Executive Engineer
Electric Division JPDCL Udhampur
Creation of HT and LT line along with Substation.
2023_PDD_201774_1
ED/UDh/90 of 2022-23, dt. 06/01/2023
Open Tender
Electrical Works
Turn-key
75 days
At Dalsar Block Chanunta
Please refer Tender documents.
2 documents required · 2 mandatory
₹1,000
Executive Engineer, Electric Division JPDCL
₹23,700
9 May 2023
7 Jan 2023
6 Feb 2023
7 Jan 2023
4 Feb 2023
7 Jan 2023
7 Jan 2023 - 20 Jan 2023
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for Erection of 11 KV line on 9 mtr. ST poles, 30mm sq. ACSR Weasel Conductor at WSS Balandh Block Parli Dhar.
8 mtr. Long poles (ST-410 SP15)
GI M Clamps for shackle insulator
50mm² ACSR Conductor
Shackle insualtor
Galvinized Nuts and Bolts.
Danger Plates with Clamps
Anti climbing device with clamps
Earthing complete by GI Rod 40 mm or GI Rod 20mm 2.5 mtr. Long through GI Strip
Painting of 8 mtr ST poles with red oxide
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI standed wire complete
Survey, Design, Supply, Transportation, Carriage, Erection, Testing and Commissioning for installation of 250 KVA Filter at WSS Dalsar Block Chanunta.
11/0.433 KV, 3-phase distribution Transformer 250 KVA with Bimetallic Terminal Connectors Energy Level-2 Copper Wound, & with LV Cable box having detachable Aluminium Gland plate
Gapless surge Arestor, 9 kv, 10 KA , LA with polymer housing stn. Type
11 KV GO AB Switch 3 phase, 3 pole, 200 Amp, vertical
11 KV Horn gap fuse set 3 phase 200 A
300mm², 1.1 KV Grade, PVC insulated stranded conductor FRLS Type
9 mtr. Long pole (ST-410 SP33)
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75KV Positive and 80 KV Negative, creepage distance 320mm
GI Channel /Angle/flat of sizes including clamps
Galvinized Nuts and Bolts.
Earthing of sub stn. Excavation of earth pit of dia 650mm & depth 3000mm installation of earthing pipe of 40mm Nominal bore & 4mm wall thickness & length 2.5 mtr. Long as per IS 1239. G.I Strip for neutral earthing of size 25mmx3mm for connection of transforemr body, GO Set & lightening arrestor as per IS 2629/85, GI Nuts & bolts refilled with earth enhancement materials and earth chamber with RCC Slab cover
11 KV Poloymer composite pin insualtor, 12 KV, 5KN Lightening impulse 75 KV Positve and 80 KV Negative, creepage distance 320mm
LT distribution box for 250 KVA DTR with MCCB for incomer and SFU's for outgoing circuits
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI standed wire complete
PG Clmaps
Danger Plates with Clamps
GI Barbed wire for Anticlimbing
HT trivector meter with CT/PT unit complete
Cement bottoming 1:2:4 mix as per REC standard 0.5 cum per pole
Painting of ST poles 9 mtr. of sub stn. Including cross arm, clamps with 1 coat of Red oxide
Painting of ST poles 9 mtr. of sub stn. Including cross arm, clamps with 2 coat of Aluminium paint
11KV Earthing /Discharge Rod (as per relevant IS ) for earthing of line at site (Set of 3)
M/s c.v Enterprises
M/S COMBINE GROUP OF ENGINEERS
Parbat and Sons
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .