Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.7 LAccepted-AOC 23 2 PANCHANANTOLA ROAD KOLKATA 700041 | KOLKATA | HOWRAH | WEST BENGAL | 700041 | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹23.3 L+₹2.6 L (12.6%)Rejected-Finance 14 HARE STREET GROUND FLOOR KOLKATA 700001 | KOLKATA | KOLKATA | WEST BENGAL | 700001 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹23.4 L+₹2.7 L (13.0%)Rejected-Finance 46 SHYAMA PRASAD MUKHERJEE ROAD KOLKATA 700 026 | KOLKATA | KOLKATA | WEST BENGAL | 700026 | L3 | Rejected-Finance 3rd lowest bidder | |
| 4 | Rejected-Technical PLOT NO 6 JAYSHREE COMPLEX ALAMPUR N H 6 P O NEW KALORAH HOWRAH 711302 | HOWRAH | HOWRAH | WEST BENGAL | 711302 | - | Rejected-Technical Disqualified |
Tender Value
Refer Docs
EMD Value
₹50,000
Closing Date
13 Jan 2021, 12:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
EE_II, Kol. South Health El. Divn.,P.W.Dte.
75 D H Road Kidderpore Kol_23
EI work for providing uninterrupted power supply at Vidyasagar SGH_SITC of 250KVA DG Set.
2020_WBPWD_309089_1
WBPWD/KSHED/Q33/20-21(2nd Call)
Open Tender
GENERATOR ORG
Item Rate
30 days
Kolkata
Please refer Tender documents.
2 documents required · 2 mandatory
₹50,000
O/o Exe.Engr., Kol. South Health El. Divn., PWDte.
1 Sept 2021
15 Dec 2020
15 Jan 2021
15 Dec 2020
13 Jan 2021
24 Dec 2020
23 Dec 2020
120 days
Amount
Supply , delivery at site on foundation , commissioning of 250KVA, 415V, 50Hz, 3Ø silent new DG Set, comprising of Engine, alternator, separate AMF panel, Base frame, Fuel tank, Battery, CPCB-II approved Engine & Acoustic Enclosure having following specifications :-
Engine:-
Make : CUMMINS/Volvo
Engine Type : 4 Stroke Diesel Engine
Rated Output : 335 BHP or Higher
Duty : PRIME
Cooling : Water cooled with radiator
Cylinder : 6
Aspiration : Turbo Charged
Type of Governor : Electronic
Fuel Tank Capacity : Minimum capacity 360 Ltrs.
Fuel Consumption at 75% rated Load with Radiator or Fan : 42 Ltr./ Hr. or Less
Fuel Consumption at 100% rated Load with Radiator or Fan : 58 Ltr./ Hr. or Less
Overload Capacity : 10% overload for one hour for every 12 hours continuous running at full load or better
Engine instrument Panel : Consisting of starting switch with Key, Lube Oil Indicator, water temperature Indicator, RPM indicator and hour meter.
Safety Controls : Emergency Stop, Low Lube Oil Pressure warning/ Shutdown, High Engine Water Temp. warning/ Shutdown, Sensor failure Indicator, Engine over speed indicator, Battery charging and low battery indicator
Exhaust Silencer : Residential Type
Starting system : 12V./ 24 V. starting system complete with starter motor, charging alternator with rectifier and Cutout as per manufacturer standard.
Battery : Lead Acid, Low Maintenance or SMF and conforming to relevant IS Specification with Low/High Battery Voltage and Weak Battery warning
Alternator
Make : Stamford/ Leroy Some
Rating : 415 V., 3Ph. 50 Hz., 250 KVA, 1500 rpm
Type : Brushless, self excited and self regulated
Insulation : Class H
Protection : screen-protected drip proof with Min.IP-23 degree of protection
Voltage Regulation (max) : ±1%
Winding connection : Star with Neutral
Total Distortion factor : Less than 3%
Total Harmonic distortion in output waveform : < 5%
AMF Panel
Cubical type floor mounted AMF panel made from 14 SWG Sheet Steel, duly pretreated, powder coated painted and aesthetically finished, suitable for controlling of 250 KVA DG set having following specification/features.
i)2 No. 400 A AC1 duty, 4pole power contactor and U/V release etc. [make: ABB, Legrand, Schneider]
ii) 2 Nos. 400 A, 3pole, 50 KA MCCB with microprosser based LSIG protection. [make: ABB, Legrand, Schneider]
iii) In Built By-Pass switch for rated capacity
iv) On -delay timer for load change over
v) On-delay timer for engine shut off
vi) Engine On-Off switch (Push button type)
viii) Minimum five number indicating lamps to indicate 'mains ON', 'load on mains', Set running', 'load on set' and 'battery charger on'.
ix) Audio visual alarm for 'Low lubricating oil pressure', 'High water temperature, Start failure', and DG over load'.
x) Microprocessor based relay with composite meter for digital display of following.
Generator voltage/AC Mains voltage.
Generator Current in all phases
Frequency
Power Factor
Energy
Indication for alternator supply
Running time indications number of hours of operation and service intervals, service due indications
The AMF panel must be designed to ensure trouble free performance and ensure switching over Electrical Load to DG within 15 (fifteen) second from the instant of mains failure.
Acoustic Enclosure
The DG set should have integrated acoustic enclosure at the manufacturing state itself. High quality acoustic enclosure must be certified as per CPCB-II norms.
Base Frame
Common iron channel fabricated base frame containing the engine and alternator, mounted on AVM pads and having provision for lifting Hook.
Terms & Conditions
(i) Rate should be quoted inclusive of all applicable taxes and Duty etc.
(ii) All materials, equipments & accessories must conform to relevant IS specifications. The DG Set to be supplied must be from the authorized OEM of the respective Engine Manufacturer.
(iii) Necessary manufacturer's test certificate for Diesel Engine, Alternator etc. Will have to submit in triplicate copy during delivery of the equipment.
(iv) Copy of "Type Approval Certificate" and Certificate of "COP" must be produced at the time of delivery issued from competent Authority (As per CPCB-II).
(v) Circuit Diagram for AMF Panel must be submitted from the Manufacturer/OEM.
(vi) The entire set must be warranted at least 15 months from the date of Delivery/12 months/ 5000 Hrs from the date of Commissioning whichever is earlier. However Engine & Alternator should be warranted of 2 years/5000 Hrs, whichever is earlier.
The Agency must procure the materials from the Manufacturer/OEM or from their authorized sales channel so that the standard warranty/supprot of the Manufacturer/OEM becomes applicable to the products to be delivered and installed by them.
Documents that authenticates such procurement from the Manufacturer/OEM or from their authorized sales channel and standard warranty/support should be sent from the e-mail of the Manufacturer/OEM/authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution of work/submission of bill.
If any refurbished material is supplied and installed, penal action will be taken as per existing rules.
Sohum Industrial Sales Corporation
C. CHOWDHURY AND CO
stage.html
html • 0.05 MB
technical_580527.pdf
PDF • 0.09 MB
techsummary_580527.pdf
PDF • 0.09 MB
finance_580527.pdf
PDF • 0.09 MB
BOQ Comparative Chart
xlsx • 0.01 MB
finsummary_580527.pdf
PDF • 0.09 MB
AOC.pdf
PDF • 0.54 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .