrication.
21 Taking down GI pipe 80 mm bore from trench. Supply, laying, jointing and testing of ductile iron pressure pipe with socket & spigot ends having ISI stamping marking confirming to IS:8329/2000 in standard length of 5.50 - 6.00 meter of class K-7 suitable for push on rubber tyton (gasket D-jointing) with cement mortar lining in the pipes having 80 mm bore, including aligning the pipes inside trench as per IS:12288/1987 and testing the joints with required water pressure complete all as specified & directed. Note: (i) Cutting of pipe shall be measured and paid for separately (ii) Excavation earth works shall be measured and paid for separately. (iii) Joints CI/DI specials shall be measured and paid for separately. 444 RM Excess(+) Full Conversion INR
22 Supply and fixing ductile iron pipe fittings such as bends, tapers, tee pieces single branch, "Y" junction, collars, caps and plugs etc spigot socketed or flanged ends type of size upto 150 mm nominal bore conforming to IS-9520/2000 with pressure rating PN-1 (all the fittings shall be coated for rust prevention i.e. external coating zinc rich paint with finishing layer of bituminous as per Annexure 'A' of IS:9523/2000 and internal lining shall be of cement mortar with seal coat as per Annexure 'B' of IS-9523/2000) complete all as specified and directed. 150 Kg Excess(+) Full Conversion INR
23 Cutting to existing CI/DI pipe line of size 150 mm dia required for repair/replacement of pipe line and insertion of collars/tail pieces, tee etc including dewatering of pit, complete all as specified and directed. Note : Excavation and earth work if any shall be measured and paid for separately. 2 Each cut Excess(+) Full Conversion INR
24 Supplying, laying, jointing and testing hot finished mild steel black pipe standard type YST-210 as per IS-1978 of 1982 (Revised upto date) nominal bore 150mm with wall thickness 5.60 mm including short pieces with flanged ends duly fabricated as required at site, laid in trenches/inside valve pits complete all as specified and directed. Note:- Excavation, earth work MS flanges & fittings, joints shall be measured and paid for separately under relevant items. 45 RM Excess(+) Full Conversion INR
25 Supplying and fixing heavy duty pipe fittings such as MS bends of any angle and length, reducers, flanges as per IS-1978 of 1982 (Revised upto date) of any radius hot finished nominal bore upto 150 mm and wall thickness 5.60 mm complete all as specified and directed. 150 Kg Excess(+) Full Conversion INR
26 Dismantling and taking out old u/s leaking GI/MS pipe line any type of size 150mm bore including fittings complete with nuts, bolts, washers and gaskets etc and removing from the site to MES store yard compete all as specified and directed. RM Excess(+) Full Conversion INR
27 Excavation in trenches not exc. 1.5 mtrs wide and not exc. 1.5 mtr deep and getting out in hard/dense soil all as directed and specified. 90 Cum Excess(+) Full Conversion INR
28 Returning filling in including spreading levelling watering and well ramming in layers not exc 25 cm thick all as specified and directed. Cum Excess(+) Full Conversion INR
29 Removing of surplus excavated materials to a distance not exc. 50 mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point all as specified and directed. 5 Cum Excess(+) Full Conversion INR
30 Demolition of cement concrete in ground floors and pavings n.exc 15cm thickness (below or above ground level) unreinforced 3 Cum Excess(+) Full Conversion INR
31 Material and labour for cement concrete type D-2 (1:4:8) thick using 40 mm graded stone aggregate as in foundations /Mass concrete etc 2 Cum Excess(+) Full Conversion INR
32 Cement concrete type B-1 (1:2:4) using 20 mm graded stone aggregate as in bed blocks, copings and the like including weathering, slightly rounded or chamfered angles & throating including provision of necessary formwork, complete all as specified. 3 Cum Excess(+) Full Conversion INR
33 Supply and fix in replacement MS framed work such as grills, grating etc with ends of bars shoulderd/ welded/ riveted or forged in to spikes, framed guard bars, barred iron doors, ladders, framed balusters, walk ways, railings, framework of water tanks and similar work confirming to Fe-290 Gde-E-165, complete all as specified and directed. 200 Kgs Excess(+) Full Conversion INR
34 Supply and fix Mild steel bolts, purpose made, with hexagonal or square head one end and screwed the other, or screw both ends, each screwed end to be fitted with washers and one hexagonal or squa 75 Kgs Excess(+) Full Conversion INR
35 re nut, not exceeding 30cm long 2 Each Excess(+) Full Conversion INR
36 Supply, installation, testing and commissioning step down transformer, outdoor type, plinth mounted HT 11 KV, 3 phase 433 volts, 4 wire, 50 Hz, delta/star connected, vector group DYN-11 double copper wound, ONAN cooled, manual type off load tap changing facility on HT side to vary secondary voltage from minus 7.5% to plus 7.5% in steps of 2.5% continuous rating of capacity 200 KVA including bushing on HT end cable box on LT side complete with all standard fittings and accessories, gauges, first fill of transformer oil as per IS:335, ISI marked filtered & dehydrated transformer oil etc, and conforming EEL-1 of IS:1180-2014 with amendment no. 1, 2, 3 & 4. 1 Each Excess(+) Full Conversion INR
37 All as per item No. 35, but copper wound transformer step down, outdoor type, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, capacity 400 KVA 1 Each Excess(+) Full Conversion INR
37.01 All as per item No. 35, but copper wound transformer step down, outdoor type, HT 11 KV 3 Phase, LT 433 volts, 3 Phase 4 wire with off load tappings on HT side to vary secondary voltage within limit, capacity 500 KVA
38 Item No.35, 36 & 37 : Transformer shall be comprising of following accessories complete :- (a) HV side bare bushing suitable for OH conductor (consisting of 3 Nos porcelain HT bushings with brass/gun metal bushing rods complete with nuts and washers) (b) One cable box on secondary (LV) side consisting of 4 Nos porcelain bushing with GM bushing rods complete with GM nuts and washers with one No cable gland suitable for reception of outgoing LT armoured cables of suitable size. (c) Oil conservator tank with filter type, drain valve and oil level gauge. (d) Dehydrating breather (Silica Gel Breather) with first fill of dehydrating agent. (e) Thermometer pocket on tank cover. (f) Buchholz Relay (having Contacts for Alarm & Trip) (g) Marshalling Box (having TTB Only) (j) Magnetic Oil Level gauge. (k) Bottom Oil filter cum drain valves. (l) Top Oil filter valve, Inspection Cover with cap/plug with connections complete. (m) Lifting lugs. (n) Air relief valve plug (Air release Plug), Explosive vent. (o) Four Nos plan solid cast steel detachable rollers (Bi directional Wheels). (p) First fill of fresh oil conforming to relevant IS and tested upto 50 KV dielectric strength upto top of core. Routine testing as per IS 1190/IS-2026. (r) Rating plate with terminal markings. (s) Two earthing terminals on tank/tank cover to facilitate fixing of 32 x 6mm GI earth strip. (t) Provision of 2 Nos danger boards 250 x 200 mm size made out of 1.6 mm thick MS Plate, vitreous enameled white, with letters, figures of voltage and conventional skull and bones in signal red colour, one at HT side and other on LT side. (u) Any other fittings/accessories so as to confirm the whole transformer to IS-1180 Note:- Foundation for outdoor transformer and cattle fencing around transformer is included in the above rates. 575 RM Excess(+) Full Conversion INR
39 Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11 KV grade (earthed) of size 120 Sqmm. 275 RM Excess(+) Full Conversion INR
40 Supply, laying & testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11 KV grade (earthed) of size 95 Sqmm.
40.01 Supply and fix in repair cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of following sizes :- 4 Each Excess(+) Full Conversion INR
40.02 (i) 120 Sqmm to 185 Sqmm 4 Each Excess(+) Full Conversion INR
41 (ii) 50 Sqmm to 95 Sqmm 50 RM Excess(+) Full Conversion INR
42 Supply and laying cable XLPE insulated screened, PVC bedded, galvanised, steel strip or wire armoured, electric power cable, (heavy duty) 1100 volts grade, with stranded aluminium conductor of size 3.5 core x 120 Sqmm 50 RM Excess(+) Full Conversion INR
43 Supply and laying cable XLPE insulated screened, PVC bedded, galvanised, steel strip or wire armoured, electric power cable, (heavy duty) 1100 volts grade, with stranded aluminium conductor of size 3.5 core x 150 Sqmm 40 RM Excess(+) Full Conversion INR
44 Supply and laying cable XLPE insulated screened, PVC bedded, galvanised, steel strip or wire armoured, electric power cable, (heavy duty) 1100 volts grade, with stranded aluminium conductor of size 3.5 core x 185 Sqmm 26 RM Excess(+) Full Conversion INR
45 Supply and laying cable XLPE insulated screened, PVC bedded, galvanised, steel strip or wire armoured, electric power cable, (heavy duty) 1100 volts grade, with stranded aluminium conductor of size 3.5 core x 300 Sqmm 1 Each Excess(+) Full Conversion INR
46 Supply, install, testing and commissioning APFC panel outdoor type of capacity 180 KVAR, factory made of suitable size, dust & vermin proof, double door, fabricated out of powder coated MS CRCA sheet 3.15 mm thick and mounted on 70 cm long legs of angle iron of size 50 mm x 50 mm x 6 mm out of which 30 cm shall be embedded in foundation of PCC 1:2:4 type B-1, using 20 mm graded stone aggregate and provided with lugs of suitable size and cable glands for incoming/out going connections complete all as specified. The panel shall be suitable for and including housing the following main parts in addition to any other part recommended by the panel manufacturer. Note: Drawing for APFC Panel shall be got approved by GE before fabrication. (i) MCCB 3 pole, 400 Amps, 36 KA, fixed type - 01 No. (for incoming) (ii) Power factor corrector relay upto 8 stage - 01 No. (iii) MD-XL Capacitor 180 KVAR (2 x 25 KVAR + 2 x 15 KVAR + 2 x 50 KVAR) conforming to IS:13340 along with suitable size/capacity duty contactor (iv) MCCB 4 pole, 100 Amp, 16 KA - 02 Nos. (v) MCB TP 20-63 Amps -04 Nos. (vi) Auto/Mannual Selector switch- 06 Nos. (vii) ON/OFF indicating light - 06 Nos. (viii) Phase indicating lamps LED type RYB. (ix) Panel mounted multi function energy meter including resin dia cast CT of ratio 400/5 - 01 No. (x) Bus bar chamber with 4 Nos aluminium strip of 600 amps rating and fixed on epoxy insulation complete with colour coding. 1 Each Excess(+) Full Conversion INR
47 Supply, install, testing and commissioning APFC panel outdoor type of capacity 150 KVAR, factory made of suitable size, dust & vermin proof, double door, fabricated out of powder coated MS CRCA sheet 3.15 mm thick and mounted on 70 cm long legs of angle iron of size 50 mm x 50 mm x 6 mm out of which 30 cm shall be embedded in foundation of PCC 1:2:4 type B-1, using 20 mm graded stone aggregate and provided with lugs of suitable size and cable glands for incoming/out going connections complete all as specified. The panel shall be suitable for and including housing the following main parts in addition to any other part recommended by the panel manufacturer. Note: Drawing for APFC Panel shall be got approved by GE before fabrication. (i) MCCB 3 pole, 350 Amps, 36 KA, fixed type - 01 No. (for incoming) (ii) Power factor corrector relay upto 8 stage - 01 No. (iii) MD-XL Capacitor 150 KVAR (1 x 50 KVAR + 2 x 25 KVAR + 5 x 10 KVAR) conforming to IS:13340 along with suitable size/capacity duty contactor (iv) MCCB 4 pole, 100 Amp, 16 KA - 01 No. (v) MCB TP 20-63 Amps -07 Nos. (vi) Auto/Mannual Selector switch- 08 Nos. (vii) ON/OFF indicating light - 08 Nos. (viii) Phase indicating lamps LED type RYB. (ix) Panel mounted multi function energy meter including resin dia cast CT of ratio 400/5 - 01 No. (x) Bus bar chamber with 4 Nos aluminium strip of 500 amps rating and fixed on epoxy insulation complete with colour coding. 2 Each Excess(+) Full Conversion INR
48 Supply, install, testing and commissioning APFC panel outdoor type of capacity 60 KVAR, factory made of suitable size, dust & vermin proof, double door, fabricated out of powder coated MS CRCA sheet 3.15 mm thick and mounted on 70 cm long legs of angle iron of size 50 mm x 50 mm x 6 mm out of which 30 cm shall be embedded in foundation of PCC 1:2:4 type B-1, using 20 mm graded stone aggregate and provided with lugs of suitable size and cable glands for incoming/out going connections complete all as specified. The panel shall be suitable for and including housing the following main parts in addition to any other part recommended by the panel manufacturer. Note: D 24 Each Excess(+) Full Conversion INR
49 rawing for APFC Panel shall be got approved by GE before fabrication. (i) MCCB 3 pole, 125 Amps, 36 KA, fixed type - 01 No. (for incoming) (ii) Power factor corrector relay upto 8 stage - 01 No. (iii) MD-XL Capacitor 60 KVAR (1 x 25 KVAR + 2 x 10 KVAR + 3 x 5 KVAR) conforming to IS:13340 along with suitable size/capacity duty contactor (iv) MCB TP 20-63 Amps -06 Nos. (v) Auto/Mannual Selector switch- 06 Nos. (vi) ON/OFF indicating light - 06 Nos. (vii) Phase indicating lamps LED type RYB. (viii) Panel mounted multi function energy meter including resin dia cast CT of ratio 400/5 - 01 No. (ix) Bus bar chamber with 4 Nos aluminium strip of 200 amps rating and fixed on epoxy insulation complete with colour coding. 309.83 Cum Excess(+) Full Conversion INR
50 Returning filling in including spreading levelling watering and well ramming in layers not exc 25 cm thick all as specified and directed. 238.68 Cum Excess(+) Full Conversion INR
51 Material & labour for earthing complete with galvanised steel earth plate electrode 600mm x 60mm x 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron earth strip 32mm x 6 mm by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No. 3 connected to earthing test point all as specified or indicated including testing on completion. 71.15 Cum Excess(+) Full Conversion INR
54 Excavation in trenches not exc. 1.5 Mtrs wide and not exc. 1.5 mtr deep and getting out in hard/dense soil all as directed and specified. 61.97 Cum Excess(+) Full Conversion INR
55 Removing of surplus excavated materials to a distance not exceeding mo mtr and deposting where directed at a level not exc. 1.5 mtr above the starting point all as specified and directed. 4250 Each Excess(+) Full Conversion INR
56 Material and labour for river sand, washed and screened dry for cushioning to under ground cable in trenches/ sub station cable ducts below and around under ground cable including spreading and levelling complete all as specified and directed. 30 RM Excess(+) Full Conversion INR
57 Supplying and laying un-reinforced precast concrete cable cover, class EVP, type 1 with peak size 300mmx180mmx40mm over sand cushioning for protection of cable complete all as specified and directed. 125 RM Excess(+) Full Conversion INR
58 Supply and fixing GI tubing size 100 mm dia light grade laid in trenches/fixed to poles, walls etc as protection of cable all as specified and directed.
Total in Figures 4 Construction of chamber for 100mm sluice plates item5 10 Nos
Quoted Rate in Figures Select
Quoted Rate in Words
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.50 MB
BOQ_833505.xls
BOQ • 0.37 MB
PS80735.pdf
Tender Documents • 0.94 MB
Download all tender documents and submit your bid