Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹34.1 LAccepted-AOC | L1 | Accepted-AOC Awarded | |
| 2 | L2₹34.6 L+₹6,034.38 (0.17%)Rejected-AOC | L2 | Rejected-AOC Rejected | |
| 3 | L3₹35.5 L+₹90,883.38 (2.63%)Rejected-AOC | L3 | Rejected-AOC Rejected | |
| 4 | L4₹38.9 L+₹4.3 L (12.4%)Rejected-AOC 171 NARAYAN PETH PUNE PUNE MAHARASHTRA 411030 | PUNE | MAHARASHTRA | 411030 | L4 | Rejected-AOC Rejected | |
| 5 | L5₹39.9 L+₹5.3 L (15.4%)Rejected-AOC | L5 | Rejected-AOC Rejected |
Tender Value
₹49.4 L
EMD Value
₹98,874
Closing Date
23 Oct 2023, 6:00 pmClosed
Garrison Engineer North Ahmednagar
Military Engineer Services Garrison Engineers (North) Nagar Pathardi Road Ahmednagar Fort Ahmednagar 414 002
SPECIAL REPAIR / REPLACEMENT OF OVERHEAD LT LINE TO UNDERGROUND LINE, LT POLE, AIR CONDITIONING AND CONNECTED ACCESSORIES AT NEW KLP AC DEPOT, AC DEPOT AND HQ ACC and S UNDER GE (N) AHMEDNAGAR
2023_MES_620588_1
8790 / E8
Open Tender
Miscellaneous Works
Item Rate
180 days
Garrison Engineer North Ahmednagar
Class D Cat b(i)
8 documents required · 8 mandatory
₹500
Garrison Engineer(North) Ahmednagar
₹98,874
Yes
11 Nov 2023
26 Sept 2023
25 Oct 2023
26 Sept 2023
23 Oct 2023
9 Oct 2023
Amount
Supply & Fixing and testing of LT cable 1100 volts grade XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) with aluminium conductor suitable for earthed system of size 95 sq mm 3.5 core in trenches, on poles and in ducts complete all as specified and directed by Engr in charge.
All as per item No. 01 abovebut size 70 sq mm 3½ core
All as per item No. 01 abovebut size 35 sq mm 3½ core
All as per item No. 01 abovebut size 25 sq mm 4 core
All as per item No. 01 abovebut size 16 sq mm 4 core
All as per item No. 01 abovebut size 10 sq mm 4 core
All as per item No. 01 abovebut size 16 sq mm 2 core
All as per item No. 01 abovebut size 10 sq mm 2 core
Excavation in trenches nexc 1.5 mtr in depth and not exceeding 1.5 Mtr wide for laying of cable/pipe etc and getting out in any type of soil complete all as specified nad directed.
All as per Item No.9 above but exceeding 1.5 mtr & not exceeding 3 mtr in depth.
Returning filling in trenches excavated soil including spreading levelling watering and well ramming in layers n.exc 25 cm thick each layer as in soil complete all as specified nad directed..
Removing excavated materials n.exc 50 mtr depositing where directed at a level n.exc 1.5 m above the starting point complete all as specified nad directed.
Supply & laying of Telerex DWC(Double wall corrugated) HDPE pipe ISI marked ( Pipe colour orange) of outer dia 63 mm and Inner dia 50 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-Charge Make : Supreme / Astrol/Prince/Jain Irrigation
Supply & laying of Telerex DWC(Double wall corrugated) HDPE pipe ISI marked ( Pipe colour orange) of outer dia 50 mm and Inner dia 38 mm polythylene with smooth internal and profiled external surface for non pressure under ground cable icluding coupler and bends etc complete all as specified and directed by Engineer-in-Charge Make : Supreme / Astrol/Prince/Jain Irrigation
M/L for GI Tubes,of size 40mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M/L for GI Tubes,of size 50mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M/L for GI Tubes,of size 80mm dia Medium grade, galvanised, with all fitting , laid in trenches for protection of cable in road /drain crossing complete all as specified and as directed.
M&L for road cutting upto 300mm deep and 200mm wide for crossing GI pipe line through road including making good the disturbed surface by filling mass concrete( 1:2:4) etc complete all as specified and directed by Engineer-in-Charge. Note : Rate of mass concrete is included in quated rate.
Demolation of u/s cement concrete in coppings etc complete all as specified and directed by Engineer-in-Charge.
M & L for PCC(1:2:4) type C-2 using 20mm grade stone aggregates for coping and similar work all as specified and directed.
S&F PVC Junction box of size 250x200x100mm, IP 66 with hinged door including locking arrangment and MCB SP 6 Amp with necessary nut,bolt etc and including mounted on insulators with suitable holes to provide incoming and outgoing LT cables and street light MCB complete all as specified and directed
Supply and fixing wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, Three core cable in surface/recessed as required 2x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire (From PVC Junction box to Security light)
Material and labour for street light control board / box of size 0.50 X 0.50 X 0.20 m made out of 1.60 mm thick MS sheet fixed / mounted on pole by means of 2 Nos of FT clamps of size 25 X 3 mm comprising the following enclousers and connecting with suitable size of copper cable all as directed:- a) MCB, TPN, 63 Amps, - 01 No b) Timer switch, Astronomical type,timelight 40 A,3 pole c) Contactor ML 2, 40 Amps,415 Volt - 01 No d) R Y B LED Indicator e) All outgoing MCBs,Contractors connected through HRC Fuse including bypass switch
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 500 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking,should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainless steel glands Nuts & Bolts complete all as specifid and directed.(Main Panel)Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II. (i) Incoming MCCB 4P, 250 Amp, 50 KA,thermal and magnetic adjustable -01 No ( Ics = 100% Icu) (ii) Outgoing MCCB 4P 100 Amp,36 KA -02 Nos ( Ics = 100% Icu) (iii) Outgoing MCCB 4P 63 Amp, 25 KA -02Nos ( Ics = 100% Icu) (iv) Outgoing MCCB 4P 16-32 Amp, 16 KA -02Nos (v) Digital voltmeter & Ammeter with necessary CTs (vi) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vii) Phase indicating LED lamps (R-Y-B) -01 set (viii) Spare chamber for MCCBs - 01 Nos (outgoing side only)
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification, double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled, insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated, locking should be screw type,mechanical type,inter locking, should have danger notice for 415 volt,AC,mounted on 50 x50 x 6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and stainles steel glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II (i) Incoming MCCB 4P 100 Amp, 35 KA -01 No ( Ics = 100% Icu) (ii) Outgoing MCCB 4P 32-40 Amp, 25 KA -02 Nos ( Ics = 100% Icu) (iii) Outgoing MCCB DP 16-32 Amp, 16 KA -04 Nos (iv) Digital voltmeter & Ammeter with necessary CTs (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vi) Phase indicating LED lamps (R-Y-B) -01 set (vii) Spare chamber for MCCBs - 01 Nos (outgoing side only)
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification,double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated, locking should be screw type,mechanical type,inter locking, should have danger notice for 415 volt, AC, mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II. (i) Incoming MCCB 4P 100 Amp, 36 KA -01 No ( Ics = 100% Icu) (ii) Outgoing MCB 4P 16-32 Amp,16 KA -06 Nos (iii) Outgoing MCB DP 16-32 Amp, 16 KA -01 Nos (iv) Digital voltmeter & Ammeter with necessary CTs (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vi) Phase indicating LED lamps (R-Y-B) -01 set (vii) Spare chamber for MCCBs - 01 Nos (outgoing side only)
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification, double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled,insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated,locking should be screw type,mechanical type,inter locking, should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II. (i) Incoming MCCB 4P 100 Amp, 35 KA -01 No( Ics = 100% Icu) (iii) Outgoing MCB 4P 16-32 Amp, 16 KA -01 Nos (iii) Outgoing MCB 2P 16-32 Amp, 16 KA -06 Nos (iv) Digital voltmeter & Ammeter with necessary CTs (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vi) Phase indicating LED lamps (R-Y-B) -01 set (vii) Spare chamber for MCCBs - 01 Nos
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification, double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 300 Amps,4 strip,(3 phase & Neutral) complete drilled, insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated, locking should be screw type,mechanical type,inter locking, should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II. (i) Incoming MCCB 4P 100 Amp, 35 KA -01 No( Ics = 100% Icu) (ii) Outgoing MCB 4P 32-40 Amp, 16 KA -05 Nos (iii) Outgoing MCB DP 32 Amp, 16 KA -01 Nos (iv) Digital voltmeter & Ammeter with necessary CTs (v) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade, IS 694 marked of approriate size but not less than 2.5 sqmm (vi) Phase indicating LED lamps (R-Y-B) -01 set (vii) Spare chamber for MCCBs - 01 Nos
Supply,installation,testing and commissioining factory made LT feeder pillar panel CPRI approved, size of panel as per CPRI Specification, double door floor mounted outdoor type,as per IP-65 grade,made out of CRCA sheet 3.15 mm thick of outer body of suitable size with Aluminium bus bar 250 Amps,4 strip,(3 phase & Neutral) complete drilled, insulated with colour coaded insulation tape,mounted on insulators etc with RYB indicater,internal wiring with suitable size of copper wire,panel should be dust proof,vermin proof,powder coated, locking should be screw type,mechanical type,inter locking, should have danger notice for 415 volt,AC,mounted on 50 x50 x6 mm angle iron frame having minimum 2 feet ground clearanceduly embedded in and including PCC block(1:2:4) type B1 foundation for fixing of panel complete including ternination of all incoming and outgoing cables with suitable size thimbles/lugs and glands Nuts & Bolts complete all as specifid and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II. (a) Incoming MCCB 4P 63 Amp, 25 KA -01 No ( Ics = 100% Icu) (b) Outgoing MCCB 4P 32 Amp, 16 KA -05 Nos (c) Phase indicating LED lamps (R-Y-B) -01 set
M & L for fabrication of bus bar chamber suitable for 415 volts 3 phase 4 wire system with MCCB 32 A 16 KA 4 pole, outdoor type, double door, with pedestal mounted, weather and vermin proof fabricated out of 3.15 mm thick MS CRCA sheet with anti corrosive coating & finally epoxy polyster powder coating of flint grey shade including 3 nos. phase indicating lamps, insertion of suitable cable glands for all incoming and out going cable including grouting of panel board 60 cm above & 30 cm below ground level duly supported on 50x50x6mm angle iron frame & welding 45 cm long angle iron legs of size 50x50x6mm on all the four corners embedded in PCC 1:2:4 using 20 mm stone aggregate upto 30 cm depth complete all as specified and directed by Engineer-in-Charge Comprising of 4 nos. Aluminium bus bar 100 Amp for phases & 50 Amp for neutral mounted on DMC/ porcelain insulator support complete all as specified and directed.Note: All MCCB Shall be Thermal and Magnetic adjustable type as per IEC 6047-II.
Notes:- For Item No 24, 25, 26, 27, 28, 29, 30 1. The Panel Should be approved by CPRI. 2.The rates Quoted shall include for earth work,Plinth protection around the panel apprx 75cm and excavation for angle iron frame for foundation of panel board up to 0.50 m below GL in any type of soil and PCC 1:4:8 type D2 filling in foundation. The ground clearance of panel board shall be 0.40 M from GL to the bottom of panel board. 3. All MCCBs should be handle operated and All cable from old panel to be terminated to new panel with proper gland,lugs and straight through joint of same size if require at site rate should be included in quated rate.
Supply M&L for earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 32 X 6 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Supply M&L for earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 25 x4 mm as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, funnel with wire mesh, watering pipe 20mm dia protection pipe etc and testing on completion complete all as specified and directed. Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Dismantling carefully the existing LT overhead line ACSR conductor with cross arm of any size from its position by necessary disconnecting of conductor and removing complete all as specified and as directed
Dismantling stay assembly complete all as specified and directed
Dismantling of unserviceable existing cross arms made from channels, angles and unserviceable FI clamps, nuts, bolts etc from OH line and removing complete all as specified and as directed
S &F PCC Cable route Indicator with suitable reinforcement of size 50 x 10 x 10 cm with letter inscribed on both side as "MES LT CABLE " of specified front side not less than 30 mm as directed and mounted on PCC 40 x 30 x 30 cm complete using PCC 1: 2:4 B1 using 20 mm graded stone aggregate and including painting using cement based paint to the satisfaction of engr in charge
Dismantling of unserviceable insulator of any type complete from its position and removing all as specified and as directed
M&L for laying GI pipe Medium grade of size 40 mm dia to pass LT cables acoss road/drain/culvert/along wall all as specified and directed.
Supply and fixing wiring for circuit/submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, Three core cable in surface/recessed as required 2x 1.5 sq. mm + 1 x 1.5 sq. mm earth wire (From PVC Junction box to Security light)
Supply and fixing sintex box of size 250x200x100mm for street ligt control box including 10 Amps SP, MCB etc complete all as specified and directed by Engineer-in-Charge.
M & L steel tubular poles with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.00 Mtrs Long) with provision for luminiries mounting arms around the top of pole in round shape complete all as specified and directed
Supply and fixing of MS clamps of size 25x3 mm with nut, bolt and washers duly painted in two coats of aluminium paint over a coat of red oxide complete all as specified and directed.
M & L for PCC(1:3:6) type C-2 using 40mm grade stone aggregates as foundation of pole and similar work all as specified and directed.
M & L for PCC(1:2:4) type C-2 using 20mm grade stone aggregates for coping and similar work all as specified and directed.
M&L Street Light Fitting Bracket made out from GI Pipe upto 40 mm Bore (dia) or suitable for light fitting, Light Grade, not exc. 1.20 Metre long, bend to required shape and fixing to Poles, etc. with and including Mild Steel Flat Iron Clamps 40x5mm of suitable Length, 2 No. Nuts, Bolts, Washers, etc. including Painting with One coat of Red Oxide Zinc Chrome Primer and Two coats of Aluminium Paint to all Mild Steel Works complete all as specified and as directed.
S&F new street light fitting (LED) of capacity 90 W, 6000-6500 Lumen- 6000 Lm, 10 KV in build surg protection IP-66, die cast aluminium housing and 2.5 Sqmm service wire for necessary connection etc complete all as specified and directed by Engineer-in-Charge.Make : Philips/Havells/WIpro
M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 2.5 metres length, buried directly and preferably vertically in ground with top edge not less than 1.25 metres below ground level connected with earthing lead of 4mm dia galvanised iron or steel wire all as shown in Plate No. 2 to the earthing test point all as specified and indicated including testing on completion Note No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I. Note No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required (iii) PCC pit shall be provided at least 500 mm away from the pit and not on the earth pit itself.
Dismantling carefully the existing LT overhead line ACSR conductor with cross arm of any size from its position by necessary disconnecting of conductor and removing complete all as specified and as directed
Labour for restringing of LT over head line consisting of 4/5/6 conductors retrive from ser item no-01 by dismantling taking down,unserviceable , damged ACSR conductor, repairing wherever required including cutting, re-joining and restringing in, with proper sag, binding to insulator with and including aluminium binding wire complete all as specified and directed. Note : (i) Rate of Transporting of conductor from one site to another site is included this rate.
Material and labour for street light control board / box of size 0.50 X 0.50 X 0.20 m made out of 1.60 mm thick MS sheet fixed / mounted on pole by means of 2 Nos of FT clamps of size 25 X 3 mm comprising the following enclousers and connecting with suitable size of copper cable all as directed:- a) MCB, TPN, 63 Amps, - 01 No b) Timer switch, Astronomical type,timelight 40 A,3 pole c) Contactor ML 2, 40 Amps,415 Volt - 01 No d) All outgoing MCBs,Contractors connected through HRC Fuse
M&L Factory made Outdoor type Panel MOUNTED ON 40X40 X 5mm angle iron frame, made out of 16 SWG CRCA Sheet, Powder Coated, Weather Proof, Front Opening Shutter with proper Locking Arrangements, suitable for Totally Enclosed complete and grouting in Cement Concrete 1:2:4 (20mm graded stone aggregate) Work of suitable size including necessary Electric Connections and Testing, Comprising with the followings including Taking down unserviceable Panel, complete all as specified and as directed:-M&L Factory made Outdoor type Panel, made out of 16 SWG CRCA Sheet, Powder Coated, Weather Proof, Front Opening Shutter with proper Locking Arrangements, suitable for Totally Enclosed complete and grouting in Cement Concrete 1:2:4 (20mm graded stone aggregate) Work of suitable size including necessary Electric Connections and Testing, Comprising with the followings including Taking down unserviceable Panel, complete all as specified and as directed:- (a) Aluminium Bus-bar 4 Strip, 450mm long, 100 Amp, 415 Volt - 01 Set
Supply and install hi wall split units indoor/outdoor of Capacity 1.5 Ton complete with cordless remote control unit and with in built air ioniser and Plasma filter for better indoor air quality with minimum 5 star rating and Efficient & Hyper Tropical Inverter Split AC with Copper , blue film condensor and it is Equipped with R410 A gas Refrigerant having 25 mtr long reach Air flow,6 speed fan control,noise level within 34 db , with warranty 01 year warrenty, equipped with Indoor/Outdoor, remote Etc. Make:- Hitachi/'O' general/Carrier
M&L for submain wiring with 2 runs of 4 Sqmm & one run of 4 Sqmm single core copper conductor cable 1100 Volts grade complete in & including PVC casing & caping/Conduit complete.
S&F Sheet metal enclosure single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp complete all as specified and as directed.
Mahindra Electric Stores
M/s. N D Karande
KESARI AND SONS
R. T. Saluji
Ms. S.K. ASSOCIATES
BHAVIN INFRA
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .