| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.3 LAccepted-AOC | L1 | Accepted-AOC Lowest Bidder | |
| 2 | L2₹33.3 L+₹1.2 L (3.65%)Rejected-Finance H NO 29 DEVILAL COLONY TCP 2 HISAR CANTT HARYANA | HISAR | HISAR | HARYANA | 125006 | L2 | Rejected-Finance Not Lowest Bidder | |
| 3 | L3₹41.7 L+₹9.5 L (29.6%)Rejected-Finance | L3 | Rejected-Finance Not Lowest Bidder |
Tender Value
₹31.6 L
EMD Value
₹31.6 L
Closing Date
3 Feb 2024, 6:00 pmClosed
GE HISAR
GE HISAR
CA NO GE(H)-70/2023-24 SPL REPAIR TO LT PANEL and ALLIED WORKS OF CERTAIN OTM AND MD ACCN AREA AND PROVN OF TRANSFORMER PLINTH ALONGWITH CONNECTED IEMS AT HISAR MIL STN UNDER GE HISAR
2024_MES_635729_1
CA NO GE(H)-70/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
HISAR
AS PER NIT
6 documents required · 6 mandatory
₹500
GE HISAR
₹31.6 L
Yes
14 Mar 2024
5 Jan 2024
5 Feb 2024
5 Jan 2024
3 Feb 2024
21 Jan 2024
Amount
Excavation in trenches not exceeding 1.5 m wide and not exc. 1.5 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed.
Removing excavated material to distance n. exc 50m and depositing where directed at a level n. exc 1.5m above the starting point etc complete all as specified and as directed. .
Returning filling in incl spreading leveling watering and well ramming in layers n. exc 25cm thick etc complete all as specified and as directed.
M&L for Sand cushioning 230mm thickness with dry sand (one layer of 80mm thickness before laying of cable and other layer of 150mm thickness after laying of cable) and punned down to 180mm after laying of cable in trenches for protection of cable complete all as directed. Note :- For the purpose of payment only punned thickness shall be measured.
Taking out the old unserviceable LT underground cable of any size, 1100 volts grade, XLPE insulated and PVC sheathed, armoured heavy duty with multistrand aluminium conductors from trenches/wall/floor/road/ culverts or pole etc including cable cover complete all as specified and directed . Note : Excavation and earth work, duct work, GI pipe for laying of cable and sand cushing etc are beyond the scope of this item and shall be measured & paid for separately under relevant items of BoQ.
Laying only old bricks retrieved from item Srl Item No. 5.00 (here-in-before) as cable covers in trenches etc complete all as specified and directed.
M&L for brick covering to underground electric cable using sub class ‘B’ bricks, laid dry, flat, perpendicular to the direction of cable etc complete all as specified and directed. .
Supply , laying , jointing, testing and commissioning of size 16 sqmm 2 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, Strip armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 95 sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, Strip armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply , laying , jointing, testing and commissioning of size 120 sqmm 3.5 core LT underground cable , 1100 volts grade, XLPE insulated and PVC sheathed, Strip armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron strip 32x6mm size as earthing lead by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 40 mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing unserviceable earthing all as specified & as directed. Note :- PCC chamber shall be constructed at least 1.5m away from the earth electrode and pipe for watering shall be provided in slanting manners.
Supply, installation, commissioning and testing in replacement of MCCB 630 Amp ( fixed on existing panel) 415 volt, 4 pole, 50 KA breaking capacity with adjustable thermal and fixed magnetic type (Ics =100%Icu) complete with spreader terminals (legs) and with proper lugs and all fixing arrangement in existing panel complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 250 Amp ( fixed on existing panel) 415 volt, 4 pole, 36 KA breaking capacity with adjustable thermal and fixed magnetic type (Ics =100%Icu) complete with spreader terminals (legs) and with proper lugs and all fixing arrangement in existing panel complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 160 Amp ( fixed on existing panel) 415 volt, 4 pole, 36 KA breaking capacity with adjustable thermal and fixed magnetic type (Ics =100%Icu) complete with spreader terminals (legs) and with proper lugs and all fixing arrangement in existing panel complete all as specified and as directed.
Supply, installation, commissioning and testing in replacement of MCCB 63 Amp ( fixed on existing panel) 415 volt, 4 pole, 27 KA breaking capacity with adjustable thermal and fixed magnetic type (Ics =100%Icu) complete with spreader terminals (legs) and with proper lugs and all fixing arrangement in existing panel complete all as specified and as directed.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with Seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 250 Amps rating and 36 KA rupturing capacity, Adjustable thermal & adjustable magnetic release type specially fixed for outgoing supply with overload, short circuit and earth fault protection, adjustable type (Ics =100%Icu). - 02 Nos (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 100 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 No. (iii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 No. (iv) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 100 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 02 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 02 Nos. (iii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 250 Amps rating and 36 KA rupturing capacity, Adjustable thermal & adjustable magnetic release type specially fixed for outgoing supply with overload, short circuit and earth fault protection, adjustable type (Ics =100%Icu). - 02 Nos (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 200 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 No. (iii) On Load Change over switch 400 Amps 4 Pole (Make Havells Cap part No IHCNFE0400 or equivalent of make mentioned here-in-after is List of makes).- 01 No. (iv) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 200 Amps rating and 36 KA rupturing capacity, Adjustable thermal & fixed magnetic type (Ics =100%Icu). - 02 Nos (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 160 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 No. (iii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 100 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 02 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 Nos. (iii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity .- 09 Nos. (ii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts with Microprocessor release, 250 Amps rating and 36 KA rupturing capacity .- 06 Nos. (ii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 100 Amps rating and 36 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 01 Nos. (ii) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 03 Nos. (iii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of LT Panel, LT (415 Volts, 50 Hz , 3-Phase, 4 wire supply), CPRI approved, factory assembled ,outdoor type, weather and vermin proof (Protection Class IP-54), made out of 3.15mm thick (for external) and 2mm thick (for internal) MS Sheet CRCA sheet with both side (front and back) hinged, compartmental design with seperate door with provision of side cable relay suitable for 415 Volts, 3 Phase, 4 wire, 50 HZ supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with seven tank pretreatment solution prior to a Powder coat of SIEMENS grey shade RAL 7032 complete mounted on angle iron frame 40mmx40mmx6mm legs 45cm high above GL and 15cm embedded in ground with and including block of PCC 1:2:4 type B1 of size 30cmx30cmx30cm complete including and comprising of the following complete all as specified and directed including taking down existing u/s LT panel :-
(a) Bus bar chamber having 4 Nos air insulated Aluminium strip bus bars of rating not less than 1.5 times the rated capacity of the incoming MCCB as well as outgoings shall have aluminium TPN extension links (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs.
(c) Outgoing (i) MCCB 4 pole , LT 415 Volts, 50 Hz, AC, 63 Amps rating and 27 KA rupturing capacity, adjustable thermal and fixed magnetic type ( Ics =100%Icu).- 03 Nos. (ii) Fine wiring with single core copper conductor for instruments / indicating lamps - 01 Job
Note:- (i) All incoming /outgoing cables shall be connected through suitable size gland plate/glands and all spreader terminals of MCCBs should be connected with external links (bus bar). (ii) Taking out of all connections from old panels and connecting to new panel MCCB, bus bar by dressing and providing new thimbles included in quoted rates. (iii) Removing of all old debris of old plinth / panels from site deemed to be included in quoted rates.
Supply, installation, commissioning and testing of factory made, out door type, self standing, double door, front and back openable, APFC panel compartmental type with APFC relay 8 stage with heavy duty MPP capacitor bank 120 KVAR (5 KVAr - 03 No, 10 KVAr - 03 No, 25 KVAr - 01 No, 50 KVAr - 01 No with 7% detuned harmonics filter reactor) with thyrister control module and MCCB TP of 16 KA of 1.5 times of rating currect of capacitor suitable for each control and MCCB TPN 250 Amps 36 KA as incomer including control CT & control wiring complete having following assessories including control wiring with HR FRLS copper wire complete all as specified and directed including taking down existing u/s panel :-
Notes :- (i) Compact modular bolted design, removable side and back panels with option of top and bottom cable entry. (ii) Capacitor installed in removable assemblies for ease of operation and maintenance. (iii) Incoming of APFC panel of MCCB TPN 250 Amps, 36 KA breaking capacity with high electrolytic grade Aluminium bus bar of suitable rating. (iv) 120 KVAR (5 KVAr - 03 No, 10 KVAr - 03 No, 25 KVAr - 01 No, 50 KVAr - 01 No) with thyrister control module and MCCB TP of 16 KA of 1.5 times of rating current of each capacitor suitable for each control (each capacitor bank equipped with discharge resister) & 7% detuned harmonics filter reactor.
(v) High performance microprocessor based 3 Phase APFC relay 8 stage with Auto / Manual option. (vi) In built 3 Phase power analyzer, Ammeter, Voltmeter and PF meter (each have 01 No) (vii) Capacitor duty thyrister control modules with high thermal current carrying capacity and early make contacts to reduce inrush current for enhancing life of capacitors. (viii) Induced air system provided with axial flow fan / centrifugal fan. (ix) Bottom cable entry system available with front glass for viewing controller and analyzer from front.
Labour only for dismantling the serviceable MCCB / ACB from any existing panel to re-fixed the serviceable MCCB / ACB with all accessories in serviceable panel whose MCCB / ACB damaged / burnt complete all as specified and directed..
Supply, laying ,testing and commissioning of HT Underground XLPE insulated, screened PVC bedded galvanized steel strip armoured electric power cable (heavy duty) with aluminium conductor 11 KV grade (Earthed) of 95 Sqmm 3 core size cable comfirming to IS-7098 Pt-II cable laid in trenches / walls / ducts / poles. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Supply, laying, jointing, testing and commissioning of size 35 sqmm 3.5 core LT underground cable, 1100 volts grade, XLPE insulated and PVC sheathed, strip armoured heavy duty with multistrand aluminium conductors IS-7098, laid in trenches /fixed on wall /floor /road /culverts /pole or encased in GI pipe complete all as specified. Note : Sand cushioning, cable protection, GI protection pipe, clamps, jointing kits and excavation & earth work shall be measured & paid for separately.
Excavation in trenches not exceeding 1.5 m wide and exc 1.5 mtr and not exc. 3.0 m depth for laying cables, foundation for pole etc and getting out in soft/loose soil etc complete all as specified and as directed.
Supplying and laying un-reinfoced precast concrete cable cover of class HV type 1 with flat size 300 x 180 x 40mm compete all as specified and directed.
Supply, errecting & fixing in true vertical position pre stressed concrete pole conforming to IS-1678 of 11 mtr long, 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 complete as specified and directed. Note : (i) The conductors / earth wires on existing pole to be shifted on new pole after errection of new pole. The rate shall be include in above quoted rate. (ii) Earth work & PCC shall be measured and paid separately.
M&L for Galvanized iron tubing, 40mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (40mmx6mm) clamps, bolts, nuts and washers for protection of LT electric cable complete. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for Galvanized iron tubing, 80mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (40mmx6mm) clamps, bolts, nuts and washers for protection of LT electric cable complete. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for Galvanized iron tubing, 100mm bore light grade, ISI marked, including all fittings and laid in trenches/under road/drains, fixed to poles/walls with required size of flat iron (40mmx6mm) clamps, bolts, nuts and washers for protection of LT electric cable complete. Note :- Excavation & earthwork shall be measured & paid for separately.
M&L for laying 40mm stone aggregate in electrical installation or below 2 pole / 4 pole structure etc complete including making it's edges all as specified & directed.
M&L Danger notice plate of size 25 x 20cm of 1.6mm thick mild steel sheet painted with vitreous enameled white paint, with letters, figures, and conventional skull and bones, in signal red colour and fixed with MS clamps of flat iron of size 25 x 5mm, bolts, and nuts of approved size complete all as specified and directed.
M&L for Boring of holes under road, pavement hard standing by trenchless technology using appropriate meansfor laying of cable complete all as specified and directed.
M&L for Cross Arms bracings supports, clamps, eye hook and back plates fabricated from structural steel sections including pole clamps stay clamps, D clamps nuts, bolts, washers welding bending cold or hot drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of aluminium paint complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 60cmx60cmx6mm thick burried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of plate not less than 1.5 m deep below normal ground level and connected to and including galvanized iron earth wire 4 mm dia by means of GI nuts, bolts, check nuts, washers thimbles, etc as shown in electrical plate No 3 of SSR Part-I and connection to main switch board/Test point/panel/equipment and testing on completion including excavation and earth work in any type of soil, returning filling in, and removal of surplus spoil to a distance not exc 50 metre, charcoal and salt in alternate layer 15 cm thick all around the earth plate electrode, MS funnel with wire mesh, GI pipe medium grade 20 mm bore for watering and 15 mm bore upto 7.50 metre long GI pipe light grade for earth wire protection fixed with poles/wall with two clamps, made from MS flat 25 mmx3mm, bolts, nuts and washers, PCC chamber (1:3:6) type C1, 40mm thick precast RCC cover 1:2:4 type B1 shall be provided on CI frame etc complete including taking down existing u/s earthing all as specified & as directed. Note :- PCC chamber shall be constructed at least 1.5m away from the earth electrode and pipe for watering shall be provided in slanting manners.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination heat shrink type joint complete with jointing material & accessories suitable for 3 Core cable XLPE armoured Al conductor cable of size 95 sqmm.
Supply installation, connecting and testing gang operated air break switch, mounted on insulators HT 11KV 200 Amps rating, triple pole, nine insulator suitable for horizontal / vertical mounting fixed and spring loaded revolving tinned brass / copper contacts, galvanized steel base frame, 32 mm bore medium grade pipe Galvanized operating rod (Medium Grade), operating handle, locking arrangement MS clamps, bolts, nuts & washers etc including two coats of aluminium paint over a coat of red oxide primer complete all as specified and directed. NOTE :- (i) Cross arms of 2 pole/4 pole structure reqd for installation of GO switch, if reqd additional, shall be measured and paid seperately. (ii) Scope of work also includes ACSR conductors PVC sleeves, PG clamps and thimbles reqd for jumpers / connections to OH lines of 2 poles / 4 poles structures and outgoings feeders.
Supply and installation in replacement of drop out fuse assambly triple pole 11 KV, complete expulsion fuse element mounted on four / two pole structures complete all as specified and directed. Note : Cost of necessary nut, bolt & washers deemed to be included in quoted rate.
M&L for lightning arresters expulsion type complete with all fittings, transmission class discharge capacity 65 Kilo Amps 11000 volts complete including taking down the existing lightening arrestor complete all as specified and directed.
Supply, installation, commissioning and testing of LT Panel ,LT(415 Volts, 50 Hz, 3-phase, 4 wire supply) CPRI approved, factory assembled, out door type, weather and vermin proof (Protection Class IP-54) with 3.15 mm thick MS CRCA sheet with both side (front and back) hinged, compartmental design with seperate door, with provision of side cable ellay suitable for 415 volt , 3 phases, 4 wire , 50 Hz AC supply system double door opening for external, rubber lining, locking arrangement, painted externally and internally with two coats of synthetic enamel gray paint First Quality) over a coat of red oxide primer complete mounted on angle iron 40mm x 40mm x 6 mm legs 45 cm high above GL and 15 cm embedded in ground with and including bocks of PCC 1:2:4 type C1 of block size 30x30x30 cm comprising of the following.:- (a) Bus bar chamber having 4 nos air insulated Aluminium strip bus bars of rating not less than the 1.5 times the rated capacity of the incomer MCCB, as well as outgoings shall have aluminium (bus bar) of current carrying capacity not less than 1.5 times the rated capacity of individual MCCBs. (i) Main Incoming MCCB 320 Amps 4P 36 KA-01 (ii) Outgoing MCCB FP 415 Volt 250 Amps 36 kA-01 (iii) Outgoing MCCB FP 415 Volt 125 Amps 25 kA-01 (iv) Outgoing MCCB FP 415 Volt 100 Amps 25 kA-01 (v) Outgoing MCCB FP 415 Volt 63 Amps 25 kA-01, for Street Light (vi) LED Type RYB Phase Indicator -01 Set (vii) Digital VAFPF Meter -01 Nos (viii) Heat resistance sleeve (ix) Bus bar support Epoxy 50 mm (x) Brass nut bolt washer 10x15mm (xi) Sheet metal work including fabrication, PCC foundation etc (xii) Complete wiring with copper cable, thimble etc. Note: (1) All incoming/ outgoing cables shall be connected by suitable size gland plate/glands and All spreader terminals of MCCBs should be connected with extension links (bus bar). 2. All CTs, PTs shall be as per the rating of the switchgear and of Cast resin type. 3. PCC foundation 0.60 mtr from GL for mounting of Panel is deemed to be included in the quoted rate for the job. 4. Danger Notice plate shall be provided on either facia of the panel.
M&L for providing 100mm PCC platform on top of brick masonry of Size 3x3 mtrs (outer dimensions) and 1.2 mtr high from ground level and 0.5 mtr below ground level for placing HT Swith gare, chainlink fencing around the platform fixed to angle iron post 1.8 mtr high using angle iron of size 40mm x 40mm x 6mm, mild steel round bars (straight or cambered) 10mm dia for tightening of chain link fencing and 1.00m away from platform of transformer and Panel with entry gate, steps and applying a coat of black bituminious paint over a coat of red oxide primer on the steel surfaces complete all as specified and directed including provision as under :- (i) 100mm thick PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation of brick wall and fencing post including excavation in earthwork, return filling in and removal of surplus soil. (ii) Brick work with fly ash brick in CM 1:6 including 15mm thick plastering in CM 1:4 over exposed surfaces. (iii) 100mm thick hard core using brick bats of grade n.exc 63mm. (iv) 100mm thick PCC (1:4:8) type D-2 (using 40mm graded stone aggregate) as in sub base. (v) 100mm thick PCC (1:2:4) type D-2 (using 20mm graded stone aggregate) as in flooring finished even and fair. (vi) Two coats of cement base paint over a coat of cement primer over plastered surfaces complete. (vii) 24 RM Chain link MS galvanised fancing of mesh size 75mm x 75mm and dia of wire 3mm complete.
Transportation of transformer of required capacity from E/M yard to a Wkshp area and fixing/connection the transformer and LT panel complete all as specified and directed by Engineer-in-charge
S & F cable route indicator of size 100 mm x 100 mm x 5 mm thick GI plate with insertion there on bolted welded to 35 mm x 35 mm x 6 mm angle iron 60 cm long and frounting the sae in ground with PCC as required for LT/HT cabLe incl necessery earth work all as specified and directed.
M/s Devendera construction
SAINI ELECTRIC STORE
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .