Tata Power Delhi Distribution Limited
Rate Contract for supply of ACSR Conductors at Tata Power-DDL Site/Store
200001671
TPDDL-ENGG-ENQ-200001671-FY 24-25
Delhi
7 May 2024
7 May 2024
Tender compliances for the Tender No. XXXX - Compliance
1 Scope This specification covers the technical requirements of design, manufacture, testing at manufacturer’s works, packing, forwarding, supply and unloading at site/store and performance of 11kV Ring Main Units with various configurations in Non-motorized, Motorised and Smart RMU along with all accessories and necessary training for trouble free & efficient performance.
It is not the intent to specify completely herein all the details of tech design and construction of material. However, the material shall conform in all respects to high standards of engineering, design and workmanship and shall be capable of performing in continuous commercial operation in manner acceptable to the TATA POWER-DDL, who will interpret the meanings of drawings and specification and shall have the power to reject any work or material which, in his judgment is not in accordance therewith. The offered material shall be complete with all components necessary for their effective and trouble free operation. Such components shall be deemed to be within the scope of Bidder’s supply irrespective of whether those are specifically brought out in this specification and/or the commercial order or not.
2 Applicable Standards The equipment covered by this specification shall unless otherwise stated, be designed, manufactured and tested in accordance with latest editions of the following Standards /IEC and shall conform to the regulations of local statutory authorities.
Standards Details
IS9920: Part 1 High Voltage Switches, Part 1: Switches for Rated Voltages Above 1kV and Less Than 52 Kv
IEC 62271-200 HV switchgear and control gear-AC Metal Enclosed switchgear and control gear for voltages above 1kV and up to and including 52Kv.
IEC 62271-100 Alternating-current circuit-breakers
IS 513 Cold Rolled Low Carbon Steel Sheets and Strips.
IEC 60694 Common specifications for high voltage switchgear and control gear standards
IEC 62271-102 HV switchgear and control gear-Alternating current disconnector and earthing switches
IEC 60529 Degrees of protection provided by enclosures (IP Code)
IEC 62262 Degrees of protection provided by enclosures for electrical equipment against mechanical impacts (IK Code)
IEC 60060 High-voltage test techniques part-1 to 3
IEC 60947 /IS 13947 Low voltage switchgear and control gear
IEC 60439-1 Low-voltage switchgear and control gear assemblies- Type tested and partially type tested assemblies
IEC 60255-3 Electrical relays – Part 3: Single input energizing quantity measuring relays with dependent or independent time.
IEC 61869-2 / IS 2705 Current Transformers
IEC 60376 Specification of technical grade sulphur hexafluoride (SF6) for use in electrical equipment
IEC 61869-3/ IS 3156 Voltage Transformers
IEC 62271-206 High-voltage prefabricated switchgear and control gear assemblies – Voltage presence indicating systems.
IS 13573-2 Cable accessories for extruded power cable for Working Voltages from 3.3 kV up to and Including 33 kV.
Note- In case of any conflict on any technical particular in the specification, the stricter requirement mentioned in the relevant standard shall be valid.
3 Climatic Conditions at the Installation of rmu: Max. Ambient Temperature 50 0C
Average Ambient Temperature in peak summer months May to July 40 0C
Min. Ambient Temperature in winter months 0 0C
Relative humidity 20 to 90%
Average Annual Rainfall 760 mm
Average rainy days per annum 60 days
Max. Altitude above MSL Not exceeding 300 meters
Max. wind pressure 126 kg/sq. m. up to 10 meter height
Seismic level (horizontal ground acceleration) 0.3 g
Note- Atmosphere is generally laden with mild acid and dust suspended during dry months and subjected to fog in cold months. The design of equipment and accessories shall be suitable to withstand seismic forces corresponding to an acceleration of 0.3 g.
4 General Technical Requirements of rmu: Sr. no. Description Requirement
1 Application Three phase – Three wire
2 Rated Voltage 12kV
3 Service Voltage 11kV
4 System Frequency 50 Hz
5 Internal Arc rating Indoor Application- IAC AFL or Better
Outdoor Application- IAC AFLR
6 Internal Arc test 20 kA for 1 Sec.
7 Lightning Impulse withstand Voltage 75 kV Peak
8 Power Frequency withstand voltage 28 kV rms
9 Rated current of incomer load break switch 630 A
10 Rated current of Circuit-breaker 630 A
11 Rated Short time current withstand (3 sec) 21 kA
12 Rated Short circuit making current 50 kA
13 Number of operations at rated short circuit current on line switches, earthing switches ,CB 5 close
14 Opening time of breaker (max.) without relay time 2.5 cycle
15 Closing time of breaker (max.) without relay time 3 cycle
16 Breaker Duty Cycle O – 3min – CO – 3min – CO
17 Rated cable charging interrupting current of incomer-
- Load Break Switch 10 A
18 Rated cable charging breaking current of breaker
19 Insulating medium SF6
20 Interrupting medium Vacuum- for CB and SF6 for LBS and earth switch
Contact martial in Vacuum bottle Copper chromium with silver plating or better
Make of vacuum bottle Bidder to mention make, should be same as mentioned in type tested report of same model and design.
21 Temperature Rise Maximum permissible temperature rise for bus bar shall not be 65˚C at an ambient temperature not exceeding 40˚C, as per IEC 62271-1. However, the temperature rise for accessible enclosures and covers shall not exceed 30K and in case, they are not required to be touched during normal operation, the limit shall be raised by 10K.
22 Cable compartment Front opening cable compartment for all feeders
Types of Ring Main Units shall be as under:
4.1 RMU configurations i) 3 Way with 1 CB (For Indoor and Outdoor application): Both side extensible
2 Nos. 630A Incomer Load Break Switches + 1 No. 630A Local Feeder/transformer Control Vacuum Circuit Breaker with self-powered O/C + E/F relays+ shunt trip coil + 1 No. Electronic Fault Passage Indicator on left LBS in each RMU
ii) 3 Way with 2CB Non extension type(For Indoor and Outdoor application):
1 Nos. 630A Incomer Load Break Switches + 2 No. 630A Local Feeder/transformer Control Vacuum Circuit Breaker with self-powered O/C + E/F relays+ shunt trip coil+1 No. Electronic Fault Passage Indicator on left LBS in each RMU + LBS with 1Cx 630 sq mm cable provisions.
iii) 4 Way with 2CB (For Indoor and Outdoor application): Both side extensible
2 Nos. 630A Load Break Switches + 2 Nos. 630A Feeder Vacuum Circuit Breakers with self-powered O/C + E/F relays + shunt trip coil + 1 No. Electronic Fault Passage Indicator in left side LBS in each RMU with 3CX400sq.mm cable suitability in all feeders
iv) 4 Way with 2CB (For Indoor and Outdoor application):
2 Nos. 630A Incomer Load Break Switches + 2 No. 630A Local Feeder/transformer Control Vacuum Circuit Breaker with self-powered O/C + E/F relays+ shunt trip coil+1 No. Electronic Fault Passage Indicator and 1Cx 630 sq mm cable suitability in one LBS.
v) 4 Way with 3 CB Non extension type (For Indoor and Outdoor application):
1 Nos. 630A Incomer Load Break Switch + 3 Nos. 630A Feeder Vacuum Circuit Breakers with self-powered O/C + E/F relays + Shunt trip coil + 1 No. Electronic Fault Passage Indicator in left side LBS in each RMU
vi) 5 Way RMU (For Indoor and Outdoor application):
2 Nos. 630A Incomer Load Break Switch With Electronic Fault Passage Indicator in each LBS + 3 Nos. 630A Feeder Vacuum Circuit Breakers with self-powered O/C + E/F relays+ Shunt trip coil
Additional - 4 way Isolator
Additional - 1 way Isolator
Cable Voltage presence Indicators having auxiliary contacts to be provided in each compartment of all type of RMUs in above mentioned combination. All LBS, EW and CB shall be with auxiliary contacts for SCADA status indication. Provision for future motorization on of LBS and CB should be kept in configuration while designing RMU for non-motorized units. All shunt trip coils shall be 24V DC.
The smart RMU can be one side extendable and motorised indoor RMU to be both side extensible.
S.N. Description As specified by TATA Power-DDL (Options defined in specs)
1 RMU Category (Normal, Motorized or Smart) 3Way - 1CB or 2 CB
4Way - 2 CB or 3 CB
Please specify the type i.e. normal, motorized or smart RMU based on tender item codes requirements.
2 RMU application Indoor or Outdoor as mentioned in tender
3 Offered Model nos. and OEM type a. 3Way (E/NE, I/D or O/D )
b. 4Way (E/NE, I/D or O/D )
c. 5 Way (E/NE, I/D or O/D )
4 Dielectric medium SF6
5 Interrupting medium a. Vacuum- for CB
b. SF6 for LBS, disconnector and earth switch
6 System Frequency 50 Hz
7 Rated Voltage 12 KV
8 Service Voltage 11 KV
9 Rated current -Line Switches 630 A
10 Rated Current-CB and LBS 630 A for all type
11 Rated Short time current withstand (3 sec ) 21 KA
12 Rated Short time Making capacity 50 KA
13 Rated cable charging interrupting current of incomer load break switch 10A
14 Rated load interrupting line current 630 A
15 Rated cable charging breaking current of breaker 25 A
16 Lightning Impulse withstand Voltage 75 kVp Min.
17 Power Frequency withstand voltage 28 kVrms.
18 Dimension (LxWxH) To be provided by bidder
19 Total weight To be provided by bidder
20 Paint shade for outer encloser Light Gray shade RAL 7032
21 Operating handle To be provided by bidder as a part of RMU with each RMU and to be placed on front or on door
22 Non removable MIMIC Diagram on Front of panel To be provided by bidder with detailed descriptions as mentioned in specs. And earth switch marking on yellow background.
23 Separate MIMIC plate/front cover for each feeder Each feeder shall have separate MIMIC plate/front cover to cover the mechanism for safety.
5 General construction for RMU
5.1 Main tank 5.1.1 The switchgear and bus bar shall be contained in a stainless steel tank filled with SF6 gas and the outer body shall be made of GI high tensile steel/CRCA 2mm thick with gland plates as per IS 513.
5.1.2 The main tank shall be of Stainless steel grade 304 or better with sheet thickness of 2.5 mm minimum and meet the “sealed pressure system” criteria in accordance with the IEC 62271-200. This is a system for which no handling / refilling of gas shall be required throughout the expected operating life, i.e. 30 years. Sealed pressure systems are completely assembled, filled and tested in the factory.
5.1.3 Bidder should use Sniffer Leak Detector Technology for leak detection of each and every sealed tank.
5.1.4 The maximum leakage rate of SF6 gas shall be lower than 0.1 % of the total initial mass of SF6 gas per annum. The filling pressure for the switchgear shall be just above the atmospheric pressure so as to prevent the tendency to leak. SF6 gas used for the filling of the RMU shall be in accordance with IEC 376.
5.1.5 It is mandatory to fit an absorption material in the tank to absorb the moisture from the SF6 gas and to regenerate the SF6 gas following arc interruption. The degree of protection for RMU tank (Indoor/Outdoor) shall be IP 67.
5.1.6 The RMU shall be complete with all connection and copper bus bar with continuous current carrying capacity of 630A. The bus bar shall be fully encapsulated by SF6 gas inside the steel tank.
5.1.7 The main bus bar current density shall be less than 2.7A/sq.mm
5.1.8 The tank shall have an separate SF6 refilling valve and the filling pressure must be mentioned near the valve. And the refilling valve should be marked properly.
5.1.9 If same valve is used for pressure indicator or remote communication then the procedure to refill to be mentioned near the NRV from with permanent sticker.
5.1.10 The SR6 tank shall be completely enclosed in the enclosure such way that any rodent entry on top or side of tank is deterred. Only in indoor RMU- the rear side of SF6 tank exposed (without cover/CRCA) shall be acceptable provided there is no damageable part in rear. The rear and top of tank is enclosed such a way to avoid any rodent entry on tank from any side.
5.1.11 All current carrying components shall be of copper inside tank.
1 Temp rise above ambient of 50 deg. Type Tested as per IEC and complying to requirements)
1. Designed ambient temp. 1. Bidder to mention design ambient temperature.
2. Any de-rating applicable at 50 deg ambient
2. Bidder to provide de-rating chart for 45, 50 & 55 deg ambient temperature.
2 Minimum Gas pressure in bar To be provided by bidder based on type tested design
3 Main Copper Bus bar Cross Section To be specified by bidder as per design
4 Main Busbar current density To be provided as per design
5 SF6 Tank design Hermetically sealed with robotically welded or TIG & MIG welded, unpainted stainless steel enclosure with SF6 Gas. Sealed pressure system such that no refilling of gas is required for 30 years. Complete body shall be tamperproof to prevent access to live parts. No gaskets shall be used.
6 Tank material and grade of SS and welding Should be of SS and non-corrosive, offered grade of SS to be mentioned. Minimum grade shall be SS304. The welding shall be such that there shall be corrosion of welding for useful life of equipment.
7 Guaranteed SF6 leakage per annum Less than 0.1%.
8 Moisture absorption material in SF6 tank Bidder should provide the detail of the moisture absorption material.
5.2 General details 5.2.1 The mimic board shall be provided with IP2X degree of protection for Indoor RMUs and protection for Outdoor RMUs shall be minimum IP 54(Main door closed). Cable compartment shall be IP54.
5.2.2 The RMU shall be suitable for mounting on plinth with trench below and shall have base frame on sides with mounting bolt accessibility from outside of RMU the mounting bolts provision shall be min. M12 bolts on all four sides.
5.2.3 The provision for cabling shall be through base plate from bottom of RMU through trench below.
5.2.4 The RMU shall be designed so that the position of the different devices is visible to the operator on the front face plate with permanent type indicators.
5.2.5 The RMU shall be identified by an appropriately sized permanent labels which clearly indicates the functional units and their operation directions etc. The ON or OFF shall be marked as words and only I/O labelling shall not suffice.
5.2.6 The RMU shall be designed to be tamper proof so as to prevent access to all live parts during operation without the use of special tools.
5.2.7 There shall be continuity between the metallic parts of the RMU and cables so that there is no electric field pattern in the surrounding air, thereby ensuring the safety of people. The enclosure and cable compartment and tank shall be connected to common earthing.
5.2.8 All parts of main circuit to which access is required or provided shall be capable of being earthed prior to becoming accessible. This does not apply to removable parts which become accessible after being separated from the switchgear and control gear. The cables shall be earthed by an earth switch with short-circuit making capacity in compliance with IEC 62271-102.
5.2.9 The LBS /CB shall not be closed in case Earth Switch is closed. The earth switch shall be fitted with its own operating mechanism and manual closing shall be driven by a fast-acting mechanism, independent of operator action.
5.2.10 Mechanical interlocking systems shall prevent access to the operating shaft to avoid all operator errors such as closing the earth switch when the Load break switch is closed and when cable is charged.
5.2.11 All panel covers shall be provided with anti-vandal screw bolts so that opening of panel covers is only possible with special tools, which shall be provided by the Bidder as mandatory spare/tool.
5.2.12 The default design of cable compartment shall be for 3Cx400sq.mm cables (91mm external dia.). Cable boots, gland plate, cable cleat, washer, bushings & terminal bolts should be suitable for 3Cx400 sq.mm cables in all RMU compartments.
5.2.13 The cable gland plate shall have split type design having two parts for removal of cable with termination.
5.2.14 Three way with two CB & Four way configuration following thing to be complied: The incomer LBS shall be suitable for 1Cx 630 sq.mm cable. Cable boots, gland plate, cable cleat, washer, bushings & terminal bolts should be suitable for 1Cx 630 sq.mm cable in LBS cable compartment. The other two CB compartment shall be suitable for 3Cx 400 sq.mm cable termination. The terminal bolt used in LBS compartment shall have 15mm longer than regular bolt to accommodate the mechanical type lug having large thickness.
1 Minimum Operation class of RMU components, Bidder to mention the class designation as per type test reports available in accordance to relevant IEC as mentioned in clause 7.1 for each module,
1. CB- E2,M1,C1 1. CB- E2,M1,C1
2. LBS- E3,M1, 2. LBS- E3,M1,
All classification declared to be supported with type test reports & mentioned on name plate.
2 Opening time of breaker (max.) Without relay time 2.5 cycle
3 Closing time of breaker (max.) 3 cycle
4 Breaker Duty Cycle O – 3min - CO - 3min - CO
5 i. Mechanical endurance for Isolator & Earth Switch Min 1000 Operations
ii. Mechanical endurance for Circuit Breaker Min 2000 Operations
6 SF6 Gas pressure manometer with indicating bars/scale to measure the actual gas pressure (indirect method RFS etc. not accepted ) 1. Dial type Manometer to be provided for gas pressure indication
2. Contacts to be provided and wires up on the TB for SCADA communication of gas status.
7 Enclosure The RMU metal parts shall be greater than 2mm thickness high tensile steel/CRCA. The overall paint thickness shall be not less than 70 microns.
8 Degree of protection a. IP 67 for the tank and
b. IP2X for the front cover / mimic board and
c. IP 54 (Main door closed) for Outdoor RMUs.
d. IP 54 for cable compartment
5.3 Internal Arc testing
5.3.1 Any accidental over pressure inside the sealed chamber tank shall be limited by the opening of a pressure limiting device provided on the tank.
5.3.2 Exhaust Gases shall be released to the bottom or top without affecting cables and termination of the RMU with partition between cable chambers such way that exhaust gases are releases away from the operator.
5.3.3 Bidder shall provide type test report to prove compliance to the ‘Internal fault IAC- AFL minimum for indoor and A-FLR for outdoor with bottom or top release’ as per IEC 62271-200 on main tank and cable chambers as well. Bidder to submit the type test for both main tank and cable chamber for 20kA current for 1 Sec.
5.3.4 An anti-reflex mechanism on the operating lever shall prevent any attempts to reopen immediately after closing of the switch or earth switch. All manual operations shall be carried out on the front of the RMU.
5.3.5 There should not be any gas leakage from tank, if In case of SF6 gas leakage from gas tank found within guarantee period, bidder shall arrange for site visit and to lift the defective equipment and provide replacement/repair of complete RMU same to be done free of cost by bidder.
5.3.6 Bidder shall conduct root cause and defect analysis of the failed unit and submit the root cause analysis report within two months of reporting of failure.
1 Internal Arc rating a. Indoor RMU- IAC AFL or better as per type test for main tank
b. Outdoor RMU - IAC AFLR or better as per type test for main tank
2 Internal Arc test current and duration For main tank - 20kA for 1 Sec. as per type test report
3 Flue gas release path from main tank Bidder to mentioned the offered details
4 Internal Arc test For cable compartment - IAC AFL with 20kA for 1 Second as per type test report
5 Flue gas release from cable compartment & main tank Bidder to mentioned the offered design details & submit the drawing for evaluation for each model offered
6 Barrier between main tank flue gases release and cable compartment Bidder to mention safety aspects taken care in offered design & presence of barrier and its material as per type testing done on cable compartment and main tank.
5.4 Incomer Load Break Switches (LBS)
5.4.1 Load break switches shall be maintenance-free. The position of the power contacts and earthing contacts shall be clearly visible on the front of the RMU. The position indicator shall provide positive contact indication in accordance with IEC 60265-1. In addition, manufacturer shall prove reliability of indication in accordance with the standard. The switches shall be of the “increased operating frequency” in accordance with IEC 60265-1.
5.4.2 The LBS shall have at least 3 positions, open-disconnected, closed, and earth ( with making capacity) and shall be constructed in such a way that natural interlocking prevents unauthorized operations.
5.4.3 The disconnector should have the maximum 200micro ohm contact resistance.
5.4.4 Earthing of the cable shall be either through a three position switch & Earth Switch having fault making capacity.
5.4.5 The switches shall be fully mounted and inspected in the factory. Provision for future motorisation of LBS and CB should be kept in configuration while designing RMU.
5.4.6 The load break switch and earthing switch operating mechanism shall have mechanical endurance of at least 1000 operations. The type test reports to be submitted along with Bid.
5.4.7 Load break switch shall have mechanical switch operation counter and should be visible on front in horizontal alignment.
5.4.8 The Load break switch should have minimum spare (for TATA POWER-DDL use) 3 NO+ 3 NC auxiliary contacts and 1NO+1NC for earth switch.
5.4.9 The load break switch shall be compatible for remote operation without any modification of the operating mechanism and without de-energizing the RMU, The LBS shall be fitted with an electrical operating mechanism and can remotely open-disconnected, closed and earthed from a reserved location.
5.5 Circuit Breaker For Transformer / Local Feeder Control
5.5.1 The circuit breakers/ interrupter shall be of the maintenance free.
5.5.2 The position of the power and earthing contacts shall be clearly visible on the front of the RMU.
5.5.3 The circuit breakers shall have at least 2 positions: Open-disconnected and closed and shall be constructed in such a way that natural interlocks prevent all unauthorized operations.
5.5.4 In view of safety each VCB shall be assisted with feeder side disconnector having 3 positions, open-disconnected, closed, and earth (having fault making capacity) and shall be constructed in such a way that natural interlocking prevents unauthorized operations.
5.5.5 They shall be fully mounted and inspected in the factory.
5.5.6 Breaker contact resistance should be <=50 micro-ohms. The various circuit contact resistance should comply with provisions in IEC 62271-200.
5.5.7 The breaker should have minimum spare (exclusively for TATA POWER-DDL use) 4 NO+ 4 NC auxiliary contacts.
5.5.8 The vacuum interrupter shall withstand 10-7 milli-bar Vacuum Pressure ensuring high quality vacuum for interruption and shall have Copper Chromium Arcing Contacts. The interrupter manufacturing unit shall have shall be single Shot brazing and have high First pass Yield. (Shall be part of Bidders own vendor evaluation criteria)
5.5.9 An operating mechanism can be used to manually close and open the circuit breaker with single push on push buttons. It shall be fitted with a local system for manual tripping by an integrated push button. There will be no mechanical automatic re-closing.
5.5.10 The operating mechanism shall be compatible for remote/ SCADA operation. The required motor for this operation shall be delivered separately to stores (at a later date) and shall be compatible with older versions of RMUs already working within the TATA POWER-DDL network.
5.5.11 The circuit breaker shall be associated with an integrated protection unit that will operate without any auxiliary power supply and shall include three toroid transformers incorporated in the transformer tee-off bushings, an electronic self-powered relay, a low energy release, and a “fast-on” test receptacle for protection testing (with or without CB tripping).
5.5.12 The protection system shall ensure circuit breaker tripping as of a minimum operating current which is the rated current of the underground network to be protected. The CT settings shall be adjustable between 60 – 400/1 Amp for feeder and transformer in relay. The pickup current of relay should be adjustable as per relay specification as per the requirement at site.
5.5.13 CT shall be resin cast only, CT shall be of Protection class having duel ratio i.e. 400/1A and 60/1A. The ratio selection shall be made available on one TB on control cubicle. The ratio section chart shall be fixed permanently at suitable nearest arrangement available.
5.5.14 The class of CT shall be 5P10 for both cores and CT Burden shall be 2.5 VA.
5.5.15 CT shall be mounted on cables the mounting arrangement shall be flexible to move to & fro, up and down based on site condition of cable terminations etc. The mounting arrangement shall ensure that the CT should not reach less tan 300mm from live part of bushing. The CT mounting shall be fixed at position while dispatch such that the cable entry, the bushing terminal bolt and CT core hole are co-axial.
5.5.16 Fixing bracket to be provided for fixing CT on particular position without touching termination cores. Bolting arrangement to be provided for fixing CT on the mounting bracket.
5.5.17 In any mounting the CT shall be mounted in such a way that the secondary connection shall be accessible and visible form front side after opening cable compartment door.
5.5.18 The relays shall be self-powered suitable numerical relay with necessary elements. Please refer Specification no. ENG-HV-95 for Self power relay for RMU feeder protection. The preferable make of relay are ABB, Ashida, Schneider, Siemens make relay.
5.5.19 Breaker shall have mechanical endurance of at least 2000 operations. Relevant type test reports to be submitted along with bid.
5.5.20 Breaker operation counter should be provided and should be visible on front in horizontal alignment.
5.5.21 The circuit breaker shall be compatible for remote operation and can close (ON) and open (OFF) by remote operation in future if automated.
5.5.22 The breaker should have one series trip coil and one shunt trip coil. The shunt trip coil shall be of 24V DC along with charger and complete wiring up to trip coil through DC MCB and MCB arrangement for AC charger.
5.5.23 In control cabinet the Terminal block shall have AC input wiring provision and MCB of 6A (min.) to be provided for incoming of LT AC supply.
5.5.24 Wiring for auto-reclosing operation of CBs through relay to be done. (Reclosing shall be only done with 10 sec. delay programed in relay)
5.5.25 The relay auxiliary power, communication ports and other required ports should be wired up on the TB.
1 Incomer Load Break switch: Shall be SF6 insulated with least maintenance. Shall have at least 3 positions, Open, Close & earth with natural interlocks. Fitting of motor at site shall be possible & shall have mechanical interlock. To be provided by bidder
The electrical interlock of cable charge with earth switch is preferred.
2 Circuit Breakers: To be provided by bidder
a. With VCB interrupter and SF6 insulated bus with minimum maintenance and shall have at least 2 positions I.e. Open & Close, Manual operation & fitting of motor at site shall be possible if required.
b. In view of safety each VCB shall be assisted with feeder side disconnector having 3 positions, open-disconnected, closed, and earth (having fault making capacity) and shall be constructed in such a way that natural interlocking prevents unauthorized operations.
3 Protection Relay-Without auxiliary power & shall include 3 CT in Tee-off bushings, electronic relay, low energy release & fast on test receptacle for protection testing Complying to Specification no. ENG-HV-95 (or latest release as per tender doc.) for Self power relay for RMU feeder protection. The approved models only shall be accepted.
4 Make of self-powered Relay ABB, Ashida, Schneider, Siemens
5 Relay Model offered Bidder to mention the model from options provided in pre-bid replies in tender.
6 Opening & Closing times with relay 125 maximum
7 Current Transformer for CB compartment Shall be epoxy resin casted and mounted on cables. The CTs around the cables shall be supported on the sheet steel bracket and should be fixed with bolts. The mounting frame should be moveable up and down or to and fro but shall be fixed at co-axial position with base plat holes and bushing terminal bolts. The CT settings shall be adjustable between 60 - 400/1 Amp at terminal block. CT ratio is 60-400/1A, Burden is 2.5 VA, Class - 5P10.
8 Make of the Vacuum Interrupter a. Make
c. Type Test report no & LAB for vacuum interrupter
d. The offered make shall be same as that used in Type testing report of RMU
9 Make of CT offered
5.6 Bushings and Cable terminations
5.6.1 Bushing should be of Epoxy resin of minimum F class. Each cable compartment shall be provided with three bushings of adequate sizes to terminate the incoming and outgoing cables. The termination bolt shall be of stainless steel and M16 size with min. 30mm only for all bushings and for RMU with 630sq.mm single core cable design the 20 mm longer terminal bolt to be provided.
5.6.2 The bushings shall be conveniently located for proper bend so as to allow easy working and termination of cables. The cable termination shall be done with Heat shrinkable /Push ON termination method so that adequate clearances are maintained between phases & cable shall be held by Nylon (fire retardant material) cleat. The Sizes of incoming and outgoing cable shall be 11kV 3 Core 400 sq.mm AL cable having 91mm outer diameter.
5.6.3 Three way with two CB configuration or any RMU if mentioned for 1Cx 630 sq.mm cable; following thing to be complied,
The incomer LBS shall be suitable for 1Cx 630 sq.mm cable. Cable boots, gland plate, cable cleat, washer, bushings & terminal bolts should be suitable for 1Cx 630 sq.mm cable in LBS cable compartment. The CB compartment shall be suitable for 3Cx 400 sq.mm cable termination. The terminal bolt used in LBS compartment shall have 15mm extra length than regular bolt to accommodate the mechanical type lug having large thickness. For Incomer LBS shall be provided with nonmagnetic base plate section and suitable cable cleat for 51 mm diameter 3x1C cables.
5.6.4 Bidder should provide bimetallic washer for connection between Copper bushing stud and Aluminum Lug. The bimetallic washer shall be suitable for M16 bolt and 630A rating in all compartments with minimum thickness of 2mm and sufficiently cover the completely copper bushing stud. The bidder can alternately offer tinned copper surface of bushing then bimetallic washer not required.
5.6.5 For each terminals bolt should be provided with Cup or Belleville Washer and flat washers. (Note- The cut spring washers are not accepted)
5.6.6 The Terminal bolt shall have arrangement for fixing the cable test rod through cable boot opening. Cable boot should have opening for test rod insertion.
5.6.7 The bolt tightening torque must be written/mentioned inside each cable chamber with permanent sticker.
5.6.8 Cable boot for cable termination should be as per IS 13573-2. Boot should be easy to install & should withstand 11kV continuous voltage.
5.6.9 The cable compartment must be without any holes or gaps and properly vermin proofed before inspection.
5.6.10 The cable testing provision to be ensured in design. In case cables are to be tested with front door open, doors shall have interlocks such that doors can be opened only with earth switch in closed position & a cable test rod (to be quoted as spare) which can be fixed on the terminations/ termination bolt through boot hole to facilitate testing. Termination boots as approved by the TATA POWER-DDL should have a proper opening to facilitate the testing. The opening in boot shall be covered by means of removable protection cap.
5.6.11 All cable compartments shall have front door opening. The cable cover door shall be pad lockable and shall be Tamper and Arc proof. The circuit breaker and earth switch shall be lockable in the open or closed positions by 1 to 3 padlocks.
5.6.12 In outdoor RMU the door should have pad lock provision and cable door shall have interlock so that it shall not be opened by external forces. Also it shall not be possible to operate the load break switch / isolator or breaker from outside once door closed. This is required to prevent pilferage.
5.6.13 Locking provision of cable compartment door to be provided in case of any switch/CB is at earth position to avoid pilferage.
5.6.14 Control cabinet having terminal block (TB) shall be located at convenient accessible height and all inputs & outputs (IOs) to be wired up to the terminal block (TB).
5.6.15 The CT secondary wires and Trip coil wires shall not have any joint in-between CT and TB or relay.
5.6.16 The wiring of the relay to be done on the TB for its all terminals along with communication terminals.
5.6.17 All terminals wires shall have proper identification ferrules and the identification marking provided on TB.
5.6.18 Control cabinet shall have control cable entry arrangement on both sides of the RMU top control cabinet with proper grommet such that the opening are sealed in normal installations when not used for our door extension box arrangement to be provided any other arrangement to be explained in drawing during tender.
5.7.1 The RMU outdoor metal clad switchgear enclosure, load Break Switch, VCB, SF6 tank etc. shall be equipped with an tinned copper earth bus throughout all compartments and securely fixed along the base of the RMU with cover.
5.7.2 The extension of this earth bus shall be taken out minimum 50mm outside the enclosure on both sides for fixing of the TATA POWER-DDLs GI earth flat of 50mm width. The extension coming out of enclosure shall be properly sealed such a way to ensure vermin proofing of the cable compartment.
5.7.3 The size of tinned copper earth bus-bar should be Min.105 sq.mm inside the enclosure to withstand short time current carrying capacity as per IEC.
5.7.4 Two nos. body earthing bolts of M12X70 mm to be provide on the extended bus-bar. Bolts must be hot dipped galvanized.
5.7.5 The mother earth need to be extended up to 250mm periphery of cable entry hole so that the cable termination earthing can be connected easily to the main mother earth with 12mm bolt and washers. This arrangement need to be provided in each compartment of RMU.
5.7.6 The main tank must be connected to mother earth at least two positions with proper contact.
5.7.7 In Three way outdoor type compact design bidders should ensure the earthing from mother earth is provided inside the cable compartment for earthing of the cable terminations. That TATA POWER-DDL shall provide only two main earthing on switchgear
5.7.8 Bidder to ensured that the earth bus shall be single conductor/bus suitable for taking specified fault current and both main earthing are interconnected by earth bus and not through thank or enclosure.
5.7.9 If bolt are provided as current carrying path then the bolt material shall be brass and size shall be suitable to carry specified fault current.
1 Tinned copper Earth bus bars To be provided to prevent tampering.
2 Material & size of earth bus bar (Minimum size is 105 sq.mm) To be provided by the bidder
3 Earthing of main Cables: it shall be earthed with earth switch with S/C making capacity as per IEC 129. And closing shall be possible only when Isolator is open To be provided by bidder
4 Making of earthing operations All earth operation to be marked with yellow back ground and permanent (non-removable) in nature
5.8 Voltage indicator lamps and phase comparators
5.8.1 Each compartment of RMU shall be equipped with a fixed type voltage indicator lamps having dip ports for insertion of phase comparators or line tester to check the phase sequence or presence of charge in cable. This is to be fixed on the front face plate to indicate presence of voltage in the cables. The capacitive dividers will supply low voltage power to the indicator lamps. Three inlets can be used to check the synchronization of phases with phase comparator or other device. These devices shall be in compliance with IEC 62271-206:2011 standard. The VPIS without dip ports are not accepted.
5.8.2 There should be electrical interlock of cable presence indicator and operation of earth switch in RMU incomer cable compartment of LBS.
5.8.3 The all VPIS shall have auxiliary contact for wired in to control compartment for SCADA communication.
5.8.4 In smart RMU this shall have to be programmed for SCADA communication.
5.8.5 This feedback should be used to operate the interlock for earth switch such that earth switch shall not operate when back end of cable is live.
5.9 Front Cover
5.9.1 The front cover shall provide a clear mimic diagram that indicates the different functions. This shall be permanent in nature throughout the useful life of the RMU.
5.9.2 The position indicators shall give a true reflection of the position of the main contacts.
5.9.3 The lever operating direction shall be clearly indicated in the mimic diagram.
5.9.4 The bidder shall provide a operating sequence process on each compartment with permanent type arrangements. So that all data shall be self-explanatory.
5.9.5 The mimic plate or cover should be separate for each module/feeder of the RMU in view of safety. In case of any work to be done on mechanism of any one feeder then operation staff shall have only access to particular feeder via opening feeder mimic pate or cover plate.
5.9.6 The mimic shall have clear Words for “CLOSE/OPEN/EARTH’ at each desired place.
5.9.7 All status indicators shall be marked appropriately with permanent labels as Earth On/OFF, Disconnector/LBS On/OFF, CB On/OFF.
5.9.8 All operating ports shall have marking like spring charging provision, three position disconnector port and Shutter operator for interlocking, Operation allowed along with arrow indication and labeled as earth operation or disconnector operation.
5.9.9 For better clarity of earthing related operations shutters and ports shall be painted in yellow background such way that the persons should get clear indication that if operating in yellow region means he is performing earthing related operation.
5.9.10 The Direction of operation shall be clock wise for any close operation and anti-clock wise for any open operation of disconnector /LBS and earth switch.
5.9.11 There shall be one label for SF6 gas pressure indicator and a clear message must be fixed near pressure indicator that region of safe operation and Alert message stating ‘ If GAS pressure not OK. Do not operate any switchgear and report to OEM(name) customer care/engineer in charge’ This message should be clearly visible in front with suitable background and shall be with permanent marked.
5.9.12 For gas pressure indication a dial type manometer to be provided with will show actual pressure.
5.9.14 IN case of smart RMU the FRTU should be programmed such that in case of low GAS pressure the remote switch operation should be blocked.
5.9.15 All the other accessories and boxes shall be properly labelled with permanent marking/printing such a way that the product is self-explanatory for user. Nomenclature to be provided along with symbols.
5.9.14 IN case of smart RMU the FRTU should be programmed such that in case of low GAS pressure the remote switch operation should be blocked.
5.9.15 All the other accessories and boxes shall be properly labelled with permanent marking/printing such a way that the product is self-explanatory for user. Nomenclature to be provided along with symbols.
5.1 Fault Passage Indicators 5.10.1 Fault Passage Indicators shall be installed on the Ring Main Unit. These devices shall be, electronic devices with their own energy source and connected to Single 3 phase Split Core CTs (CBCT) for O/C. These shall be provided with bright LED s / flag Indicators, which shall be clearly visible in the day time. These shall have the following resetting facilities:
a. Manual reset
b. Resetting after a set time duration
c. Electrically reset from remote with at least 2-spare potential free contacts.
d. Resetting on restoration of LV
5.10.2 The unit shall have Short Circuit adjustable to different settings with separate Current transformer. They shall be fully field-programmable and shall have at least and 5 settings for Phase fault or over current.
5.10.3 FPI shall have min 5 setting of phase fault (OC) with 300A or 400A set as default. This shall be ensured before inspection call in each RMU.
5.10.4 It shall be possible to Test these indicators at site thru “Test” push button. The Fault Passage Indicators shall also be provided with a SCADA output contact.
5.10.5 The process of fixing the FPI shall be fixed on the wall of the incomer LBS cable compartment along with pictorial view.
5.10.6 FPI connecting wires should be properly dressed and covered in insulated sleeve and tied to the side walls with help of cable ties. If sticking type arrangement is provide then it must be with good quality permanent adhesive from reputed makes like 3M and should not come out with force of 10kN.
5.10.7 These shall confirm to the following standards:
IEC 60068-2-6, IEC 60068-2-9 : Environmental testing – For Vibration, solar radiations
IEC 60950 : Information Technology equipment – Safety
IEC 1000-2 : Electromagnetic compatibility for low-frequency conducted disturbances and signaling in public low power supply systems
IEC 1000-4 : EMC – Testing & Measurement
IEC 1000-6 : EMC- Immunity for Residential, Commercial and light industrial environments.
Remote Control of the RMU & other requirements
5.11 A. For non-motorized RMU:
a) Future provision for motorization to be kept on each feeder of each RMU.
b) For future requirement of remote operation of the RMU line switches shall be possible using motors fitted to the operating mechanism for both line switch and circuit-breaker functions as and when required. All the necessary accessories shall be supplied separately to stores based on PO placed on quotation provided in this tender.
c) The fitting of the motors to the mechanism must not in any way impede or interfere with the manual operation of the switches. An auxiliary contact to prevent motorized operation of the mechanism while the operating handle is inserted into the operating point shall also be provided.
B. For motorized RMU:
d) The motors to be fitted in LBS & CB in all RMU. The fitting of the motors to the mechanism must not in any way impede or interfere with the manual operation of the switches. An auxiliary contact to prevent motorized operation of the mechanism while the operating handle is inserted into the operating point shall also be provided.
e) The On/Off Push button of LBS and VCB shall be Illuminated type with inbuilt LED indicating presence of electrical supply.
f) Both the LBS should be wired up for auto changeover scheme. And CB to be wired up for Autorecloser Scheme/feature.
g) The CB mechanism should be suitable for auto reclosing after 10second dead time.
h) 1 No. Surge Protection Device to be provided for the relay communication ports for protection from external surge.
i) Preferred communication protocol for FRTU shall IEC-60870-5-104.
j) All Close-Open coils / auxiliary contacts shall be rated for 24 V DC. Following auxiliary contacts are essential for remote operation of RMU:
a. Aux. contact for Line Isolator (Status )
b. Aux. contact for all earthing switch (Status)
c. Aux. contact for Breaker (Status)
d. Aux. contact for FPI indication
e. Aux. contact for Protection trip (Breaker module)
f. Aux. Contact for Low Gas Pressure
k) 2 Nos. spare relay tripping NO, NC contacts to be provided. Flag Indications on RMU when tripped should be on shunt trip. A provision for physical disconnection of motor supply (like fuse) of line isolator must be provided in RMU unit itself.
l) (A flag is required for series and shunt coil actuation).
m) There should wiring provision for individual Isolator as well as breaker motor connections, which will be fitted on the RMU body itself. Also the PCB of motor should be covered by anti-tracking agent. There should be relay with timer instead of only relay, which is used in the latching circuit.
n) Signal requirement for field RTU (which shall be mounted near RTU) is attached (refer Annexure-1). The bidder shall quote the cost of field RTU (FRTU) separately with all technical details for acquisition of the signal as described in Annexure-1.
o) Group marking & labeling to be done for all TB.
C. For Smart RMU:
a) The smart RMU shall be motorized in LBS and CB also. This shall also have FRTU of TATA POWER-DDL approved make and approved models viz. Siemens, ABB, Schneider etc. (updated list shall be shared during pre-bid meeting) & shall have auxiliary PT having 1000VA burden for power supply to the FRTU, relay and DC battery charger.
b) The On/Off Push button of LBS and VCB shall be Illuminated type with inbuilt LED indicating presence of electrical supply.
c) The FRTU shall be of approved make and model along with any license key (if required) for programming and logic development at any site at any time.
d) The wiring diagram drawing should be fixed inside the compartment preferably at back side of door.
e) Any TB should not be mounded on base plate of RMU.
f) The battery terminal & other live terminals should be protected with insulating medium covering to avoid any direct accidental contact.
g) One Single pole MCB required for all DI signals and one single pole MCB required for DO positive supply.
h) 1 No. Surge Protection Device to be provided for the relay communication ports for protection from external surge.
i) Provision for taking out antenna to be kept in FRTU cabinet and space for fixing 4G modem to be kept in cabinet.
j) Both the LBS should be wired up for auto changeover scheme. And CB to be wired up for Autorecloser Scheme/feature.
k) The CB mechanism should be suitable for auto reclosing after 10second dead time.
l) Local/Remote switch & Auto/Manual Switch should be provided on the FRTU Chamber.
m) One lamp with door open sensor to be provided in FRTU cabinet and switch and socket to be provided.
n) The chamber shall have space heater at suitable location away from wires.
o) Group marking & labeling to be done for all TB.
1 Technical Details of motors For motorized and smart RMU only
a Operating Voltage 24 V DC
b Max. power rating 240 Watts
c Max current drawn 9 Amp (±10%)
d Operating time 4-8 seconds
e Power Supply Motor shall be suitable for 230 V AC & 24 V DC
2 Technical details of Auxiliary PT For smart RMU only
a. Voltage ratio- 11000/Rt3240V
b. Power frequency withstand: 28kV
c. Impulse withstand: 75kVp
d. Voltage factor 1.2 continuous and 1.9 for 8hours
e. Burdon- 1000VA
f. Accuracy- 6P
g. Type tested design (test report from OEM)
h. offered make
3 The FRTU offered model and make Please provide details
(As on date of release of document the approved models are
ABB Make FRTU with Model No – RTU540
Siemens Make FRTU with Model No – A8000,
Schneider Make FRTU with Model No – T 300 compling to FRTU specs.)
4 Aux PT HT connection should have insulation cover The busbar connecting to PT should have 11kV insulation sleeve.
5 THE HT compartment and FRTU compartment shall have separate door for safety & In view of safety the FRTU compartment and HT compartment shall have separate door.
6 The Aux. PT shall have HT fuse protection Bidder to mention make and rating of fuse offered
7 Aux PT compartment cover interlock The Aux. PT compartment cover shall have interlock so as to avoid opening when bus is charged for safety, applicable for the FRTU and PT placed having common enclosure.
8 4G modem for communication of data (Approved Make- ABB Viola as on date of release of document) 4G modem Model to be mentioned.
9 In the scope of bidder testing, commissioning and integration of signals through FRTU up to ADMS is included Bidder to comply
5.13 For all type RMU
1 Protection against theft Design of RMU shall be tamper & arc proof. Anti-vandal screws shall be provided. Cable covers shall be pad lockable. All live parts and internal parts etc. shall be covered with antitheft covers.
2 Doors Hinged doors shall be provided for outdoor type RMU. The hinges for the doors need to be riveted and shall not have any access from outside. Bolted hinges shall not be acceptable.
3 Voltage indicator box shall be fixed type-This device shall be in compliance with IEC 62271-206:2011 standard only Capacitive dividers type which will supply low voltage to power the lamps AND 3 inlets can be used to check phase sequence or presence of voltage in cable
4 Cable cleats (full circle) Nylon (Fire Retardant)
5 Bushing suitability for cable termination types Bushing should be suitable for Heat & Cold shrink terminations TATA POWER-DDL may use any type of termination.
6 Cable compartment suitability shall be Suitable for cable sizes
a. 11kV 3CX400 sq.mm having dia of 92mm in all compartment and
b. LBS suitable for 11kV 1CX630 sq.mm cable having diameter of 51mm if applicable as per requirement in tender.
7 The cable compartment All cable compartment shall be bottom entry and front opening type only
8 Size of bimetallic washer in all compartments Must be suitable for M16 bolt and bushing sizes with min. 2mm thick, not applicable if tinned copper bushing provided.
9 Height of bushing terminal from base plate in each cable compartment. The cable compartment box length for easy termination of 3Cx400sq.mm AL armoured cables. Minimum 800mm from base plate to bushing bolt center for proper termination space.
10 Fault passage indicator (SCADA compatible) One per RMU in Incomer left LBS as a part of each RMU with specified default setting. The five way RMU shall have FPI in both LBS.
11 Future motorization and SCADA Compatibility in non-motorised RMU To be provided
12 List of Type test of product To be attached for each model & type offered with test report number and date
13 Availability of spares Assurance by bidder for 25 years, list of spares as mentioned in specification to be provide along with RMU lot.
14 VPIS electric interlock The VPIS shall have electrical interlock with earth switch such that only earth when cable not charged.
15 VPIS with Aux. contact In all compartments
16 Breaker operation counter To be provided
17 LBS operation counter To be provided
18 Direction of operation a. LBS – ON/off
b. ES- Open/ close
(Close - clock wise c. CB disconnector- ON/off
Open- counter clock wise) d. CB earth switch-Open/ close
19 Auxiliary contacts (total and spare) a. LBS
b. Earth Switch
d. Series Disconnector of CB -
e. Earth switch of CB-
20 Control cable entry provision To be provided
21 DC Shunt trip coil (24V) To be provided along with series trip coil and specify DC power rating and charger/converter ratings offered
22 MCB for LT AC incomer and TB connection of all CT, Aux switches and relay wiring in separate control cabinet. To be provided in all RMU.
Separate compartment to be provided for Terminal block of all auxiliary contacts wired up.
MCB approved makes- ABB, Siemens, Scheider, EATON.
23 RMU Cable Boot/ terminal protector to be provided in each compartment for each phase. Bidder to mention offered
c. Material of boot
d. Test report and data sheet showing suitability
e. Confirmation from bidder that same boot was used during type testing of RMU.
f. Impulse voltage rating of boot
27 On the extensible bushings of each phase the 11kV insulation to be provided. Bidder to comply for the same.
28 Cable boot/ terminal protector should be suitable for 400sq.mm cables with flat lugs square end 400 sq.mm, Bidder to comply for the same.
29 All auxiliary contact, relay LT Supply contact, relay DI/DO contact, provision for communication device in a control compartment. Separate compartment to be provided for Terminal block of all auxiliary contacts wired up.
30 In each cable compartment each bushing shall have temperature sensors. The temperature data should be shown on one common display unit and shall be communicated to SCADA in motorised and Smart RMU.
31 Total height of the indoor RMU should be <1900mm Bidder to accommodate without compromising other requirements.
32 Terminal bolt material and bolt length & washers offered The terminal bolt shall be M16 and of stainless steel.
The offered length to be mentioned along with washer details.
All paint shall be applied on clean dry surfaces under suitable atmospheric conditions by seven tank process and powder coating. The overall paint thickness shall not be less than 70 microns.
The paint shall not scale off or crinkle or be removed by abrasion during normal handling.
The enclosure of the RMU shall be painted with shade light Grey, i.e. RAL 7032. If any damage observed after delivery same need to be touch-up painted after delivery at site.
5.14 Control wiring All wiring in the control cabinet shall be carried out with 1100V grade single core multi strand flexible copper conductor with HRPVC insulation without any joints in between runs and shall be flame retardant, vermin and rodent proof.
1. CT circuit- 2.5 sq.mm flexible copper.
2. Earth circuit – 2.5 sq.mm flexible copper.
3. AC control circuit- 1.5 sq.mm flexible copper.
4. DC control circuit-1.5 sq.mm flexible copper.
5. SCADA circuit- 1.5 sq.mm flexible copper.
6. Wire identification -Tubular printed ferrules
5.15 SLD and configuration
The SLD and the offered configurations for particular manufacturer cannot be changed without prior notice and approval from Tata Power-DDL.
Tata Power-DDL reserve the right to accept the change or reject the same based on operation ease and safety features based on the product evaluation Safety being utmost concern hence same need to be taken care in any offered designs.
6 Name Plate & Marking: - All the components and operating devices of the RMU shall be provided with durable and legible stainless steel (or anodised AL) nameplates containing all technical parameters. Name plates shall be suitably embossed with” PO no. with date”, “PROPERTY OF Tata Power-DDL, DELHI’ & “CODE NUMBER” along with the following information. A Danger plate of appropriate size shall also be provided on the enclosure. (The drawing of name plate shall contain following details)
a) Manufacturer’s Name
d) Month and year of supply
e) PO Number and date
f) Rated Voltage
g) Rated current
h) System Frequency
i) Rated Short time withstand current
j) Rated Impulse withstand Voltage
k) Degree of Protection
l) Mechanical duty of CB and LBS
m) Duty cycle of CB
n) Internal ARC test category
o) Year and month of manufacture.
q) SF6 gas filling pressure in ‘bar’
r) Property of ‘TATA POWER- DDL’
Also the customer care centre number and mail address to be mentioned in the name plate at bottom.
The name plate data should be printed in QR code with name plate details, purchase details, operating manual, SOP, troubleshooting techniques, warranty details and customer care contact details with complaint registering mechanism and fixed on the front cover or suitable place.
7 Tests for RMU All the Routine and acceptance tests shall be carried out in accordance with the relevant IS/IEC standards. All routine/acceptance tests shall be witnessed by the purchaser/his authorized representative. All the components within the RMU enclosure shall have been tested for Routine/acceptance and Type tests as per the relevant standards. All Type tests as per latest IS / IEC shall have been carried out on the RMU as a whole as per relevant IS/IEC. Following tests shall be necessarily conducted on the equipment and its components as specified in IEC 62271-200:
Note- In case of any conflict on any technical particular in the specification, the stricter requirement mentioned in the relevant standard shall be valid.
7.1 TYPE TESTS Sr. No. Type Tests stipulated as per Tender Spec. Applicable standard Acceptance Clause as per IS / IEC
1 PF withstand voltage test & Lightning Impulse voltage withstand test for Switches IEC62271-103 Cl 6.2 0f IEC62271-103, Cl 7.2.7.2 & 7.2.7.3 of IEC62271-1
2 PF withstand voltage test & Lightning Impulse voltage withstand test for CB IEC 62271-200 Cl 6.2.6.1 & 6.2.6.2-IEC 62271-200
3 Measurement of contact resistance & Temperature rise test LBS & CB combined unit (if individual then two separate reports required) IEC 62271-200 Cl 6.4 & Cl 6.5 of IEC 62271-200
4 Short Time current and Peak current withstand tests Main Circuit IEC 62271-200 Cl 6.6 a & b -IEC 62271-200
5 Short Time current and Peak current withstand tests Earthing Circuit IEC 62271-200 Cl 6.6 a & b -IEC 62271-200
6 Short Circuit Breaking current tests LBS IEC 62271-103 Cl 6.101, Table3 of IEC 62271-103
7 Short Circuit Making current test on LBS IEC 62271-103 Cl 6.101.1.2, Table3 of IEC 62271-103
8 Short Circuit Making test on Earth Switch IEC 62271-102 Cl 6.101 of IEC 62271-102
9 Short circuit making & Breaking tests on CB – three phase fault IEC 62271-100 Cl 6.112..1 of IEC 62271-100
10 Single Phase test on CB IEC 62271-100 Cl 6.108 of IEC 62271-100
11 Double Erath Fault test on CB IEC 62271-100 Cl 6.108 of IEC 62271-100
12 Mechanical operation tests on LBS IEC 62271-200 Cl 6.102.2 - IEC62271-200
13 Mechanical operation tests on CB IEC 62271-200 Cl 6.102.2 - IEC62271-200
14 Mechanical Endurance tests on LBS IEC 62271-103 Cl 6.102.2. - IEC 62271-103
15 Mechanical Endurance tests on CB IEC 62271-100 Cl 6.101.2.4 of IEC 62271-100
16 Mechanical Endurance tests on DS IEC 62271-102 Cl 7.102.3 of IEC 62271-102
17 Partial Discharge test on CB & LBS IEC 62271-200 Annex BB , Procedure B of IEC 62271-200
18 Pressure withstand test of gas filled compartment/Tank IEC 62271-200 Cl 6.103.1 of IEC62271-200
19 IP67 of Gas compartment/Tank IEC 62271-200 Cl 6.7.1 of IEC62271-200
20 IP54 for outdoor RMU IEC 62271-200 & IEC- 60529 Cl 6.7.1 of IEC62271-200
21 IAC on Cable Compartment IEC 62271-200 Cl 6.106 IEC62271-200
22 IAC on Gas Compartment IEC 62271-200 Cl 6.106 IEC62271-200
23 Cable charging current breaking test IEC 62271-100 Cl 6.102, 6.105 of IEC 62271-100
24 Capacitive current switching test IEC 62271-100 Cl 6.111 of IEC 62271-100
Note: The bidder can submit the test report with combination of above listed tests. The test of CB & LBS to be done on combined unit if bidder submits individual unit CB/LBS tests then both units test detailed test reports are to be submitted.
7.2 ROUTINE TESTS Following routine tests are to be done on 100% of the lot quantity
1. Power Frequency Withstand Test.
2. Dimensional & Visual Checks
3. Operational & Interlock Tests of breaker & isolator switches
4. Helium leakage detection test in vacuum chamber
5. SF-6 leakage test in vacuum chamber
6. Sniffer Leak Detection Test on each and every sealed tank.
7. HV withstand test across isolator distance.
8. HV withstand test of control and auxiliary circuits.
9. Voltage Indication Tests on VPIS
10. Contact Resistance Test
For other components, as per applicability, the RTC as per relevant IS/IEC from Original Equipment manufacturer (OEM) shall be required:
2. Routine test report of the Relay
5. Auxiliary PT
7.3 ACCEPTANCE The test mentioned in ITP attached as annexure-2 to this document shall be carried out as acceptance test on random samples. Minimum 10% units (or minimum 2 RMU if lot size is small) of the lot shall be selected for acceptance test shall be selected for testing from each offered lot.
TESTS Sr. No. Tests details Applicable standard Acceptance Criteria
1 PF withstand voltage test on LBS and CB combined with switches closed position IEC62271-103 & IEC 62271-200 Cl 6.2 0f IEC62271-103, Cl 7.2.7.2 & 7.2.7.3 of IEC62271-1 Cl 6.2.6.1 & 6.2.6.2-IEC 62271-200
Should withstand 28kV for 1minute
2 HV withstand test across isolator distance with opened contact of VCB IEC 62271-200 Should withstand 28kV for 1minute
3 Voltage Indication Tests on VPIS - VPIS indication should lit up when voltage applied in all phases
4 Measurement of contact resistance on LBS & CB combined with all switches in closed condition IEC 62271-200 Cl 6.4 & Cl 6.5 of IEC 62271-200
Total resistance limit shall be maximum 350micro ohm with busbar & switches closed.
5 Dimensional & Visual Checks - As per approved drawing and technical compliance document for tender
6 Operational & Interlock Tests of breaker & isolator switches As per specification All interlock shall operate without fail in any operation
7 Leak Detection Test at bushing terminals after RMU assembly IEC 62271-1 clause 8.5 For gas-filled systems tested in factory, the probing test using a sniffing device to be done. The sensitivity of the sniffing device shall be at least 10-8 Pa × m3/s.
8 HV withstand test of control and auxiliary circuits of motorised and Smart RMU Should withstand 2kV for one minute
9 Insulation resistance test With open contacts and closed contacts of switches. Should be in Giga-ohms.
10 Other components, as per applicability, the RTC as per relevant IS/IEC from Original Equipment manufacturer (OEM) to be shared for OEM reports as per IS and IEC.
d. Auxiliary PT
11 For smart RMU compatibility & data integration check after operations, alarms and reset check All desired functionality shall be checked along with auto-reclosing and auto-changeover. The relay data and FRTU configuration shall be verified bidder to keep ready with all details
12 Relay testing- Relay testing should be done with primary injection kit on installed relay. Total tripping time with relay & without relay (Without relay shall be done at trip coil directly) timing shall be within specified in specification.
Bidder should have all the requisite testing equipment’s to carry out routine and acceptance test mentioned in ITP and following set up to be arranged for RMU relay testing:
a. Facility for primary current injection up to 1000amp.
b. Facility to check total trip timing of breaker along with breaker main contacts through primary current injection
8 Type Test Certificate
The Bidder shall furnish the type test certificates of the 11KV RMU of same design as offered in bid for the tests as mentioned above as per the corresponding standards. All the tests shall be conducted at CPRI/ERDA or any other International Laboratory as per the relevant standards of IS and IEC. Type tests shall have been conducted in certified Test laboratories during the period not exceeding 5 years from the date of opening the bid. In the event of any discrepancy in the test reports, i.e. any test report not acceptable or any/all type tests (including additional type tests, if any) not carried out, same shall be carried out without any cost implication to TATA POWER-DDL.
Bids without all type test reports shall stand disqualified.
9 Pre-Dispatch Inspection
Equipment shall be subject to inspection by a duly authorized representative of the TATA POWER-DDL. Inspection may be made at any stage of manufacture at the option of the purchaser and the equipment if found unsatisfactory as to workmanship or material is liable to rejection. Supplier shall grant free access to the places of manufacture to TATA POWER-DDL’s representatives at all times when the work is in progress. Inspection by the TATA POWER-DDL or it’s authorized representatives shall not relieve the supplier of his obligation of furnishing equipment in accordance with the specifications.
The first time supplies (new bidder or new models or change of design from previous supplies) shall be applicable for prototype inspection after CAT-B drawing approval and before mass manufacturing. In prototype manufacturing bidder have to make one or two sample RMU for inspection after CAT-B approval of drawings after award of RC/PO.
Material shall be dispatched after specific MDCC (Material Dispatch Clearance Certificate) is issued by TATA POWER-DDL. Following documents shall be sent along with material
a) Routine Test reports
b) MDCC issued by TATA POWER-DDL
c) Invoice in duplicate
d) Packing list
f) Delivery Challen
g) Installation and maintenance Manual soft copy for FPI, Relay, RMU
h) Other Documents (as applicable)
10 Inspection After Receipt At Store
The material received at TATA POWER-DDL Store will be inspected for acceptance and shall be liable for rejection if found different from the reports of the pre-dispatch inspection.
If any deviation or anomaly observed at this stage same need to be rectified by bidder at bidders own cost at earliest.
1. Bidder shall stand guarantee towards design, materials, workmanship & quality of process / manufacturing of items under this contract for due and intended performance of the same, as an integrated product delivered under this contract. In the event any defect is found by the Purchaser up to a period of at least 48 months from the date of commissioning or 60 months from the date of last supplies made under the contract whichever is earlier, Bidder shall be liable to undertake to replace/rectify such defects at its own costs, within mutually agreed time frame, and to the entire satisfaction of the Purchaser, failing which the Purchaser will be at liberty to get it replaced/rectified at Bidder’s risks and costs and recover all such expenses plus the Purchaser’s own charges (@ 20% of expenses incurred), from the Bidder or from the “ Security cum Performance Deposit” as the case may be.
2. In case of GP failure, BA shall report at site within 48 hours from intimation and arrange for rectification of fault within a mutually agreed time. In case rectification at site is not possible then alternative arrangement (replacement) to be made by BA within 15 days of intimation of failure. The SLA shall be as per attached.
3. Bidder shall further be responsible for ‘free replacement’ for another period of THREE years from the end of the guarantee period for any ‘Latent Defects’ if noticed and reported by the Purchaser.
12 Packing Bidder shall ensure that all equipment covered by this specification shall be prepared for rail/road transport (local equipment) and be packed in such a manner as to protect it from damage in transit. The packing should be in such manner that during storage the RMU and its components should not be damaged. No single use plastic to be used in packing material. Packing should be done with environment friendly recyclable materials.
13 Tender Sample
Not applicable. Bidders to mention offered model number along with GA drawing during tender for each variant.
The bidder shall arrange to provide the installation and operating training at TATA POWER-DDL offices as and when required for better installation and usage of the product.
It is preferred that the service engineer present during installation shall arranged to provide the operation training of RMU to the staff during installation and inform about the critical points. In addition to this for new bidder, new product or change in design the bidder has to provide minimum 12 training sessions one at each district office of TATA POWER-DDL.
In addition to above bidder to share Digital /Video based training module for safe operation of RMU in pen drive.
15 Quality Control
The bidder shall submit with the offer, assurance plan indicating the various stages of inspection, the tests and checks which will be carried out on the material of construction, components during manufacture and after finishing, bought out items and fully assembled component and equipment including drives. As part of the plan, a schedule for stage and final inspection within the parameters of the delivery schedule shall be furnished. The Purchaser's or its nominated representative engineer shall have free access to the manufacturer/sub-supplier's works to carry out inspections.
To ensure proper operation of RMU the bidder shall provide onsite training of TATA POWER-DDL teams as and when required. To ensure quality of installations bidder shall provide supervision support during impartation.
16 Testing Facilities Bidder shall have adequate in house testing facilities for carrying out all routine tests, acceptance tests and special test as per this document and accordance to relevant International / Indian standards as mentioned.
The bidder shall have in-house helium gas leakage detection system and all RMU main tank shall be checked for leakages.
17 MANUFACT-URING ACTIVITIES 1. The successful bidder will have to submit (after placement of RC) technical compliance document and drawing of cable as per RC line items for getting approval before mass manufacturing.
2. Manufacturing mass quantity to start only after getting CAT-A approved drawings or as per intimation from Tata POWER-DDL.
3. The first time supplies (new bidder or new models or change of design from previous supplies) shall be applicable for prototype inspection after CAT-B drawing approval before mass manufacturing. In prototype manufacturing bidder have to make one or two sample RMU for inspection after CAT-B approval of drawings.
18 Spares, Accessories & Special Tools / Gauges Bidder shall provide a list of recommended spares with quantity and unit prices for 5 years of operation after commissioning.
TATA POWER-DDL may order all or any of the spare parts listed at the time of contract award and the spare parts so ordered shall be supplied as part of the definite works. TATA POWER-DDL may order additional spares at any time during the contract period at the rates stated in the Contract Document.
Bidder shall give an assurance that spare parts and consumable items will continue to be available through the life of the equipment which shall be 25 years minimum. However, the TATA POWER-DDL shall be intimated with a minimum of 12 month notice in the event that the Bidder or any sub-vendor plans to discontinue manufacturing of any component used in this equipment.
Any spare apparatus, parts or tools shall be subject to the same specification, tests and conditions as similar material supplied under the Contract. They shall be strictly interchangeable and suitable for use in place of the corresponding parts supplied with the plant and must be suitably marked and numbered for identification.
Bidder has to provide quotation unit rate for below mentioned spare of RMU
SL. No. Name of Spare Parts Required spares with above 100 No. of RMU Required spares with above 30 No. up to 100 No. of RMU Required spares up to 30 No. of RMU
1 Breaker Mechanism 4 No’s 3 No’s 2 No’s
2 Isolator Mechanism 4 No’s 3 No’s 2 No’s
3 Trip Coil 5 No’s 3 No’s 2 No’s
4 Relay 5 No’s 3 No’s 2 No’s
5 CT (All types) 3 Sets (1 Set = 3 Nos.) 2 Set 1 Set
6 Bolt (For cable connection) 5 Sets (1 Set = 3 Nos.) 3 Set 2 Set
7 "L" Key (All Size) 2 Sets 1 Set 1 Set
8 Operating Handle 1 No. 1 No. 1 No.
9 Cable Bushing (If replaceable) 15 (5 Set) 9 (3 Set) NA
10 VPIs 10 No’s 5 NA
11 FPI 10 No’s 5 NA
12 Push Button (ON & OFF Both) 10 (5 On & 5 Off) 6 NA
13 Manometer 5 No’s 3 NA
14 Washer (S.S.) 20 No’s 15 NA
15 Anti vandal Screw (All Size) 20 No’s 15 NA
16 Cable Boot 5 sets 3 Sets NA
17 Reducer M16 to M12 12 3 NA
18 M12 to M16 conducting Bolt (If M12 bushing supplied in past) 12 3 NA
19 The nonmagnetic base plate arrangement for 3x 1Cx 630 mm cable 10 5 NA
20 HDPE cable cleat arrangement for 3x 1Cx 630 mm cable in incomer LBS included 10 5 NA
21 The extensibility connection kit – indoor RMU 10 10 NA
22 The extensibility connection kit – Out door RMU 10 10 NA
19 Drawings & Documents Following drawings and documents shall be prepared based on TATA POWER-DDL specifications and statutory requirements and shall be submitted with the bid:
a) Completely filled in Technical Particulars
b) Any deviation sheet or No deviation
c) General description of the equipment and all components including brochures.
d) General arrangement for RMU
e) SLD of each feeder
f) Arc path drawing of all variants offered
g) Foundation plan
h) Experience List
i) All set of Type test certificates & detailed reports for offered design of each variant
Drawings / documents to be submitted for approval after the award of the contract are as under:
Sl. No. Description For Approval For Review/ Information Final Submission
1 General Technical Particulars (GTP) Ö Ö
2 General Arrangement drawings Ö Ö
3 Schematic Diagram of MIMIC with ON/OFF and all front labelling Ö Ö
4 Bill of materials Ö Ö
5 Arc path drawing for each variant Ö Ö Ö
6 SLD of complete RMU and feeders Ö Ö Ö
7 Control wiring diagram and arrangement in control cubicle Ö Ö Ö
8 Cable compartment internal dimension drawing and one drawing stating standard boots arrangement and cable earthing arrangement with cable Ö Ö Ö
9 CT mounting arrangement drawing with details of fixing and frame movement etc. Ö Ö
10 Foundation Plan/Drawing Ö Ö Ö
11 Installation & Maintenance Instructions and manual Ö
12 QA & QC Plan Ö Ö
13 Test Certificates Ö Ö Ö
All the documents & drawings shall be in English language.
After the receipt of the order, the successful bidder will be required to furnish all detailed drawings of components for TATA POWER-DDL approval.
Instruction Manuals: Bidder shall furnish softcopies and one hard copy manuals of RMU, FPI, Relay (In English language) covering erection and maintenance instructions and all relevant information and drawings pertaining to the main equipment as well as auxiliary devices.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Tender Documents_Annexure-3 ENG-HV-2011.pdf
Tender Document • 0.58 MB
Tender Documents_Clause wise complaince sheet_RMU.xlsx
Tender Document • 0.07 MB
Tender Documents_ENG-GEN-146-01 Specification of FRTU .pdf
Tender Document • 0.95 MB
Tender Documents_ENG-HV-2011.pdf
Tender Document • 1.68 MB
Tender Documents_ePayment_Mandat form.docx
Tender Document • 0.02 MB
Tender Documents_GCC-Supply.pdf
Tender Document • 1.17 MB
Tender Documents_Response to pre-bid queries.pdf
Tender Document • 0.46 MB
Tender Documents_Vendor Appraisal Form- Supply.pdf
Tender Document • 0.21 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .