Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹42.2 LAccepted-AOC | L1 | Accepted-AOC Found lowest and reasonble | |
| 2 | L2₹44.8 L+₹86,980 (1.98%)Rejected-Finance 205 PARSHAV VIHAR PLOT NO 50 1 P EXTN PATPARGANJ DELHI 110092 | DELHI | EAST DELHI | DELHI | 110092 | L2 | Rejected-Finance In order but L2 | |
| 3 | L3₹45.9 L+₹1.9 L (4.40%)Rejected-Finance 289 KASERU KHERA MAWANA ROAD MEERUT 250001 U P | MEERUT | UTTAR PRADESH | 250001 | L3 | Rejected-Finance In order but L3 | |
| 4 | L4₹48 L+₹4.0 L (9.19%)Rejected-Finance D 89 SHASTRI NAGAR MEERUT 250004 | MEERUT | UTTAR PRADESH | 250004 | L4 | Rejected-Finance In order but L4 | |
| 5 | L5₹51.1 L+₹7.1 L (16.3%)Rejected-Finance | L5 | Rejected-Finance In order but L5 |
Tender Value
Refer Docs
EMD Value
₹96,960
Closing Date
13 Aug 2022, 6:00 pmClosed
GE(U)E/M Meerut
Roorkee Road, Meerut Cantt
SPL REPAIR FOR REPLACEMENT OF 120 X CONVENTIONAL SECURITY LIGHTS WITH ENERGY EFFICIENT LED LIGHT AT IDSR AND SPL REPAIR/ REPLACEMENT OF LT PANEL AND ALLIED WORKS AT SUNDARJI ENCLAVE, SOMNATH ENCLAVE AND AHQ UNDER GE(U) MEERUT CANTT
2022_MES_538670_1
8451/E8
Open Tender
Electrical and Maintenance Works
Works
180 days
Meerut
Please refer tender documents
11 documents required · 11 mandatory
₹500
GE(U) E/M Meerut
₹96,960
Yes
29 Sept 2022
16 Jul 2022
15 Aug 2022
16 Jul 2022
13 Aug 2022
30 Jul 2022
Amount
Supply, installing, testing and commissioning of LT out door type factory made(CPRI Approved ), junction box of size 600mmX600mmX500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT Junction box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system,The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indiated in Hindi and English complete all as specified and directed.with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. Aluminium bus bar of 450 Amps rating with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size . Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws ,bolts, nuts and washers -08 Nos , complete all as specified and as directed. , The platform shall be such
that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge (NOTE:- Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
Supply, installing, testing and commissioning of LT out door type factory made(CPRI Approved ), junction box of size 900mmX600mmX500mm (over all dimension )with mild steel angle iron of size 40X40X5mm vertical frame and legs with mild steel flat iron 40X6 mm in horizontal sides of the frame LT Junction box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system,The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x5 mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front & back opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door pillar box etc with voltage and danger indiated in Hindi and English complete all as specified and directed.with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock-2Nos with 3 keys. with MCCB 4 pole, 415 volts AC grade, 200 Amps rating and 16 KA rupturing capacity - 01 No Aluminium bus bar of size 10X6mmX400mm long with drilled holes for incoming /out going cable core connection including aluminium lugs ,GI bolts ,Nuts and washers of suitable size
Porcelain / synthetic bridge insulators, heavy duty with necessary steel / GI screws ,bolts, nuts and washers -08 Nos , Porcelain / Bakelite rewirable type fuse carrier of capacity 32 Amps (Make-Anchor/Aristo) - 10 Nos complete all as specified and as directed. , Platform for the panel with PCC 1:4:8 type D-2 with 40mm graded crushed stone , 15 cm thick in foundation, brick work in CM 1:6 with sub class `B’, old size bricks, rendering 15mm thick in CM 1:6 on exposed surfaces and 100mm thick PCC padding 1:3:6, type C-1 using 20 mm graded crushed stone aggregate on top and grouting bolts etc for Junction box. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directed (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
Supply, installing, testing and commissioning, factory made of minimum size 1200 mm x 900 mm x 600 mm and tested . LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 350 Amps rating installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops
in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- (Near MT yard) (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
(I) Incoming :-
(i) MCCB 4 Pole, Microprocessor Based 250A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider )
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based 100A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals
(ii) MCCB 4 Pole, Thermal Magnetic Based 63A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -04 Nos along with Spreader terminals
(iii) MCB TPN 32 Amp C-Curve - 1No (Make-Schneider / Legrand L&T )
Supply, installing, testing and commissioning, factory made of minimum size 1500 mm x 900 mm x 600 mm and tested . LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 450 Amps rating ( MAIN OFFICE ) installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of size
25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- (Near MT yard) (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
(I) Incoming :-
(i) MCCB 4 Pole, Microprocessor Based 315A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider )
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based 100A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -3 Nos along with Spreader terminals
(ii) MCCB 4 Pole, Thermal Magnetic Based 63A, Breaking capacity 25 KA, 415 V, 50 Hz with OL, SC, protection, -03 Nos along with Spreader terminals
(iii) MCB TPN 40 Amp C-Curve - 2 No (Make-Schneider / Legrand L&T )
Supply, installing, testing and commissioning, factory made of minimum size 900 mm x 900 mm x 600 mm and tested . LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 450 Amps rating ( NEAR QTR GUARD ) installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of size
25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- (Near MT yard) (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
(I) Incoming :-
(i) MCCB 4 Pole, Microprocessor Based 315A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider )
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based 250 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -1 Nos along with Spreader terminals
Supply, installing, testing and commissioning, factory made of minimum size 1200 mm x 900 mm x 600 mm and tested . LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 500 Amps rating ( JCO CLUB BACK SIDE ) installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of
size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- (Near MT yard) (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
(I) Incoming :-
(i) MCCB 4 Pole, Microprocessor Based 400A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider )
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based 300 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -1 Nos along with Spreader terminals
(i) MCCB 4 Pole, Thermal Magnetic Based 100 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -2 Nos along with Spreader terminals
Supply, installing, testing and commissioning, factory made of minimum size 1200 mm x 900 mm x 600 mm and tested. LT feeder pillar box (KIOSK), outdoor type, platform mounted, suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system, having bus bar chamber with insulated aluminum bus bars 450 Amps rating (NEAR OFFR MD ACCN ) installed on porcelain insulators. The panel shall be dust and vermin proof, IP 65 class protection and made of 3.15mm CRCA MS sheet and 40x40x4mm thick angle iron frame work, powder coated finish over one coat of red oxide primer outside and two coats of red oxide primer on inside, front opening type, with aprons for cable entry, and fixing danger notice plate made of 1.6mm thick mild steel sheet, vitreous enameled white, of size 20 x 15cm with letter, figures and conventional skull bones in signal red colour and fixed front & back door LT panel etc with voltage and danger indiated in Hindi and English with double door shutter and locking arrangement (including provn of 65mm Godrej (Freedom) stranded lock with 2 keys, internal wiring with PVC insulated, stranded copper conductor, FRLS cables, IS-694 marked of adequate size but not less than 2.5 Sqmm. The platform shall be such that it is of a height 45 cm above the nearest road level. complete all as specified and directedincluding connections of all out going/in coming existing cables of size 25/35/50/95/120/ 150 sqmm by drawing /digging out cable from
loops in trenches out side the Bldg inclusive of necessary excavation and earth work as required and relaying the cables with retrieved bricks and providing new sand cushioning and crimping suitable size copper lugs for terminal connections of cables, necessary brick foundation with plastering to the Panel board, All out going feeders shall be connected by cable through suitable size gland plate / glands.& The various feeders shall be indicated by 50 mm size letters in synthetic enamel white paint and taking out of old skelton type panel with control switches complete all as specified and as directed Engr-in-Charge , The scope of work includes the following:- (Near MT yard) (NOTE:-Panel should be as per IEC- 61439 and Contractor shall Submit All Certificate Before Executing the work.)
(I) Incoming :-
(a) MCCB 4 Pole, Microprocessor Based 300A, Breaking capacity 36 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals (Make : Siemens: / L&T & Equivalent Schneider )
(II) Outgoing :-
(i) MCCB 4 Pole, Thermal Magnetic Based 125 A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -1 Nos along with Spreader terminals
(ii) MCCB 4 Pole, Thermal Magnetic Based 63A, Breaking capacity 16 KA, 415 V, 50 Hz with OL, SC, protection, -01 Nos along with Spreader terminals
(iii) MCB TPN 40 Amp C-Curve - 6 Nos (Make-Schneider / Legrand L&T )
Taking out the existing unsv ACB any size / Make and Supply and Fixing (Existing same model / size suitable for Eixting Panel size ) Air circuit breaker 630 A TP&N(4 Pole) (thermal magnetic DNI and microprocessor based SR21(LSIG+2SI) 415V, 50Hz, AC supply, draw out type, having microprocessor based release for over current and earth fault, IS-2516 marked, complete with racking inter lock and push button this incl removing existing old unsv ACP any size all as directed Engr-in- Charge Make: ABB/Legrand/Schneider
Taking down down of old existing cable and Supply, laying, jointing, testing and commissioning LT underground cables, 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, IS-7098 (marked, laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe complete all as specified and directed. Cables of the following sizes:- (Note;- Rate quotted includes terminal Lugs / road cutting/ wall cutting/ floor cutting and making good damged portion matching with existing surface with all existing finishes.) (Note :- Excavation & earthwork, duct work, GI pipe for laying of cable and sand cushioning / cable protection covers etc are beyond the scope of this item and shall be measured & paid for separately under respective items of Sch `A') All purchase bill and test certificate will be submitted at the time of material brought at site.
16 Sqmm 4 core
25Sqmm 4core
35 Sqmm 3.5 core
50 Sqmm 3.5 core
95 Sqmm 3.5 core
185 Sqmm 3.5 core
240 Sqmm 3.5 core
Relaying laying, jointing, testing and commissioning LT underground cables of any size , 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty armoured, with multistranded aluminium conductors, ( laid in trenches / ducts / fixed on poles / walls / laid under roads / paths / drain / culverts or encased in GI pipe) complete all as specified and directed. Cables of the following sizes:- (Note;- (i) Rate quoted includes terminal Lugs / road cutting/ wall cutting/ floor cutting and making good damged portion matching with existing surface with all existing finishes. (ii) Note :- Excavation & earthwork, duct work, GI pipe for laying of cable and sand cushioning / cable protection covers etc are beyond the scope of this item and shall be measured & paid separately under respective items of Sch `A'
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth and getting out in Soft/Loose soil including trimming sides and bottom of trenches complete all as specified
Returning, filling-in, including spreading, watering and well ramming in layers not exceeding 25 cm thick each, in soft /loose soil complete all as specified.
Removing excavated surplus soil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified.
Material and labour river washed and screened, dry sand for filling in trenches below and around underground cables for cushioning of cables complete all as specified. Note: Punned thickness of sand shall be measured.
M & L Bricks protection cover to under ground cable (with standard size fly ash bricks) with width equal to length of brick laid dry and flat abutting each other with gaps between adjacent brick not exceeding 10mm as directed.
Taking out existing old unsv pipe and Supply and laying/ fixing galvanised steel water tubing, medium grade, IS-1239 marked with all fittings (IS marked) and laid in trenches / under roads / in drains / fixed to poles/walls ( with required size flat iron clamp bolts, nuts and washers ) pipes of the following sizes of pipes :-
40 mm bore
50 mm bore
80 mm bore
100 mm bore
M&L auguring hole suitable for passing 40mm to 100mm bore pipe in true horizontal position under road, PCC paths etc., by means of mechanical ring/ auger after doing ultrasound to prevent any damage to existing cables pipe line coming in the route not exceeding 1.5 m in depth below existing surface level of road and not excd 30M in length complete all as specified. Note: Pipe shall be measured and paid separately under appropriate items and any dahage to existing cables of anytype shall be made good by the Bidder without any extra cost to department.
Taking out old stay Assembly and Supply and fixing stay assembly for LT poles complete, comprising of galavanised steel stranded stay wire 7 / 3.15 mm, galvanished steel stay bow 400 x 14, galvanized steel rod 2150 mm long 16 mm dia with nut bolts and washers, steel plate 230 x 230 x 6mm thick , 2 nos thimbles , loop insulator size 65 x 90 mm clearance hole 16 mm including clamps and fixed to stay clamp complete all as specified. (Note : Rate quotted includes Excavation, earth work and PCC )
Supply and fix in repair pin type insulator, porcelain, vitreous white, size 100mm height and 65mm dia, 1100 Volts grade, ISI marked, including one galvanised mild steel spindle, two Nos GI washers and one GI nut complete,all as specified and directed.
Supply and fix in repair shackle type insulator, ISI marked, porcelain, vitreous white, 1100 volts grade, ISI marked of size 90 x 75 mm, including galvanized mild steel strips 31x3 mm, washers, insulators bolts (12 mm dia), washers and nuts all as specified and directed.
Taking out old earthing and M&L plate earthing for sub station equipments complete with galvanised mild steel plate electrode 60 cm x 60 cm x 6.3 mm thick buried directly in ground vertically (in earth pit not less than 3.5 m below normal ground level) with the top edge of the earth plate at a depth not less than 2.75 m below normal ground level, the earth electrode surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides and incl GI earth strip 32 x 6 mm bolted (with GI nuts, bolts & check nuts) and riveted to earth plate at one end and connected to metallic bodies of HT/LT equipments etc at the other, earth strip encased in and including 40mm bore GI light grade pipe with all fittings from top of electrode to body of equipment fixed with and including 25 x 3mm flat iron clamps, bolts, nuts and washer and also including providing watering pipe 20mm bore GI pipe medium grade from bottom of earth pit to top of electrode complete with earth pit in PCC 1:2:4 type B-O using 12 mm graded crushed stone aggregate excavation & earth work and RCC cover complete all specified and shown in electrical plate No 5 of SSR Pt-I.
Supplying and fixing STRAIGHT THROUGH cable jointing Kit for 1100 V grade cable for complete with jointing material ( heat shrink type) and accessories suitable for 50 sqmm to 150sqmm 3.5/4 core XLPE armoured aluminkium conductor cable and testing aftre jointing complete all as specified and directed.
Cutting of worn-out / burnt aluminium cable terminal lugs from the HT/LT cable , crimping of new aluminium cable core and fixing with transformer/ Panel MCCB terminal/ FPB/ JB/ pole/DBs/ stud including cutting/ dressing of cable, disconnecting under ground / OH line cable conductor , cutting down worn-out portion and refixing with suitable lugs complete , including under ground cables of any type and size for repairs including taking out under ground cable loop from ground and making connections of restoration of electric supply complete all as specified. Note:- aluminim Bus bar/ Excavation, earth work , taking out cable protection covers, and sand cushion and relaying the same shall be deemed included in the unit rate quoted by Contractor)
Releasing the binding of ACSR conductor of OH lines from insulator , removing the jumper, connector, service wire, disconnecting the connection of UG cables and restretching of existing HT/LT OH lines , any size, length and span upto desired sag as directed by Engineer-in-Charge and rebinding the ACSR Conductor on insulator , reconnecting the UG cable etc complete all as specified. (Note :- Linear length centre to centre of the poles restretched shall only be measured as one span for the purpose of payment)
M&L preparation of old painted steel and iron surfaces of any description of panels , not otherwise described ,over 10 cm width or girth and painting one coat with synthetic enamel of approved shade using spray gun including cleaning, stopping and rubbing down and removing all drops etc. complete all as speciified.
Taking down of existing mild steel/ CRCA shutters of LT panel and repairing the same by welding and providing 100mm long medium weight mild steel hinges and 65mm size pad lock of make Godrej including painting the surafces with one coat of synthetic enemal paint to match with existing and making the shutter operations complete all as specified.
S&F 3.15mm thick mild steel/ CRCA steel shutters of LT panel duly fitted with 100mm long mild steel medium weight butt hinges -02 Nos per leaf duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed. (Note:- Superficial area of leaf shall be measured for the purpose of payment)
Taking out existing old unsv any type / size security lights and Supply and fixing LED street light fitting 90 Watt 230 V , 50Hz AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP -66 protection , Surge protection @4Kv internal 8kv external to driver with superier finish with top maintanable driver compartment complete with all accessories (as applicable to the fitting) the fittings with two pairs of necessary nuts and bolts with washers with suitable packing arrangement ( 40 mm light grade GI Pipe 40 mm size 1.2 mtr length bend to shape and fix 2 pole with FI 40 mm x 4 mmclamps, 2 Nos and suitable size of nut and bolts including painting work / welding work for existing pole with bracket ) to fixing with bracket etc incl duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and one runs of 1.5 Sqmm three core (nominal area) ( approx 9 meter) PVC insulated and PVC sheathed multi stranded unarmed Copper conductor cable LT 1100 volt grade FRLS drawn through pole for connecting to street light and pole JBs with cable terminal (MAKE: FOR CABLE HAVELLS,FINOLEX, MESCAB, KEI) pole wirings connecting up with streetlight feeder(Junction box) . complete all as Specified and directed Engr -in -Charge
Taking out existing old unsv any type / size security lights Supply and fixing LED street light fitting 70 Watt 230 V , 50Hz AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket , with impact and corrosion resistant including thermal management in multiple optics complete with IP -66 protection , Surge protection @4Kv internal 8kv external to driver with superier finish with top maintanable driver compartment complete with all accessories (as applicable to the fitting) the fittings with two pairs of necessary nuts and bolts with washers with suitable packing arrangement ( 40 mm GI pipe 30 CM / welding work for existing pole wirh bracket ) to fixing with bracket etc incl duly painted with two coats of synthetic enamel paint over a coat of red oxide primer and one runs of 1.5 Sqmm three core (nominal area) ( approx 9 meter) PVC insulated and PVC sheathed multi stranded unarmed Copper conductor cable LT 1100 volt grade FRLS drawn through pole for connecting to street light and pole JBs with cable terminal (MAKE: FOR CABLE HAVELLS,FINOLEX, MESCAB, KEI) pole wirings connecting up with streetlight feeder(Junction box) . complete all as Specified and directed Engr -in -Charge
Supply and fixing of mounting bracket made of 40 mm bore (or higher size to suit the opening of fitting) light grade GI pipe of 1.2 mtr length bent to shape and fixed to pole with FI 40mm x 6mm clamps, 2 nos and suitable size necessary nuts & bolts ,including Bracket complete set painting of two coat red oxide and aluminium painted fittings for Street lights with swaged tubular/ PCC pole connected all as specified and as directed Engr in charge.
Taking out existing old unsv any type / size Junction box and S&F pole mounting type junction box factory made of size 350x250x150mm of FRP sheet duly powder coated with front openable hinged door , locking arrangements, with 4 Nos aluminium bus bars 40 Amps rating mounted on porcelain insulator, cable glands and lugs consisting DP 6 Amps 'C' series (Make of MCB :Legrand / C&S / ABB) ,mounted on MCB rail -01 no. including mild steel flat iron clamp made out of 40x4mm FI, nuts, bolts and washers duly painted with two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified Engr-in- Charge.
Supply & fixing Unplasticised PVC pipes of prssure rating 10Kgf/cmSq 20 mm bore and 3mm thick complete fixed on pole using suitable clamps nuts & bolts (not less than 03 Nos) complete set painting of two coat red oxide and aluminium painted complete all as specified and as directed.
Supplying and fixing in repair automatic operation street light timing switch having lighting control (ON-OFF) through Astronomical Calculation of Sun rise/ sun set by setting date, time and degree of longitude and latitude without separate light sensors and prewired with suitable size of copper conductor single core PVC insulated and sheathed caable and all mechanism fitted into panel, outdoor type , pole mounted with FI 25x4mm clamps , nuts, bolts and washers dully painted, connecting and testing factory made , epoxy powder coated, Single Phase street light panel, digital 24 hrs, suitable for 6KW (max) complete with 32 Amps TP Contactor, and 32 Amps TPN MCBs and fixed on pole/ wall/ feeder pillar complete all as specified and directed.
sanjeev enterprises
Shikha Enterprises
mohanlal gupta
Narender Construction
Ravi Electrical
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .