| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.1 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹44.1 L+₹67,332.70 (1.55%)Rejected-Finance | L2 | Rejected-Finance Other than lowest bidder | |
| 3 | L3₹44.9 L+₹1.4 L (3.30%)Rejected-Finance | L3 | Rejected-Finance Other than lowest bidder | |
| 4 | L4₹46.8 L+₹3.3 L (7.70%)Rejected-Finance 0 | L4 | Rejected-Finance Other than lowest bidder | |
| 5 | L5₹47.2 L+₹3.7 L (8.62%)Rejected-Finance | L5 | Rejected-Finance Other than lowest bidder |
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
3 Sept 2021, 6:00 pmClosed
GE (AF) Bamrauli
GE (AF) Bamrauli
SPECIAL REPAIR TO LT PANELS AT VARIOUS LOCATION AND CONVENTIONAL LIGHT WITH ENERGY EFFICIENT LED LIGHT IN BUILDING NO. 159, AND ADDITION/ALTERATION IN BUILDING NO P-788 AND OTHER SANCTION WORKS UNDER GE (AF) BAMRAULI
2021_MES_455892_2
8657/E8
Open Tender
Civil Works
Works
180 days
GE (AF) Bamrauli
Please refer Tender documents.
6 documents required · 6 mandatory
₹500
Yes
GE (AF) Bamrauli
₹80,000
Yes
17 Nov 2021
14 Aug 2021
4 Sept 2021
14 Aug 2021
3 Sept 2021
20 Aug 2021
Amount
Demolition of brick work or stone/ boulder masonry built in cement mortar , including all quoins, arches, pillars, etc but excluding ashlar facings , dressed stone work and pre cast concrete articles complete all as specified and as directed by the Engineer-in-Charge.
Demolition of cement concrete in ground floors and pavings n Exc 15 Cm thickness ( below or above ground level ) complete all as specified and as directed by the Engineer-in-Charge.
M & L for PCC 1:3:6 Type C-2 using 40mm graded aggregate as in foundations, filling and mass concrete complete all as specified and as directed by the Engineer-in-Charge.
Taking down Chowkats or frames with shutter exceeding1.5 Sqm but not exceeding 4 Sqm each (Without taking off shutters from the frames)complete all as specified and as directed by the Engineer-in-Charge.
S&F 150mm, long, aluminium anodised barrel tower bolt of extruded section and fixed complete all as specified and as directed by the Engineer-in-Charge.
S&F 150 mm long , aluminium handles cast type, anodised and fitted complete all as specified and as directed by the Engineer-in-Charge.
S&F for powder coating Anodised aluminium frame for doors, windows, ventilators with one or more rebates including joining cleat for fixing etc. complete all as specified. (minimum thickness of powder coating 50 micron).complete all as specified and as directed by the Engineer-in-Charge.
M&L for Aluminium (powder coated) sliding glazed shutter of suitable size with necessary joining cleats, glazing clips, rubber gasket, aluminium snap beading and locking arrangement at both end all as specified and as shown and drawing complete all as specified and as directed by the Engineer-in-Charge. Notes : (i) Frame and Glass filling in panels to windows shall be measured and paid for separately under respective item of schedule 'A' part V. (ii) Thickness of powder (epoxy polyster) coating shall not be less than 50 Micron (iii) Shade/tint of powder coating (epoxy polyster) shall be as approved by GE. (iv) Aluminium section shall be as per drg No. CE/ALD/TD-194 sheet No. 1/2 & 2/2
S&F 5.50mm thick coloured Sheet glass, best quality and glazing with aluminium clips in square exc 0.5 sq. m in each pane complete all as specified and as directed by the Engineer-in-Charge.
S&F for 9mm thick pre-laminated particle board exterior grade prelaminated both side with decorative choice laminations fixed with screws to aluminium door etc complete all as specified and directed.
S&F for Stainless steel concealed door closer/over head in floor mounted best quality, suitable for door shutters of 851 to 1000 mm in width and (overall length of cover plate) 140mm etc complete all as specified and as directed by the Engineer-in-Charge.
S&F rebated mortice aluminium lock vertical type size 100mm with 4 levers.
M & L for Reinforcement cement concrete pre-cast reinforcement cover slab (1:2:4) type B-1 using( 20 mm graded crushed stone aggregate) RCC ring/Frame and MS frame set in CM (1:4) etc complete all as specified and directed.
M & L for TMT bars 8 mm dia and over cut to length, bent to shape required including cranking, bending, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9 mm dia complete all as directed.
Excavation over areas, not exceeding 1.5 mtr depth and getting out loose soft soil etc complet
M&L for returning filling in , including spreading , levelling , watering and well ramming in layers not exc 25 cm complete all as specified and as directed.
M&L for brick work with sub class B bricks with old size bricks straight or curved on plan exceeding 6 m mean radius built in CM (1:6) complete all as specified and directed
M&L PCC 1:4:8 type D 2 using 40 mm stone aggregate as in sub base of flooring / fdn of wall etc complete all as specified
M&L for PCC 1:2:4 type B 1 using (20mm graded stone aggregate) as in bed blocks, copings and like including weathering, slightly rounded or chamfered angles and throating as directed complete
M&L for rendering 15mm thick in cement mortar CM 1:4 in two layer (First coat 10 mm thick and second 5 mm thick)
M&L for preparation of newly plastered surfaces of walls and applying two coats of oil bound distemper over a coat of primer complete all as specified and directed
M& L for removing excavated material n exc 50 m and depositing where directed at a level N exc 1.5 mtr above the starting point complete all as specified and as directed by the Engineer-in-Charge.
M&L for preparation of old painted steel surfaces of any description not otherwise described over 10cm width or girth and applying one coat of synthetic enamel paint complete all as directed by Engineer in charge.
M&L for preparation of old painted wooden surfaces of any description not otherwise described over 10cm width or girth and applying one coat of synthetic enamel paint complete all as directed by Engineer in charge.
Dismantling floor hearth or wall tilling including cement mortar bedding , removing unserviceable tiles and rubbish off the premises for minor repair to floor tiles/ nahani traps / concealed stop cock and GI tubing in wall etc in patches complete all as specified and as directed by the Engineer-in-Charge..
S&F for Acid resistant tiles 15 mm thick vitreous ceramic , unglazed, set , jointed and pointed in chemical resistant mortor , resin type in floor complete all as specified and directed.
S&F 15 mm bore medium grade , galvanised , with all fittings , fixed to walls and ceilings or laying in floors all as specified and directed
S&F 15 mm bore bib tap chromium plated fancy type fixed to GI tube walls and ceilings or laying in floors all as specified and directed
S&F in rational moulded polyurethane water storage tanks 500 ltr capacity (Cylindrical vertical with closed top) hoisted and fixed in position all as specified in SSR Part-I
S&F stain less steel sink with drain board made out of 1.0mm thick sheet for kitchen or laboratory with plug, washers, waste pipe , cast iron cantilever brackets , connecting union overall size 915x460x with bowl size of 410x330x160mm
S&F 5 mm thick PVC wall panelling of desired colour / pattern as approved by users including back side grid support of PVC Sheet of 50mm width and avg distance between each supporting strip should be not more than 300 mm all as specified and as directed
Supply, laying and testing cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core complete all as specified and as directed by the Engineer-in-Charge.
M&L for excavation in trenches/Pits in any type of soil(soft/loose/hard/ dense soil), n.exc. 1.5M wide and n.exc. 1.5M deep and getting out complete, all as specified & directed .
Supply and spreading clean and dry sand (unwashed) in trenches around the cable for cushioning all as specified & directed
Supply and laying sub class 'B' bricks (Old Size) laid flat in trenches as cable covers all as specified and directed
S&F 40 mm dia galvanized iron pipe “Medium grade”, including fittings complete all as specified and as directed by the Engineer-in-Charge.
M&L for earthing complete with galvanised steel earth plate electrode 60 x 60 cm x 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised iron wire 4mm dia as earth lead wire by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No. 3, MES SSR Part I- 2009 with 15 mm dia medium grade GI pipe as a protection to earthing lead and 20 mm dia medium grade GI pipe for watering purpose including excavation & earth work in any type of soil, funnel, wire mesh, RCC pit with cover, cast iron frame complete and connected to earthing test point all as specified or indicated including testing on completion. Notes (i) The concrete pit shall be PCC (1:3:6) type C-1, 40mm thick precast cover slab of RCC with suitable Mild steel handle in lieu of cast iron cover shown in electrical plate No 3 of MES SSR Part-I complete all as specified and as directed by the Engineer-in-Charge. (ii) PCC pit shall be provide at least 500 mm away from the earth pit and not on just on the earth pit and extra cost of additional length of water pipes and fittings junction etc shall be deemed to be included in the rate. (iii) Item includes the cost of 7.5 metre earth lead wire and GI pipe for protection of earth wire. Any variation in quantity shall be adjusted.
S&F factory made, sheet metal enclosure distribution boards, double door type, protection class ( IP-42),vertical type suitable for mounting MCCBS, MCBs confirming to IS-13032, IS-8623, BS-5484 with min 200 Amps rating copper bus bar ,SP and N 4 ways ,415 volts Make :Schneider/ABB/Legrand complete all as specified and as directed by the Engineer-in-Charge. Note: MCB/MCCBs shall be measured and paid separately under respective item of this schedule
S&F MCCB, four pole, 415 Volt ,125 Amp rating, 25 KA ultimate breaking capacity fixed in DBs catered herein before complete all as specified and as directed by the Engineer-in-Charge.
S&F MCB, SP, 6 to 32 Amp rating, 230 volt, 10 KA, 'C' series suitable for fixing in DBs as item no 10 in this sch complete all as specified and as directed by the Engineer-in-Charge. Make : Schneider/Legrand
S&F sheet metal enclosure with socket and plug top and MCB single pole and neutral enclosure with two Pin and earth plug and socket complete with one single pole MCB, 240 V, 20 Amp complete all as specified and as directed by the Engineer-in-Charge.
S&F sub main wiring with 2 run of single core PVC insulated and PVC Unsheathed, multi-stranded copper conductor of nominal area 6 sqmm FR, 1100 Volts grade cable drawn into and including rigid non metalic PVC Conduit of including all fittings and one run of PVC insulated and PVC unsheathed, multi-stranded copper conductor of nominal area 6 sqmm FR 1100 volts grade cable continuous earth wire of green colour code complete all as specified and as directed by the Engineer-in-Charge Note:- (a) Two runs of 6.0 sqmm cable and one run of 6.0 Sqmm cable as earth lead with conduit shall be measured as one unit length for payment. (b) Quoted rate shall deem to be included cost of cutting chasses in wall for concealing conduit and making good to match with existing finish.
M&L for point wiring with PVC insulated, PVC unsheathed cable single core, nominal area 1.5 sq mm FR with stranded copper conductor 1100 volts grade drawn into and incl rigid PVC conduit (concealed) 19 mm internal dia with all PVC conduit fittings such as Tees, elbows, bend, reducers etc and 1.5 sq mm unsheathed copper conductor earth wire connected to earth dolly including CI/MS boxes 1.6 mm thick with two coats of anticorrosive paint outside and aluminum paint inside sunk in wall with 3 mm thick laminated bakelite Hylam/Arkay light brand sheet cover (white) for mounting of switches, sockets and switch sockets, regulators as required complete all as specified and directed for light/fan/bell point controlled by one switch single pole one way. Note :-(a) The rates of chase cutting on wall concealing conduit and steel terminal boxes are included in the unit rates.(b) Colour code of wire will be strictly followed , Red for Phase , Black for neutral and green for earth wire
All as per item No. 43 here-in-before but one 3 pin 5 amp switch socket out let independent complete all as specified and directed.
Supply & fix switch piano flush type, single pole one way, 5 Amp. complete all as specified and as directed by the Engineer-in-Charge.
S&F socket out let 2/3 pin 5 Amps flush type complete all as specified and as directed by the Engineer-in-Charge
S & F ceiling rose, surface bakelite, 65 x 50 mm,three terminals complete all as specified and directed.
Supply and fix exhaust fan 300/308mm sweep, heavy duty, four blade, double ball bearing, 1400 RPM, minimum air delivery discharge 6120 CMH suitable for SP, 230/250 volts, 50Hz, AC supply with louver shutter complete in existing opening and connecting with and including 3 run 1.5 sqmm single core, PVC insulated but unsheathed FR multi-stranded copper conductor cable from ceiling rose to fan and taking down existing exhaust fan complete all as specified and as directed by the Engineer-in-Charge. Make: CG/USHA/BAJAJ
M & L for point wiring with PVC insulated, PVC unsheathed cable single core, nominal area 4.00 sq mm with stranded copper conductor 1100 volts grade drawn into and incl rigid PVC conduit (concealed) with all PVC conduit fittings such as Tees, elbows, bend, reducers etc and 4.00 sq mm unsheathed copper conductor earth wire connected to earth dolly as required complete all as specified and directed for the one 3 pin 5/15 amp switch socket out let independent . Note :- The rates of chase cutting on wall concealing conduit and steel terminal boxes for modular point are included in the unit rates complete all as specified and as directed by the Engineer-in-Charge Note- colour code of wire will be strictly followed , Red for Phase , Black for neutral and green for earth wire
Supply & fix Modular switch 1 way 16A, 1 module complete all as specified and as directed by the Engineer-in-Charge
S&F Modular socket 6A/16A - 2/3 pin combined 2 module complete all as specified and as directed by the Engineer-in-Charge
S&F steel body desert cooler electric driven (single phase) 240 volt 50Hz having exhaust fan 1400 rpm 380 mm sweep & 5000 Cum per hr Capacity (Make Crompton/Havells/Bajaj or equivalent) with hub type impeller of and front grill, Submersible pump( Vansal) Crompton or equivalent with continuous regulator duly painted with two coats of enamel paints Make : Crompton or equivalent make all as directed by Engineer-in- Charge
Supply, installation, testing & commissioning of Tripod Chemical Earthing (i.e. Three chemical earthing are individually connected in Delta form through copper strip )which include: (i) Three No's 3000 mm long 50mm dia copper bonded rod with top removal compound filling cap, seepage holes, stainless steel fasteners, HDPE Lockable earth pit cover cum inspection chamber along with 150 Kg of Earth Enhancement Back fill compound including digging of pits. (ii) Copper earthing strip 25x3 mm for interconnection of all three pits along with necessary clamps. (iii) Any other accessories including design modifications, to achieve the required earth termination rod resistance value below 1 ohms or as per the OEM / International Standard recommendation. complete all as specified and as directed by the Engineer-in-Charge. Make: Indelec/Tercel/ Erico .
S& F Earth continuity conductor 25x3 mm copper strip fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required. complete all as specified and as directed by the Engineer-in-Charge.
Supply and laying in replacement of cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, elect power cable (heavy duty) 1100 volt grade with stranded aluminium conductor of size 16 Sqmm 4 core.
All as per item No 62 but size 25 sqmm 3.5 core.
As per item No 62 but size 35 sqmm 3.5 core.
As per item No 62 but size 50 sqmm 3.5 core.
As per item No 62 but size 70 sqmm 3.5 core.
As per item No 62 but size 120 sqmm 3.5 core.
M & L for point wiring complete with PVC insulated unsheathed stranded copper conductor cable 1.5 sqmm (FRLS)(nominal area) in and incl.concealed PVC conduit not less than 20mm outer dia med grade ISI marked comp.with all the accessories incl pressed steel concealed terminal box,grid plate and base plate suitable for Modular switch outlet 1.5 Sqmm PVC insulated unsheathed stranded copper conductor cable as continuous earth wire connected to common earth dolly complete all as specified and directed for the following : (a) For one light point/fan/Exhaust fan point controlled by one switch
All as per item No. 68 here-in-before but one 3 pin 5 amp switch socket out let on independent board complete all as specified and directed.
All as per item No. 68 here-in-before but one 3 pin 5 amp switch socket out let on same board complete all as specified and directed.
Supply and fixing Modular Switch single pole one way 6A, 230 Volts.
Suupply and fix electronic step type modular fan regulator 240 volt 50 Htz 120 watt (switch/socket type in shape) modular type
Supply and fixing recess mounting 2' x 2' LED fitting of 36watt with white powder coated CRCA housing with high power LEDs with aluminium front frame with flat white high transmission acrylic cover,6500k, 150 lumen/watt, 240 volt 50 Htz, all as specified and as directed Make : Philips/Havells/Syska
Supply and fixing LED fitting of 21 watt integral sleek extruded polycarbonate LED channel with white acrylic cover wall mounted type complete with 21 watt LED tube all as specified and as directed Make : Philips cat part No-BN021C LED20S PSU CDL GR or equivalent model of CG/ Havell's.
Fixing hi wall split units indoor and outdoor complete with cordless remote control nit and with in built air ioniser and plasma filter for better indoor air quality with minimum 5 star rated, invertor type and capacity 2.0 ton including breaking necessary hole in wall any type for fixing indoor and outdoor unit and making good disturbed surfaces with cement mortar and paint to match existing surface, all as required including necessary connections complete all as specified and directed. Note ;- Note :- Split AC unit (Indoor & out door units ) will be issued under Sch 'B' free for fixing
Supply and fix voltage stabilizer for automatic operation, single phase naturally air cooled outdoor type, Built in thermal overload protection, low & high voltage cut-off protection & designed for input variation between 90 V to 285 V with out put voltage stabilized at 23 V with accuracy of ± 2.5% and of capacity 5 KVA Make : V GUARD / BLUEBIRD or equivalent
M&L for laying of copper tubing of dia 5/8” including insulation with heavy duty rubber foam and brazing work complete all as specified and as directed by Engineer-in-Charge.
M&L for laying of copper tubing of dia 3/8” including insulation with heavy duty rubber foam and brazing work complete all as specified and as directed by Engineer-in-Charge.
S&F PVC insulated stranded 4 core flexible copper cable of size 2.5 sqmm 1100 volt grade complete all as specified and directed by Engineer-in-Charge.
S&F low density polyether pipe (LDPE) of pressure rating 6Kg/cm2 drain pipes of size 40 mm from indoor unit to exist point as per design including accessories clamps fasteners complete all as specified and as directed by Engineer-in-Charge
M&L for outdoor unit stand for wall mounting type or floor mounted complete factory made as recommended for make Airconditioner and approved by Engineer-in-Charge.
S&F factory made sheet metal enclosure distribution boards, (protection class IP-65) double door, vertiical type suitable for mounting isolator fixing MCBs conforming to IS : 13032, IS : 8623, BS : 5484 with 200 Amps rating copper bus bar, SP and N, 12 ways, 240 volts, Note : MCBs shall be measured and paid for separately under respective item of this schedule.
S&F MCB, single pole and neutral, 230 volts, 35 to 60 Amp rating, 'C' series fixed in DBs catered here-in-before.
S&F MCB, SP, 230 volts, 35 to 63 Amp rating, 10 KA, C series fixed in DBs catered herein before.
Taking down carefully aluminium batten point, wiring for light/fan/socket/bell or power point including. All fittings i.e. switch, sockets, ceiling rose, regulators, batten holders, etc. Complete and making good disturbed surfaces of wall/floor to match with the surroundings of wall/ceiling/floor etc including taking down old light fittings. Note :- (i) Contractors quoted rate of this item deemed inclusive of unscrewing of the serviceable fittings and fixture as directed and deposit in MES store yard. (ii) Quoted rate also deem to be included cost of cutting chases for taking out concealed conduit and nitch for terminal box. (iii) Decision of GE shall be final and binding in respect of serviceability of fittings/fixture. (iv) Exhaust fan and ceiling fan shall be taken down in under separate item of this schedule.
Supply and fix modular socket outlet 6Amps, 2 module complete
Supply and fix in replcement picture light made out of silver finish lamp base LED 12 watt 3000k/6500K 240 volt 50 Htz dimension 500x180x95mm Philips model No-31441 or equivelent Bajaj & syska
Supply and fix ceiling light made out of aluminium comprising 04 Nos 4 watt LED light adjustable alignment including fixing arrangement 240 volt 50 Htz dimension 560x82x60 mm Philips model No-56244/31or equivelent Bajaj/Syska
Supply and fix in replcement ceiling light comprising 02 Nos LED of 5.5 watt made colour white made out of metal 2x230 lumen dimension 280x155x100 mm philips model No-50312 or equivelent Bajaj or syska
Supply and fix flood light for building illumination 20 watt 240 volt 50 Htz 3000/6500K 120 lumen/watt IP-65 protection Syska model No-SSK-BLS-F-20 watt or equivelent Philips/Bajaj
Supply and fix in replcement flood light 50 watt 240 volt 50 Htz 3000/6500K 120 lumen/watt IP-65 protection Syska model No-SSK-BLS-COB-50 W watt or equivelent Philips/Bajaj
Supply and fix in replcement bollard light 9 watt with opal acrylic diffuser and IP-65 protection 240 volt 50 Htz including PCC work for foundation of 1:2:4 ratio. Bajaj model No-BGBOM650 9watt LED Tulip or equivelent Philips/Havells
Supply, laying and testing cable , in trenches,wall, on roof XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sq mm 2 core
Material and labour for replacement of GI tubing light grade 50 mm bore for passing through cables under the floor ,along the wall or along the pole complete all as specified and directed . Make – Ravindra,Oswal,Kinjal.
Supply and fix junction box made out of polycarbonate weather proof and ingress protection, two hole for incoming & out going cable comprising one single pole MCB of 6 Amp, busbar, fixing arraangement with clamp nuts and bolt.
Supply and fix feeder pillar box made out of 3mm CRCA sheet powder coated factory made out door type conforming to IP-65 canopy mounted protection with front and back hinges door with proper locking arrangement, rubber gasket on front and back to make it dust and vermin proof and painted comprising one incommer MCB TPN 100 Amp-01 Nos,MCB SP 40 Amp-03, MCB SP 32 Amp-02 Nos, 04 Nos copper bus bar strip duly fixed horizontally step manner , indication lamp -03 Nos, duly fixed on angle iron frame grouted in 1:2:3 PCC
Supply and fix 6 sqmm two core aluuminium multistranded PVC sheathed service cable 240 volt 50 Htz
Supply and fix pole mounted LED lights for outdoor land scaping lighting esthetically symetry, 35 watt 240 volt IP-65 protection Havells model No-victoript35WLED730PSYMTOTG including 8 feet 76 dia cast aluminium designer pole and broader designer base finished with polyurethane paint. including 1.5x1.5x2 feet size PCC foundaation of 1:2:4 .length of pole is 8 feet.
Supply and fix in replacement LED post top lantern IP-65 protection warm white made out of die cast of aluminium housing with decorative clear opal acrylic diffuser Bajaj model No-Arean BGCTW4LED WW or equivelent philips and Syska
Supply and fix wll mounted fan 400 mm sweep 240 volt 50 Htz copper wound Make - Bajaj/Havells/CG
M&L for laying of copper tubing of dia 3/8” including insulation with heavy duty rubber foam and brazing work complete all as specified and as directed by Engineer-in-Charge.
S&F PVC insulated stranded 4 core flexible copper cable of size 2.5 sqmm 1100 volt grade complete all as specified and directed by Engineer-in-Charge.
S&F low density polyether pipe (LDPE) of pressure rating 6Kg/cm2 drain pipes of size 40 mm from indoor unit to exist point as per design including accessories clamps fasteners complete all as specified and as directed by Engineer-in-Charge
M&L for outdoor unit stand for wall mounting type or floor mounted complete factory made as recommended for make Airconditioner and approved by Engineer-in-Charge.
M&L for Boring of holes (manually) under road, hard standing without damaging the surface for 50 mm bore GI pipe. Complete all as specified and directed. Note : (i) Depth of hole shall be 1 Metre below the top surface of Road/ Hard standing. (ii) Pipe shall be measured and paid seperately under respective item of the schedule.
Note :- Credit shown in credit schedule of tender document shall be considered by the tenderer while quoting the rates of various items. The same shall be recovered from various payment to contractor before handing over old material.
M/s Techno India and Company
M/s NSA Engineering Corporation
A S ENTERPRISES
M.R. ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .