CWE NAGPUR
Commander Works Engineers Bldg No. P-9, Sitabuldi Fort, Nagpur-440 001 Pin-900419, C/o 56 APO
REPAIR AND MAINTENANCE OF DG SET , AMF PANAL AND CONNECTED ITEMS AT KAMPTEE AND NAGPUR AREA UNDER GE KAMPTEE
2023_MES_573300_1
84753/E8
Open Tender
Civil Works
Item Rate
120 days
GE KAMPTEE
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
Yes
GE KAMPTEE
₹30,000
1 Mar 2023
6 Jan 2023
8 Feb 2023
6 Jan 2023
7 Feb 2023
21 Jan 2023
6 Jan 2023 - 18 Jan 2023
Amount
Material and labour for servicing of 125 KVA DG Set (Installed at MH OT of make Kirloskar) including greasing of nipples, draining of unserviceable engine oil by unscrewing drain plug , cap, and other moving parts of engine and alternator as per manufacturer’s instructions:- (a) Opening, cleaning and re-connecting of battery terminals and apply petroleum jelly (b) Checking of coupling and replace it if required. (c) Checking of engine oil leakage if any by replacing gasket, tightening of all nuts and bolts etc, (d) Removing of radiator completely and cleaning as per manufacturer instructions and refitting the same. (e) Check the tightness of fan belts if found loose to be tightened. (g) Draining of water accumulated in filter or separate in fuel line including complete fuel tank drying and cleaning re-filling of drain out fuel, (h) Checking of all electric connections in AMF & LT panel board , switches and contactors etc, (j) Checking of free rotation of fly wheel/ shaft of generator and testing to the satisfaction of Engr-in-Charge complete all as specified and directed. Make:- Kirloskar NOTE:- Engine oil shall be measured and paid separately in respective item.
All as per item Sl.No 1.00 herein-before , but DG Set of 200 KVA installed at MSL Power house, Trg shed Msl, MH Kamptee, treated water pump house, Radial well complete all as specified and directed. Make :- Kirloskar/ KOEL
All as per item Sl.No 1.00 herein-before , but DG Set of 100 KVA installed at Record Office GRC, Auditorium GRC, Station Exchange , complete all as specified and directed. Make :- Ashok leyland/ Mahindra/ KOEL
All as per item Sl.No 1.00 herein-before , but DG Set of 62.5 to 63KVA Installed at Shivaji Pump House ,APS Tech Block, Tele Exchange Msl, Msl Gp pump house, Fort area Naagpur , complete all as specified and directed Make :- Kirloskar / KOEL
All as per item Sl.No 1.00 herein-before , but DG Set upto 30 to 40 KVA installed at APS record, NCC OTA , STP , HQ UMG , complete all as specified and directed. Make :- Kirloskar / KOEL
All as per item No 1.00 herein-before , but DG Set of cap 20 KVA to 25 KVA installed at 'R' Line Pump House, 'T' Line pump house, 8 Major pump house Nagpur, Signal centre GRC complete all as specified and directed. Make :- Kirloskar / Kerala Electricals Notes for Item No 01 to 6 above:- (a) Rate quoted by Contractor shall deemed to be included following provisions:- (b) Sufficient/required man power employed for the servicing purpose, T&P used and other petty items such as cotton waste kerosene oil, nuts and bolts etc and any ther minor items. (c) replacement of spares will be measured and paid separately as supply only under respective items. (d) If any defect observed during defect liability period the same shall be rectified by contractor without any extra cost to the Govt. The Contractor shall visit each DG Set prior quoting the rate to know the current status of respective DG Sets. No claim what so ever on this account shall be entertained whether he visit the DG set or not.
Supply and fix in replacement of automatic voltage regulator (AVR) suitable for the DG Set 20 to 125 KVA , complete all as specified and directed. Make :- Kirloskar /Mahindra/ Ashok leyland
Supply and fix in replacement automatic voltage regulator (AVR) suitable for the DG Set 200 KVA , complete all as specified and directed. Make :- Kirloskar /Mahindra/ Ashok leyland
Supply and fix in replacement MNX 185 power contactor for DG set, standard coil voltage 110V,220V,240Vand 415 V,50 HZ ,complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement MCX 03 contactor 32 Amp 4 pole 240 V suitable for DG set complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement MCX 43 contactor 400 Amp, 240V suitable for DG set 200 KVA, complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement MCX 13 contactor 80 Amp 4 pole, 240V suitable for DG set 200 KVA, complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement MCX32 power contactor for DG for DG set, standard coil voltage 220V,240V and 415 V, 50 HZ complete all as specified and directed. Make - L&T/ ABB/ Legrand
Supply and fix in replacement unserviceable contactor coil of power contactor MNX 300 voltage , 240V at 50 Hz complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement unserviceable contactor coil of power contactor MNX 95 voltage, 240V at 50 Hz complete all as specified and directed. Make :- L&T/ABB/Legrand
Supply and fix in replacement unserviceable contactor coil of power contactor MNX 185 voltage, 240V at 50 Hz complete all as specified and directed. Make :- L&T/ABB/Legrand
Material and labour for taking down old unserviceable Alternator from DG set 25 KVA to 62.5 KVA, for rewinding of starter, armature and refixed to the existing position after rewinding, including replacement of suitable size bearing complete all as specified and directed. Note : Material and labour for rewinding with existing size copper wire will be paid under separate item only.
Material and labour for taking down old unserviceable Alternator from DG set 125 KVA to 200 KVA for rewinding of starter, armature and refixed to the existing position after rewinding, including replacement of suitable size bearing complete all as specified and directed. Note : Material and labour for rewinding with existing size copper wire will be paid under separate item only.
Material and labour for rewinding of starter ,armature with copper wire of same gauge and size of 25 KVA to 200 KVA, DG Set, complete all as specified and directed.
Material and labour for taking down unserviceable self starter from DG set of cap 20 to 125 KVA 12V, for complete replacement and refixed to the existing position after rewinding, including replacement of suitable size bearing complete all as specified and directed. Note : Material and labour for rewinding with existing size copper wire will be paid under separate item only
Material and labour for taking down unserviceable self starter from DG set of capacity 200 KVA 12V, for complete replacement and refixed to the existing position after rewinding, including replacement of suitable size bearing , complete all as specified and directed.
Material and lablour for taking down radiator of DG set of capacity from 20 to 62.5 KVA at site and cleaning its fans externally by air pressure and washed internally by cleaning agent carefully and fiixing its original position after checking any leakage, complete all as specified and directed.
Material and lablour for taking down radiator of DG set of capacity from above 62.5 to 200 KVA at site and cleaning its fans externally by air pressure and washed internally by cleaning agent carefully and fiixing its original position after checking any leakage , complete all as specified and directed.
Supply and fix in replacement lubricant oil filter element with washer suitable for DG set of capacity from 30 KVA to 125 KVA , complete all as specified and directed. Make:- Kirloskar
Supply and fix in replacement lubricant oil filter element with washer suitable for DG set of capacity from 200 KVA , complete all as specified and directed. Make:- Kirloskar
Supply and fix in replacement lubricant oil filter element with washer suitable for DG set of capacity from 20 KVA to 30 KVA , complete all as specified and directed. Make:- Kirloskar
Material and labour for radiator coolant concentrate, complete all as specified and directed.
Material and labour in replacement fuel filter element with 'O' ring suitable for DG Sets 100 to 200 KVA, complete all as specified and directed. Make:- Kirloskar, Mahindra, Ashok Leyland
All as per item Sl.No 28.00 herein-before but for DG Set of capacity 20 to 63 KVA complete all as specified and directed. Make:- Kirloskar, Mahindra, Ashok Leyland, Cummins
Material and labour for lubricant oil 15W complete all as specified and directed. Make : Castrol , HP or equivalent as approved by GE.
Supply and fix battery connection copper lead with 200 Amps rated capacity complete all as specified and directed. Makes:- As approved by GE.
Material and labour for distilled water in supplier's packing complete all as specified and directed.
Supply and fix battery terminals complete all as specified and directed. Makes:- As approved by GE.
Material and Labour for rubber hose pipe complete of suitable sizes for DG sets 20 to 63 KVA , complete all as specified and directed.
Material and Labour for rubber hose pipe complete of suitable sizes for DG sets 100 to 200 KVA , complete all as specified and directed.
Material and labour for fan belt as per sampler for dynamo/ alternator of suitable for DG Set 200 KVA , complete all as specified and directed. Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
All as per item Sl.No 36.00 herein-before but suitable for DG set 100 KVA complete all as specified and directed Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
All as per item Sl.No 36.00 herein-before but suitable for DG set 63 KVA complete all as specified and directed Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
All as per item Sl.No 36.00 herein-before but suitable for DG set 40 KVA complete all as specified and directed Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
All as per item Sl.No 36.00 herein-before but suitable for DG set 20 KVA to 30 KVA complete all as specified and directed Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
All as per item Sl.No 36.00 herein-before but suitable for DG set 20 KVA complete all as specified and directed Make: Kirloskar/Cummins/Mahindra/Ashok Leyland
Material and labour for fuel pipe heavy duty, suitable size for the DG Set 20 to 200 KVA complete all as specified and directed Make:- Kirloskar/Mahindra/cummins
Material and labour for air filter complete of suitable sizes for DG Set 200 KVA, complete all as specified and directed.
All as per item Sl.No 43.00 herein-before but, for DG Set 125 KVA complete all as specified and directed.
All as per item Sl.No 43.00 herein-before but, for DG Set 30 to 100 KVA complete all as specified and directed.
All as per item No 43.00 above but for DG Set 20KVA to 25 KVA complete all as specified and directed.
Supply and fix in replacement of steel hinges suitable for DG set doors complete all as specified and directed. Make : Kirloskar or equivalent as approved by GE.
Supply and fix in replacement, indicator lamp LED type complete all as specified and directed.
Supply and fix in replacement of ammeter complete all as specified and directed.
Material and labour for replacement of digital Meter indicating hrs run ,PF, Voltage, Ampers, Energy consumed, complete all as specified and directed. Make : As approved by GE
Material and labour for replacement of radiator cap with rubber gasket complete all as specified and directed.
Supply and fix in replacement of unserviceable canopy door lock of suitable size , complete all as specified and directed. Make : As approved by GE.
Supply and fix for broken door glases of DG set canopy complete all as specified and directed.
Material and labour for replacement of Ignition/ Starter Switch with key complete all as specified and directed.
Material and labour for replacement of water temperature meter gauge complete all as specified and directed.
Material and labour for replacement of oil pressure gauge meter complete all as specified and directed.
Material and labour for replacement of fuel tank cap with locking arrangement, complete all as specified and directed. Make : As approved by GE.
Supply and fix in replacement onload changeover switch 160 A,415 V open execution suitable for fixing in existing position of LT panel complete all as specified and directed Make - L&T/Legrand/Havells or equivalent as approved by GE.
Supply and fix in replacement of controller display suitabe for DG set complete with all accessories complete all as specified and directed. Make & Model :- KG934 of Kirloskar or equivalent in L&T/ABB
Supply and fix in replacement of MCCB 200 Amp, 415 V, 50 HZ, breaking Capacity 25 KA with thermal magnetic release, complete all as specified and directed.
Supply and fix in replacement of relay 12 V for AMF panel complete all as specified and directed. Make - L&T/ABB/Legrand.
Supply and fix in replacement of battery charger 12 V (SMPS) for DG set complete all as specified and directed.
Supply and fix in replacemet of voltage stablizer 0.5 KVA suitable for DG set with all accessories complete all as specified and directed. Make - L&T/ABB/Legrand.
Supply and fix in replacemet of panel box lock complete all as specified and directed
Supply and fix in replacement of 24 V play relay suitable for DG set complete all as specified and directed.
Supply and fix in replacement of NONC suitable for DG set complete all as specified and directed.
Supply and fix in replacement of battery charger 24 V ( SMPS) complete all as specified and directed.
Supply and fix in replacement VMR for AMF panel complete all as specified and directed.
Supply and fix in replacement of Isolator 63 Amp 4 pole complete all as specified and directed.
Supply and fix in replacemet CT suitable for DG set 62.5 KVA complete all as specified and directed.
Supply and fix in replacement of relays 24V for AMF panel complete with all accessories complete all as specified and directed.
Supply and fix in replacemet of HRC fuse 100 Amp complete all as specified and directed.
Material and labour for spray painting to existing LT Panel of any capacity with two coats of synthetic enamel paint complete including dusting, cleaning of existing dust before applying synthetic enamel paint and writing feeder name with synthetic enamel paint complete all as specified and directed.
Material and labour for AMF panel rewiring with existing size, copper wire complete all as specified and directed.
Material and labour for Earthing complete with galvanized steel earth plate electrode 600x600x6mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of earth plate not less than 1.5m below ground level connected to galvanized iron earth strip 32 x 6 mm by means of bolts, nuts, check nuts, washers of galvanized iron and connected to main switch/control board upto 7.5m away from the earth electrode including excavation earth work, PCC chamber, RCC cover slab char coal, watering pipe, wire mesh lugs, earth lead protection pipe 15mm bore, light grade 7.5m long as applicable and as per plate No. 3 of SSR 2009 ,complete including demolition of existing earthing all as specified and directed. (a) Excavation and earth work in any type of soil. (b) Drilling of holes in electrode (c) PCC pit in cement concrete (1:2:4) type B-1 (d) 40 mm thick Pre-cast RCC cover with suitable handle. (e) Funnel with watering pipe of GI 20 mm nominal bore ,medium grade & copper lug etc. (f) 50 mm nominal bore medium grade GI protection pipe 7.50 m long for protection of earthing lead. (g) Requisite quantity of charcoal and common salt. (h) Connection to earthing test point and testing on completion.
Supply and fixing in repair retro reflective boards in shape of rectangle of size 1.0M x1.4M made out of 2 mm thick stainless steel both side bounded/pasted with high prismatic (iv) sheet manufactured by avery dennison or 3 M with desired letters/logos designed as directed the board shall be supplied with and including stainless steel frame made out of 25 mm dia pipe in frame around duly welded with and including stainless steel sheet and stainless steel posts of 38 mm dia and full length of 2.20 m one side and 2.8 m other side complete all as specified and directed. Note : (i) Rate for fixing of boards with PCC 1:2:4 type B2 filling of size 45x45x60 cm to be included in unit rate. (ii) The board should be written description as direction given by Engineer-in-Charge
NOTE :- SCHEDULE OF CREDIT (Amount shall be deducted offline from the total quoted amount to workout the net contract sum to be considered for acceptance.) [(-) Rs.70988.00/- ]
Paragon Electrotechnics
Asha Enterprises
Bidder Name
Paragon Electrotechnics
Chinmaya Enteprises
Asha Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .