Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance BE BLOCK 396 BACK SIDE GALI NO 7 HARI NAGAR SOUTH WEST DELHI DELHI 110064 | WEST DELHI | DELHI | 110064 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
Tender Value
Refer Docs
EMD Value
₹11,500
Closing Date
9 Feb 2022, 1:00 pmClosed
EXECUTIVE ENGINEER (SDW)-I
EXECUTIVE ENGINEER (SDW)-I KILOKRI SPS JAL VIHAR LAJPAT NAGAR NEW DELHI - 110 024
Renovation of 100 KVA, HT Transformer and allied work at Kilokri old SPS. (Re-invited).
2022_DJB_215748_3
NOTICE INVITED TENDER NO. - 16 (2021-22)
Open Tender
Miscellaneous Works
Works
45 days
EXECUTIVE ENGINEER (SDW)-I
Please refer Tender documents.
3 documents required · 3 mandatory
₹500
EMD A/c No. 50448339804 at Indian Bank,
₹11,500
Yes
19 Feb 2022
1 Feb 2022
9 Feb 2022
1 Feb 2022
9 Feb 2022
1 Feb 2022
A) Renovation of 100 KVA, 11 KV to 0.04 KV (Japan make) imported Transformer by following works:- Removing all the electric connection HT panel, transformer of 100 KVA by taking all the precaution as per IER guideline
Opening of ducts & transformer by cutting the nut bolts by gas cutter etc. from transformer to panel if needed.
Checking the continuity of bus bars transformer.
Filling of new transformer oil & dehydration of the same. Make:- Power oil / Savita.
Dismantling the transformer by removing to cover, oil tank, silica jel in breather etc.
Lifting the core and winding with the helps of tripot and chain pulley block etc.
Cleaning the core and winding by hot vacuum machine.
Cleaning the transformer and removing the sludge etc.
Replacement of HT defected insulated main leads inside the transformer.
Replacement of LT defected insulated main leads inside the transformer.
Replacement the winding protection pads.
Fixing the core and winding in original shape.
Replacement of top cover gasket and oil seals complete set.
Making connection of buckets relay calibration etc.
Replacement of slica jel.
Re-assembling all the equipment, but bars, making all the connection on HT side, LT side etc. and testing it on load.
Providing & laying of 50mm2 aluminium 3.5 core, armoured cable 1100 volts make:- Havells / Grandlay / Gloster / CCI.
Testing & Commissioning of the transformer full load
(B) Renovation of the GI shed of 12’x13’ size by replacement of rusted & damaged of 6 Nos. GI sheet 12’x3’ size, i/c GI J&L hooks i/c replacement of damaged wire mesh & MS gate etc. by providing of locking arrangement, complete work in all respect.
GOGIA BROTHERS
M/S CHAITANYA CONSTRUCTION CO.
Aqua Mech Systems
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .