Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹18.7 LAccepted-AOC | ₹18.7 L Quoted ₹20.0 L | L1 | Accepted-AOC Being L1 and found in order |
| 2 | L2₹21.4 L+₹1.4 L (7.00%)Rejected-AOC | ₹21.4 L+₹1.4 L (7.00%) | L2 | Rejected-AOC Not being L1 |
| 3 | Rejected-Technical | - | - | Rejected-Technical Being No in WLR |
| 4 | Rejected-Technical | - | - | Rejected-Technical Being not eligible in req cat |
Tender Value
₹29 L
EMD Value
₹58,000
Closing Date
6 Mar 2020, 6:00 pmClosed
HQ 135 WE
HQ 135 WE C/O 56 APO
REPAIR/ MAINTENANCE OF 33/11 KV POWER TRANSFORMER AND 33 KV OVERHEAD LINE AND REPAIR/MAINT OF HT XLPE UG CABLE HT FEEDER PILLAR BOX AND CONNECTED WORKS UNDER GE(NORTH) AKHNOOR
2020_MES_322666_1
CWE/JA-26/2019-20
Open Tender
Civil Works
Item Rate
180 days
AKHNOOR
Class D Cat b ii
7 documents required · 7 mandatory
₹500
GE NORTH AKHNOOR C/O 56 APO
₹58,000
19 Jun 2020
7 Feb 2020
9 Mar 2020
7 Feb 2020
6 Mar 2020
22 Feb 2020
7 Feb 2020 - 14 Feb 2020
Amount
Disconnecting power transformer 33/11 KV of capacity 3.15 MVA from the cable on both sides (HV/LV) and all earthings at 33 KV main receving station at Akhnoor and transporting to contractors workshop at Jammu for repair. Retransporting the same after the repair to the site and making all necessery connections of cables and earthings.
Dismantling the transformer at work shop, taking out core assembly, bushes, bush rods, bucchaulg relay, OLTC, breather assembly, drain out all transformer oil to prevent leakage in the transformer body by replacing all gasket. and reassembling the transformer after repair / replacement of following defective parts.
Insulating Material
33 KV Bushing set
11 KV bushing set
HV and LV Bush rod set
Oil and winding Temperature meter.
Magnetic Oil Gauge
Off Load Tap Changer fixed contacts
Off Load Tap Changer mousing contacts
Filling of transformer oil
Off Load Tap Changer coils overhauling
M & L for Testing and commissioning of Power transformer at site.
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of underground cable and getting out in any type of soil, complete all as directed by the Engr-in-Charge
Returning, filling in, including spreading, leveling watering and well ramming in layers n.exc 25 cms. thick in soft / loose soil, complete all as specified and directed by Engr -in -charge .
Removal of surplus soil not exceeding 50 Mtr and depositing where directs at a level not exceeding 1.5 Mtr above the starting point, complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning in trenches spreading and consolidation 8cm thick before laying the cable & 15 cm of sand after laying the cable, complete all as specified and directed. (compacted thickness will be measured)
Supplying and laying Un-reinforced precast concrete cable cover as in repair 'factory made' of class HVP, Type 1 with peak, of size 300 mm x 180 mm x 40 mm, complete all as specified and directed by Engr-in-Charge.
M&L in repair galvanized iron tube light grade for protection of cable at road crossing/fixed with pole of size 100 mm dia, complete all as specified and directed.
M&L in repair galvanized iron tube light grade for protection of cable at road crossing/fixed with pole of size 80 mm dia, complete all as specified and directed.
Cutting of road for passing cable through roads including re surfacing of disturbed road surface with premixed carpet, WBM etc, complete all as specified and directed by Engr-in-charge.
Taking out old unserviceable HT under ground cable of any size, complete all as specified and directed.
Supply, Laying, jointing and testing of under ground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade and 95 Sqmm 3 core cross sectional area conforming to latest IS and ISI marked, complete all as specified and directed.
Supply, Laying, jointing and testing of under ground cables XLPE insulated screened PVC bedded galvanized steel strips armoured electric power cable (heavy duty) with aluminium conductor HT 11000 volts grade and 120 Sqmm 3 core cross sectional area conforming to latest IS and ISI marked, complete all as specified and directed.
Cable joining kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, as in repair, complete all as specified and directed.
Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 95 sqmm, as in repair, complete all as specified and directed.
Cable joining kit for 11 KV (Earthed) grade cable for outdoor end termination heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm, as in repair, complete all as specified and directed.
Cable joining kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with joining material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 120 sqmm, as in repair, complete all as specified and directed.
Danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, in English and Punjabi/Hindi figures and conventional skull and bones in signal red colour and fixed with M.S clamps, bolts and nuts of approved size, HT, 25x20 cm, complete all as specified and directed by Engr-in-Charge
Supplying and fixing in replacement out door, triple pole, gang operated switch single bank, tilting type suitable to vertical/horizontal mounting consisting of hot dipped electro plated galvanised channel iron base with drop out fuse having 15 Nos insulators 11 KV, copper/copper alloy tinned contacts, copper or chromium plated MS arcing chains capable of making and breaking the magnetising current complete with horizonatal bar, GI pipe as down level coupling and operating handle with locking arrangements and drop out fuzes working voltage 11000 volts 200 Amps including testing, complete all as specified and directed by EIC.
Lighting Arrestor expulsion type for out door use complete with all fittings transmission class discharge capacity 65 kilo Amps suitable for 11000 V including bracket, clamps, nuts and washers and connecting to earth wire, as in repair, complete all as specified and directed by EIC.
MS Framed work as in framed structure of Fe 410-W (Gde-E-250) Quality-A (around 4 pole/2 pole/ LT pannel/ Transformer) guard bars, framed balusters and similar works, as in repair, complete all as specified and directed by Engr-in-Charge
Expended metal cut to length, bent to required shape weight not less than 4 Kg/Sqm and tying with and including annealed MS wire not less than 0.9 mm dia or welded to steel members, complete all as specified and directed by Engr-in-Charge
Surface excavation not exc 30 cm deep and average 15 cm deep and getting out in soft /loose soil, complete all as specified and directed by Engr-in-Charge
Broken stone or boulder hard core of gauge n exc. 63 mm, deposited, spread and levelled in layer not exceeding 15 cm thick watered and rammed to a true surface, complete all as specified and directed by Engr-in-Charge
PCC 1:3:6 type C2 using 40 mm graded stone aggregate as in floor 100 mm thick floor and finished even and smoth without using extra cement, complete all as specified and directed by Engr-in-Charge
Preparation of old steel tubular surface and painting of steel tubular HT pole up to full length complete with two coat of anti corrosive aluminium paint including painting of clamps cross arms, channels, GI pipes and street light fittings breackets etc complete including strip painting with black synthetic enamel paint and aluminium paint up to 1.5 mtr length in alternate layers 30 cm width and marking of pole/feeder no. etc, complete all as specified and as directed by Engr-in-Charge.
Supply & install HT bus bar chamber, factory made, weather and vermin proof having size 90x90x60cm made out of 3mm thick MS sheet with 200 Amp rated aluminium bus bar and with 11 KV pedestal type HT insulators 6 Nos with angle iron frame of size 75x75x6mm duly painted with 2 coats of enameled paint & necessary PCC work for foundation, complete all as specified and directed by Engr-in-Charge.
Over head ACSR conductor, steel reinforced of any size for overhead LT line with and including binding wire 14 SWG (aluminium) for jumpers and stretching, as in repair, complete all as specified and directed by Engr-in-Charge
Mild steel works in repairs as in cross arms of different sizes brancings, supports, clamps and back plates febricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot drilling for bolts in any size or shape as indicated or directed and inclusive of two coats of synthetic enamel painting over a coat of red oxide, complete all as specified and directed by Engr-in-Charge.
Dismantling HT insulators off sizes any type, complete all as specified and directed by Engr-in-Charge
Disc type insulator, porcelain, vitreous 145mm high and 225mm dia ball and socket type, white, brown or green Two-in-series' assembly for tension with tension clamps for conductors, working pressure 11000 volts, complete all as specified and directed by Engr-in-Charge
Pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade, complete all as specified and directed by Engr-in-Charge
Stay assembly complete with accessories in repairs as shown in Electrical Plate No 1 (Dia of stay rod 16 mm) complete all as specified and directed by Engr-in-Charge (Note:- Excavation and PCC Work shall be measured and paid seperately under relevant items)
S&F in repair MCCB of current rating 630 Amps, 415V Four Pole, breaking cap 37KA with adjustable thermal and adjustable magnetic setting, complete all as specified & directed.
S&F in repair MCCB of current rating 630 Amps, 415V Three Pole, breaking cap 37KA with adjustable thermal and adjustable magnetic setting, complete all as specified & directed.
S&F in repair MCCB of current rating 400 Amps, 415V Four Pole, breaking cap 37KA with adjustable thermal and adjustable magnetic setting, complete all as specified & directed.
S&F in repair MCCB of current rating 400 Amps, 415V Three Pole, breaking cap 37KA with adjustable thermal and adjustable magnetic setting, complete all as specified & directed.
Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6 mm thick buried directly in ground (Earth pit not less than 2.25 m below normal ground level) with top edge of the plate not less than 1.5 m below normal ground level connected and including GI strip 32 mmx6mm (upto the body of equipment) by means of brazing, GI bolts, nuts, check nuts and washers, earth plates surrounded by packed layers of coal dust and common salt 15 cm thick all around top and bottom and watering pipe 40 mm bore of GI pipe, light grade all as shown in Electrical plate No 5 of SSR Part I, testing on completion including PCC 1:2:4 type B1 using 20mm graded stone aggregate as in pit cover and PCC chamber in PCC 1:3:6 type C-1 using 20mm graded stone aggregate including excavation and earth work, disposal of surplus spoil to a distance n exc 50 m, complete all as specified and directed by Engr-in-Charge
M & L for Plat form for Transformer of size 4mx3mx1.2 m above ground leval and 30 cm below ground leval including necessary brick work and PCC 1:4:8 type D2 using 40 mm graded crushed stone aggregate , including necessary from work and exposed surfaces finished fair with rendering in CM (1:4) without using extra cement, complete all as specified and directed by Engineer-in-charge.
M & L for Plat form of size 2mx2mx1.2 m for Feeder pillar above ground level and 30 cm below ground level including necessary brick work and PCC 1:4:8 type D2 using 40 mm graded crushed stone aggregate , including necessary from work and exposed surfaces finished with rendering in CM (1:4) fair without using extra cement, complete all as specified and directed by Engineer-in-charge.
M/S SAHNI CONSTRUCTION CO
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .