Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.9 LAccepted-AOC 218 D 1A JYANTIPUR NEAR SHYAM PIPE FACTORY SULEM SARAI PRAYAGRAJ UP | PRAYAGRAJ | PRAYAGRAJ | UP | L1 | Accepted-AOC Lowest tenderer | |
| 2 | L2₹29.3 L+₹3.5 L (13.4%)Rejected-Finance | L2 | Rejected-Finance Other than lowest quoted tenderer | |
| 3 | L3₹36.6 L+₹10.8 L (41.7%)Rejected-Finance | L3 | Rejected-Finance Other than lowest quoted tenderer | |
| 4 | L4₹38.0 L+₹12.1 L (46.9%)Rejected-Finance | L4 | Rejected-Finance Other than lowest quoted tenderer | |
| 5 | L5₹38.5 L+₹12.6 L (48.8%)Rejected-Finance | L5 | Rejected-Finance Other than lowest quoted tenderer |
Tender Value
₹45.0 L
EMD Value
₹89,940
Closing Date
15 Nov 2024, 6:00 pmClosed
HQ CWE Prayagraj
HQ CWE New Cantt Prayagraj
REPAIR/ MAINT OF LT UG CABLE, LT POLE PAINTING, LT PANELS, MCBs, MCCBs AND MISC ALLIED WORKS AT AYODHYA CANTT.
2024_MES_661454_2
81892/AYD/E8
Open Tender
Civil Works
Item Rate
180 days
Ayodhya
Class D and Category b(i)
6 documents required · 6 mandatory
₹500
AGE (I) Ayodhya
₹89,940
Yes
2 Jan 2025
25 Oct 2024
22 Nov 2024
25 Oct 2024
15 Nov 2024
1 Nov 2024
Amount
Excavation in trenches, not exceeding 1.5 meter wide and not exceeding 1.5 meter in depth for foundation of poles, stays or for taking out/laying of cables and getting out in soft/loose soil complete all as specified and directed by Engr-in-Charge.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25cm in soft/loose soilcomplete all as specified and directed by Engr-in-Charge.
Removing excavated materials (soil) n. exc 50m and depositing where directed at a level n.exc 1.5m above the starting point complete all as specified and directed by Engr-in-Charge.
M&L for sand cushioning to underground cable with clean dry river sand complete all as specified and directed by Engr-in-Charge. Note:- Punned thickness only shall be measured & Paid.
Supply & Laying of sub class 'B'bricks locally available best quality laid flat (length of bricks laid across the length of cable) in tranches for protection of U/G cable complete all as specified and directed by Engr-in-Charge.
Supplying, laying, commissioning & testing LT underground cable 1100 volts grade, XLPE insulated, PVC sheathed heavy duty, armoured with multi stranded aluminium conductor all as per IS 7098(Part-I) 1998, laid in trenches, ducts, pipes or on poles etc including cable gland, cable lugs, jointing, supporting clamp complete etc of the under mentioned type and following sizes complete all as specified and directed by Engr-in-Charge. 10 Sqmm 2 core
Description same all as per Sl Item No 6 here in above but 16 Sqmm 4 Core complete all as specified and directed
Description same all as per Sl Item No 6 here in above but 25 Sqmm 3. 5 Core
Description same all as per Sl Item No 6 here in above but 35 Sqmm 3.5 Core complete all as specified and directed
Description same all as per Sl Item No 6 here in above but 50 Sqmm 3. 5 Core complete all as specified and directed
Description same all as per Sl Item No 6 here in above but 70 Sqmm 3. 5 Core complete all as specified and directed
Description same all as per Sl Item No 6 here in above but 95 Sqmm 3. 5 Core complete all as specified and directed
Description same all as per Sl Item No 6 here in above but 120 Sqmm 3. 5 Core complete all as specified and directed
Disconnecting electrically incomming and outgoing LT UG cable of LT panel of any size and replace burn/unsv suitable size of aluminium bus bar, Welding work for hinches and doors, fixing the locking arrangement including scraping outdoor/indoor side of LT Panel and one coat of redoxide, two coat of synthetic enamelled seimens gray spray of outdoor/Indoor side and reconnecting LT UG cable with fixing cable gland of all suitable size cable and aluminium lugs by using crimping tool, nut, bolt washer etc and all necesary work required for smooth functioning of LT panel all specified and directed by Engr-in-Charge.
Supply and fixing 415V 10KA 'B' curve miniature circuit breaker (MCB) of TPN 63 A, 4 poles current carrying capacity with connection testing and commissioning all as specified and directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of MCCB, 4 pole, 100 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 25 KA,lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of MCCB, 4 pole, 125 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 36 KA,lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/ Indoasian).
Supply & fix in replacement of MCCB, 4 pole, 160 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 36 KA, lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of MCCB, 4 pole, 200 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 36 KA, lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of MCCB, 4 pole, 250 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 36 KA, lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of MCCB, 4 pole, 400 Amp, 415V 50Hz with thermal magnetic trip unit rating breaking capacity 36 KA, lcu=100%, confirming to IS : 13947 (Part I & II) including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S/Indoasian/Havells).
Supply & fix in replacement of ACB, 4 pole, 630 Amp, 415V 50Hz with Microprocessor based SR18G, MDO, C - power Draw-out ACB, including under voltage, rating breaking capacity 50 kA,with connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T Cat No. SL-96061 or equivalent to Legrand/C&S/Havells.
Supply & fix in replacement of ACB, 4 pole, 1000 Amp, 415V 50Hz with Microprocessor based AHA-10S-CS, MDO, C - power Draw -out ACB, including under voltage, rating breaking capacity 50 kA,with connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L & T Cat No SL96043 or equivalent to Legrand/C & S/ Havells.
Supply & fix in replacement of On load Change over switch 400 Amp, 415V 50Hz with Sheet steel enclosure and operating handle confirming to IEC : 60947-3 including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S).
Supply & fix in replacement of On load Change over switch 125 Amp, 415V 50Hz with Sheet steel enclosure and operating handle confirming to IEC : 60947-3 including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S).
Supply & fix in replacement of On load Change over switch 63 Amp, 415V 50Hz with Sheet steel enclosure and operating handle confirming to IEC : 60947-3 including connection and testing complete all as specified and as directed by Engr-in-Charge. (Make :- L&T /Schneider/C&S).
Servicing/Repair the ACB of various Capacity of outdoor/indoor type, tripping circuit and resetting trip values and the nuemerical relays and checking tripping machnism fully by engaging well experianced technicians as per manufacturer recommendation and all as directed by the Engineer-in-Charge.
Shifting of LT Panel after Disconnecting all the electric connections from and earthing terminals from the LT Panel including fixing to another bay with new foundation and necessary earthwork all as directed by Engr-in-Charge.
M&L for Indicator lamp LED type (R,Y,B) complete with bakelite fuse complete all as specified and directed by Engr-in-Charge. Make:- L&T/KEYCEE/SIL.
M&L for installing, testing and commissioning of factory made bus bar chamber comprising of 4 Nos Copper bus bar of 200 Amp rating supported on insulator and enclosed with sheet steel enclosure out door type made out of 3.15 mm thick CRCA sheet, with top edge tappered, dust and vermin proof , having locking arrangement at front and opening arrangement from front & rear both including fixing arrangement on pole/gorunting in floor, with colour coded FRP with compression cable glands for entry & exit of cables, powder coated complete all specified and directed by Engr-in-Charge.
Labour for cutting/ trimming of tree branches up to 80mm thickness along the alignment of LT /HT over head electric line which are going/ touching or falling or ACSR conductor/ poles or near by sub stns etc at any height from GL and making ta leastlearance 1.5m form conductor and removing to a distance up to 100 mtr where directed by Engineer-In-Charge. Note:- (i) Trimming of the branches on one sides of the conductor. (ii) Actual length of cutting will be measured. (iii) The distance as mentioned above will be maintained during contract current period & same location subject to at least 6 months period between two trimming/laping. (iv) Measurement will be taken including all conductor as one only.
M&L for Earthing complete with galvanised steel earth plate electrode 600 X 600 X 6mm thick buried directly in ground vertically to a depth not less than 2.25 meters deep below ground level with top edge of the earth plate not less than 1.5 meters deep below normal ground level, connected with and including galvanised iron strip of size 25 x 4mm connected to main test point as directed as earthing lead by means of nuts, bolts and washers of galvanised iron protected by 40mm dia (medium grade) GI tubing, funnel, wire mesh, 20mm bore GI tubing (light grade) watering pipe, including concrete pit in PCC (1:3:6) type C-1, precast RCC (1:2:4) type B-1 cover slab of size 350 x 350 x 50mm reinforced with 8mm dia TMT bars @ 15cm c/c in both ways and 10mm dia MS handle (01 No) of suitable size for lifting of cover slab, charcoal and salt in alternate layers including necessary excavation and earth work in soft/loose soil all as shown in Electric plate No 3 of SSR Part-I and testing on completion complete all as specified and directed by Engr-in-Charge.
Providing services by deploying adequate number of manpower for attending day to day complaints/ breakdowns of 'NO LIGHT / SHORT CIRCUIT'' including general maintenance, cleaning and dusting of all external electric supply installations from feeder pillar box to building including LT overhead lines & LT under ground cable jointing, distribution panel board, repairs/replacement of defective componenets, fittings & fixtures and depositing the defective/unserviceable dismantled materials in store yard of AGE E/M Ayodhya complete all as directed by Enginner in Charge
Note :- (i) The Electrician should have good working knowledge of LT Supply. (ii) The Electrician should in possession of all requisite T&P as required at site. All the T&P and equipments to be provided by the contractor at his own cost and the rates shall be deemed to be included all expenses on this account. (iii) Vehicle, ladder,tools and takes as required at site for repair shall be provided by the contractor at his own cost and arrangement. (iv) The timing of shifts will be 0900 to 1700 Hrs and reliever shall be arranged by the contractor and the cost thereof shall be deemed to be included in the quoted rate (v) The contractor's representative will report to Engineer-in-Charge / JE EM I/C Ext Electric Supply daily in forenoon and afternoon to collect routine/urgent works related to Ext Elecctric Supply till completion of the contract. The work shall be attended by the contractor immediately. (vi) The complaint shall be rectified within 24 Hrs or otherwise a panelty of Rs 500/- per complaint per day shall be imposed to the contractor for delayed period. (vii) The contractor shall provide all the safety equipments to his workers at his own cost and all safety measures shall be adhered to strictly. The department shall not be held responsible for any lapse / mishappening due to lack of safety measures.
(B) OUTGOING (i) MCCB 4 Pole 250 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T, Cat No CM90642OOPO - 02 Nos. (ii) MCCB 4 Pole 200 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T, Cat No CM90642OONO - 02 No. (iii) MCB SPN 20 Amp, 50 Hz, 230 V, 'C' curve with rupturing capacity 10 KA - 01 No. (iv) Space only for accomodating 4 pole MCCB upto 250 Amp 25 kA - 01 cubicle. (v) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 mm below ground level and 100 mm above the ground level with slot openings fo I/C and O/G cables. Note :- The structural and connection diagram of panel should be got approved by the AO before placing order to the panel manufacturer.
(B) OUTGOING (i) MCCB 4 Pole 200 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T/C&S/Havells/Indoasian - 01 Nos. (ii) MCCB 4 Pole 160 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T/C&S/Havells/Indoasian - 02 No. (iii) MCB SPN 20 Amp, 50 Hz, 230 V, 'C' curve with rupturing capacity 10 KA - 03 Nos. (iv) Space only for accomodating 4 pole MCCB upto 100 Amp 25 kA - 01 cubicle. (v) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 mm below ground level and 100 mm above the ground level with slot openings fo I/C and O/G cables. Note :- The structural and connection diagram of panel should be got approved by the AO before placing order to the panel manufacturer.
(B) OUTGOING (i) MCCB 4 Pole 100 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T/C&S/Havells/Indoasian - 02 Nos. (ii) MCCB 4 Pole 63 Amp, 50 Hz, 415 V with rupturing capacity 25 KA, make: L&T/C&S/Havells/Indoasian - 02 No. (iii) MCB SPN 20 Amp, 50 Hz, 230 V, 'C' curve with rupturing capacity 10 KA - 02 Nos. (iv) Space only for accomodating 4 pole MCCB upto 100 Amp 25 kA - 01 cubicle. (v) Foundation for the panel should provided with PCC 1:4:6 at a depth of 150 mm below ground level and 100 mm above the ground level with slot openings fo I/C and O/G cables. Note :- The structural and connection diagram of panel should be got approved by the AO before placing order to the panel manufacturer.
S&F for Straight through cable joint kit for LT UG cable of following sizes complete all as specified and directed by Engr-in-Charge.
Description same all as per serial Item No 32 here in above but 16 Sqmm 4 Core complete all as specified and directed
Description same all as per serial Item No 32 here in above but 25 to 50 Sqmm 3.5 Core complete all as specified and directed
Description same all as per serial Item No 32 here in above but 70 to 120 Sqmm 3.5 Core complete all as specified and directed
Description same all as per serial Item No 32 here in above but 150 to 185 Sqmm 3.5 Core complete all as specified and directed
Description same all as per serial Item No 32 here in above but 240 to 300 Sqmm 3.5 Core complete all as specified and directed
Supply and fixing in repair aluminium sector lugs short barrel complete all as specified and directed of following sizes:
Description same all as per serial Item No 33 here in above but 25 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 35 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 50 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 70 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 95 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 120 Sqmm complete all as specified and directed
Description same all as per serial Item No 33 here in above but 150 Sqmm complete all as specified and directed
Hiring of cable fault detector, to detect exact position of fault for XLPE /PVC LT/HT cable, 1100/11000 Volts grade heavy duty aluminium conductor of any size including to and fro transporting charges etc. complete all as specified and directed by Engr-in-Charge.
Horizontal boring in soft/loose soil/under roads of any width by manual arrangements for inserting GI pipe up to 100mm bore for passing cables complete all as specified and directed by Engr-in-Charge. Note : GI pipe shall be measured and paid separately.
Supply & laying steel tubing, galvanized light grade bores, for passing LT/HT cable under road or PCC floor or fixed on wall/on pole or drain etc or whenever protection is required including necessary clamps and nut bolts with GI fitting complete all as directed and specified as follows:- (a) GI Pipe 50mm dia.
(b) GI Pipe 80mm dia complete all as specified and directed
M&L for Structural steel work using rolled mild steel section of Fe-290 (Gde E-165) like Angles, flat, square, round bars as in framing for cladding, glazing and the like fixed with angle cleats and connecting plates etc complete all as specified and directed
M&L for Cement concrete for filling in foundations or making good of Road, PCC Floor, supports etc. Type B1, 1:2:4, using 20 mm graded stone aggregate including necessary form work and fair finishing of exposed surface of concrete / facia finish with cement mortar complete all as specified and directed
M&L for chain link fencing galvanised including line wires 4 mm dia, mesh size 150x100mm weight not less than 2.3 Kg/sqm and type of standards rails, straining bolts etc. Including provision of binding wire and fixing complete all as specified and directed.
M&L for preparation of old painted surface of steel tubular swaged poles (9 to 11 meter long) with good neck brackets including junction box, GI pipe and painting with one coat of aluminium paint including cleaning the acrylic cover and painting with black to 1.5 mtr height from top of PCC coping and marking pole numbers with one coat of synthetic enamel paint complete all as specified and directed by Engr-in-Charge. Make - Shalimar/Nerolac/Berger.
M&L for preparation of old painted surface of RCC poles up to the height of 1.5 mtr height and painted with one coat of synthetic enamel paint in strips alternative with black and white colour paint and marking pole number including painting MS channel 'D' clamps bracket, GI pipes etc with one coat of aluminium paint complete all as directed by Engineer-in-Charge. Make - Shalimar/Nerolac/Berger.
S&F for pin type insulator, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle two galvanised iron washer and one galvanised iron nut, 100mm height, 65 mm dia for 1100 bolts grade complete all as specified and directed by Engr-in-Charge.
S&F for shackle type, porcelain, vitreous, white brown or green insulator of size 75mm high and 90mm dia including galvanised mild steel straps of section 31mm x 3mm, 12mm dia insulator bolts, nuts, washer etc for working pressure 1100 volts complete all as specified and directed by Engr-in-Charge.
S&F for small size loop type insulator, vitreous porcelain, white, borwn or green with overall dimensions 65 x 90mm clearance of hole 16mm complete all as specified and directed by Engr-in-Charge.
M&L for aluminium conductor, steel reinforced (ACSR) of any size as approved on LT poles including straining, binding to insulators with aluminium binding wire with connectors, etc providing PVC sleeves for jumpers as in OH conductors complete all as specified and directed by Engr-in-Charge.
Re-Straining tightening of existing ACSR conductor of any size on LT/HT poles including necessary aluminium binding wire, connectors, PVC sleeves for jumpers etc complete all as specified and directed by Engr-in-Charge.
Supply and hanging for Flex board of min size 8' x 8' x1' (back light) (including 6 pass digital printing on back light star flex with 3/4” square iron frame (heavy gauge) with aluminum beeding with side panel covered with painted G.I. sheet with 4 Nos of philips/Crompton LED tube lights 20 watt complete all as specified and directed. Note : hard copy of colour distribution diagramm to be given to the contractor at the time of flex board ordering.
Supply and hanging for Flex board of min size 5' x 5 ' x1' (back light) (including 6 pass digital printing on back light star flex with 3/4” square iron frame (heavy gauge) with aluminum beeding with side panel covered with painted G.I. sheet with 3 Nos of philips/Crompton Make LED tube lights 20 Watt complete all as specified and directed. Note : Hard copy of single line distribution diagramm of HT supply at MRS to Sub stations to be given to the contractor at the time of flex board ordering.
His And Her Enterprises (BID ID -3160902)
VIDYA TRADERS (BID ID -3159602)
Avion Industries (BID ID -3165978)
Hindustan Power Corporation (BID ID -3160710)
AIRDOT ENGINEERING (BID ID -3160422)
PRADEEP TIWARI CONTRACTOR (BID ID -3160815)
M/s Shiksha Enterprises (BID ID -3160684)
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .