| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹20.9 LAccepted-AOC 411 STREET NO 4 PANCHVATI NAGAR BATHINDA 151001 | BATHINDA | PUNJAB | 151001 | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹35.9 L+₹13.3 L (58.5%)Rejected-Finance ASHOKA PARK PALLAVA PARK BVT INS VISHWAKARMA INDIAN NAVY OF GE ND VISAKHAPATNAM | VISAKHAPATANAM | ANDHRA PRADESH | 530001 | L2 | Rejected-Finance Being other than lowest |
Tender Value
₹25.5 L
EMD Value
₹51,000
Closing Date
8 Feb 2020, 6:00 pmClosed
GE Chandigarh
GE Chandigarh
REPAIR AND MAINT OF LT PANEL BOARD, E/M EQUIPMENTS AND UPLIFTING E/M INSTALLATIONS AT N AREA AND HALLOMAJRA UNDER GE CHANDIGARH.
2020_MES_311133_1
GE/CHD-74/2019-20
Open Tender
Civil Works
Item Rate
270 days
Chandigarh
Class D cat a i and b i
7 documents required · 7 mandatory
₹500
GE Chandigarh
₹51,000
Yes
28 Feb 2020
2 Jan 2020
10 Feb 2020
2 Jan 2020
8 Feb 2020
17 Jan 2020
2 Jan 2020 - 9 Jan 2020
Amount
Excavation in trenches in any type of soil not exceeding 1.5 metre deep and not exceeding 1.5 mtr width and getting out soil including forming bottom surface to required slope/gradient for laying cables/pipes etc. all as specified and directed by Engineer-in-Charge including removing cable protection PCC covers/ bricks & stacking serviceable covers / bricks for reuse and disposal of unserviceable covers within 50 m all as directed.Note : (i) Excavation shall be made carefully in order to avoid damage of existing cables and protection covers.(ii) The excavation work may be carried out in short lengths for locating fault in under ground cables at different locations.
Excavation in trenchs exc. 1.5 mtr in depth and n.exc 3 mtr depth and getting out in any type of soil complete all as specified.
Returning filling in including spreading leveling watering and well ramming in layers not exc 25 cm thick all as specified.
Removing of surplus excavated material to a distance not exceeding 50 m and depositing where directed at a level not exc 1.5 m above the starting point all as specified .
M&L for ordinary sand cushioning 8cm thick below the cable & 15cm above the cable and punned down to 10cm from top of cable complete all as specified. Total spread thickness shall be 23 cm and measured 18 cm compacted thickness for payment).
Material and labour for old size bricks sub class 'B' laid in trenches for cable protection laid flat adjacent to each other and length perpendicular to direction of cable all as specified and directed.
M&L for protection pipe laid in trenches /fixed to pole as for cable with galvanised steel tubing 80 mm dia bore light grade
M&L PCC (1:3:6) type C1 using 20 mm graded crushed stone aggregate for coping of pole including dnecessary form work complete all as specified and as directed
M&L PCC (1:3:6) type C2 using 40 mm graded crushed stone aggregate for foundation of pole including dnecessary form work complete all as specified and as directed
Supply and install steel tubular swaged pole type 410 SP-31 (9 meter long) complete with CI base plate and final incl foundation incl dismantling of old unsv RCC pole complete all as per SSR and as directed.
S&F for PVC insulated aluminium conductor 1100 volts grade heavy duty cable, served with inner sheathed of PVC tape and overall PVC sheathed in service connection suspended by insulating hangers not more than 1 metre apart including 4 mm suspension wire, one twin core cable flat or circular of size 2 core 10 Sqmm complete all as specified and as directed by Engineer-in-Charge . MAKE : FINOLEX/ HAVELL’S PLAZA.
All as per item No 11 here-in-before but 6 Sqmm
Supply, Laying in repairs ,testing and connecting underground cable PVC insulated armoured heavy duty electric cable with aluminium multi-stranded conductor 1100 volts grade,4 core, 16 Sqmm.
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 Sq mm 4 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 35 Sq mm3.5 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 Sq mm3.5 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 70 Sq mm3.5 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 Sq mm3.5 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Supply and lay in repairs ,cable XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 120 Sq mm3.5 core.MAKE-Havells/KEI /Plaza/GRANDLEY
Dismantling of old unserviceable ACSR conductor and supply and fixing by stratching required tension new ACSR (Aluminium Conductor Steel Reinforced) on existing LT pole conductor complete. Make : Alind / Bharat Conductor / Nicco.
Supply and Fixing Shackle type porcelain, vitreous white, brown insulator incl galvanised mild steel straps, washers, insulator bolts, washers and nuts working pressure 1100 Volts. 75 mm in heiqht and 90 mm dia and incl galvanise steel fittings like straps and bolts complete. Make: Bengal portries or equivalent
Caliberation of VCB relay for phase imblance, earth leakage tip and under voltage and testing the VCB in open and close position , continuity of contacts , manual closing , electrical closing and remote closing, remot tripping through protection relays , checking spring charging motor etc and servicing the VCBs for smooth and trouble free functioning . Setting of VCBs relays as per load of feeders and also amps setting as per incoming feeder from UT. All equipment required for setting , servicing and caliberation shall be arranged by contractor. Servicing of VCBs shall be carried out through OEM rep or pers auth by OEM.
Testing of Earth resistance with an earth megger after disconnecting the same from the equipment in presence of MES rep for all electrical equipments such as Transformers , HT/LT Panels , Two pole/4 Pole structure, GOD, LA , Pump House Panels, Gen Set etc and writing earth resistance result on the earth cover with black or paint and in a separate earth test register including connecting the same afte testing complete all as directed
Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 4.5 meter below normal ground level (with top edge of earth plate not less than 3.75 meter below ground level) connected to GI strip 32x6mm main earthing lead by means of galvanized bolts, nuts and washers with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed.
Material and labour for earthing complete with copper earth plate electrode 600mm X 600mm X3.15mm buried directly in ground vertically to a depth not less than 4.5 meter below normal ground level (with top edge of earth plate not less than 3.75 meter below ground level) connected to copper strip 25x4 mm main earthing lead by means of brass bolts, nuts and washers with connected to earth test point & to main switch board /panel etc. all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to equipment/substation/panel etc, adequate quantity of charcoal dust and common salt, test point, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI light grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI light grade earth lead protection pipe, complete all as specified and directed.
Supplying and fixing earth continuity conductor or main earthing lead 32mm X 6mm ,GI strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by GI nuts, bolts and washers at every joint complete all as specified & directed.
Material and labour for earth continuty conductor or main earthing aluminium strip 25mm X 3mm laid in pipe or fixed on wall or any other position including jointing by nuts, bolts & washers at every joint complete all as specified & directed.
Material and labour for spreading and levelling stone aggregate 63 mm 150 mm average thickness around transformer , two pole/four pole structure including removing of grass and bushes from roots of the area
Cleaning the area of electric /water supply outdoor/ indoor installations by cutting and removing jungle sturts, roots, bushes plants small trees etc and deposited to n.exc 50 mtr to 100 mtr out side installations complete all as specified and as directed by Engr-in-Charge.
S&F in repair rolled mild steel duct cover made out 6 mm thick of plates (plain or chequred) channels, square cut or notched (ordinary and counter sunk) forming holes, handle with riveted, bolted or welded attachment conforming to Fe 410-W(Gde-E-250) quality-A complete all as specified and directed by Engineer in charge.
Supply,fixing and connecting in repirs MD-XL double metalized paper (Extra low Loss) power capacitor for 3 phase 440 volts 50 Hz system for permissible non-linear load 20% of capacity 2 KVAR. Make: APCOS/L&T/ Siemens/BCH
All as per item no 31 here in beore but of cap 3 KVAr
All as per item no 31 here in beore but of cap 5 KVAr
All as per item no 31 here in beore but of cap 7.5 KVAr
All as per item no 31 here in beore but of cap 12.5 KVAr
All as per item no 31 here in beore but of cap 15 Kvar
All as per item no 31 here in beore but of cap 20 KVAr
All as per item no 31 here in beore but of cap 25 KVAr
Power Contactor 9 Amp 3 Pole AC 3 Capacitor Duty Make : Legrand /BCH/Siemens
Power Contactor 16/18 Amp 3 Pole AC 3 Capacitor Duty Make Legrand /BCH/Siemens
Power Contactor 32 Amp 3 Pole AC 3 Capacitor Duty Make Legrand /BCH/Siemens
Power Contactor 50 Amp 3 Pole AC 3 Capacitor Duty Make Legrand /BCH/Siemens
Power Contactor 63 Amp 3 Pole AC 3 Capacitor Duty Make Legrand /BCH/Siemens
MCB 10 Amp TP C Curve Make Legrand /BCH/Siemens
MCB 16 Amp TP C Curve Make Legrand /BCH/Siemens
MCB 25 Amp TP C Curve Make Legrand /BCH/Siemens
MCB 50 Amp TP C Curve Make Legrand /BCH/Siemens
MCB 63 Amp TP C Curve Make Legrand /BCH/Siemens
ON,OFF Indicating Lamp Make BCH/Siemens/Legrand/L&T
Start,Stop Push Button for APFC Panel Make BCH/Siemens/Legrand/L&T
S & F in repair Power factor controller digital type 6 step controller all as per cat no.415043 fixed as in repair complete all as specified Make: Legrand or equivalent in/L&T/C&S/BCH
Blanking plates to cover unused space in DB’s.complete all as specified. MAKE : ABB, AE, HAGER, LEGRAND, SIEMENS.
Cutting road/ Trench less boring for passing the cable/pipe and making good with plain cement concrete 1:2:4, type B-1 using 20 mm graded crushed stone aggregates complete all as specified. Note :- Average width of excavation 300mm,average depth 600mm and average thickness of PCC 300mm, rates quoted against the item shall deemed to be included for the same.
Surface dressing in hard/dense soil n exc 15 cm deep , levelling and site clearence for electric instalations area and water supply installation .
Hardcore of guage n. exc 63mm , broken brick bats deposited, spread and levelled in layers n. exc. 15 cm thick, watered and rolled/rammed to a true surface all as directed by Engr in charge.
M & L for 100 mm thick PCC (1:4:8) type D-2 using 40mm thick stone aggregate as in sub base complete all as specified and as directed by Engineer-in-Charge.
M&L for 100 mm thick PCC (1:2:4) type C-2 using 40 mm graded crushed stone aggregate laid in alternate bays, each bay n. exc 2.5m in length as in PCC path , finishing cement concrete surface even and fair without using extra cement including fillings of joints with bitumen grade 85/25 complete all as specified and as directed by Engineer-in-Charge.
Demolition of cement concrete (unreinforced) in ground floors and paving n.exc 15cm thickness (below or above ground level) complete all as specified and directed by Engineer-in-charge
M & L for machine pressed 60mm thick pre-cast cement concrete( Design Mix-35 ) inter locking tiles any colour and shape ( confirming to ISI-15658-2006) bedded over 50 mm thick sand cushioning and joint filled with sand complete all as specified and directed by Engineer-in-charge
All as per item ser No 60 above but of size 80 mm thick
Supply and fixing in repair LED type solar street light fitting with following features/specification:- 1. Luminaire:- Aluminium housing LEDs for light source optics with high effeciency driver & MPPT charge controller, Excellent heat dessipation IP 65 protection, High birghtness and high efficiency of more than 120 lm/W new age LEDs, individual peanut optical lenses for uniform light distribution system output: 2200 Lm. 2. Solar Panel:- Polycrystaline solar cells. 3. Battery:- Tubular construction, 12 V 100 AH, 75% depth of discharge, galvanised battery box 3 days autonomy, long life, weather proof, long back-up ideal for cloudy conditions. 4. Pole:- Galvanised pole, Rigid and safe, corrossion free length 5/6 mtr. With optimum thermal management and heat sink design and microprocessor based charge controller and led driver maximizes the performance of panel & battery. Cat part No : BRP 402 make philips Minigreen 21 Watt.
S &F in repair energy saving LED street light 40 to 45 watt luminaire with high power LEDs with lens of beam angle of 120 degree,luminaire made of pressure die cast aluminium body with built in heat sinks, painted with polyurethan/powder coated paint, enclosed with toughened glass including separate compartment for cable and incl sealed/compact driver for easy access during maintenance,suitable for operating on voltage 120 - 270 volt,AC,50 HZ,with inbuilt surge protection device having maximum discharge surge current( Imax) -10kA (8/20 µs) ,Nominal discharge surge current ( In)-10kA (8/20 µs) and protection level (Up) upto 10 kv , out put Luminous efficacy not less then120 Lumen/Watt , CRI more then 70, conforming to IP 65, class 1 complete all as per Manufacturer's specifications including taking down old unserviceable fittings of any size/ wattage complete suitable for 50 Mm OD pipe ingressproctection IP 65 with DI clamp, GI Bracket complete all as directed by Engr-in-Charge. Make :- Philips / Bajaj / Osram/ C&S/CG/Halonix
Taking down old U/S any type of sign board from any position and M& L for Informatory LED Glow sign display board with all necessary electrical wiring and conection with battery back up of 6 hrs of size 7.35 Mtr x 0.50 Mtrs LED desplay in red colour as ( ELECTRIC AND WATER SUPPLY COMPLAINT CELL AGE E/M (CHANDIGARH) duly supported with MS sheet from the back side and stiffened with angle iron of size 25x25x4mm to withstand wind pressure . LED glow sign board to be fixed on Chromium plated Stainless steel Pipe frame of 50mm Dia, at 4.5 mtr height complete all as per ground requirement and as directed by Engr-in-Charge Note : The cost of Excavation post hole, earth work , PCC for foundation etc shall be deemed to be included in the unit rate of this item. Nothing extra shall be admissible on this account
M& L for Informatory sign board of size 1000mm x600mm made out of 2mm thick aluminium sheet fixed on Chromium plated Stainless steel Pipe frame of 50mm Dia, 2.25mtr long vertical member and 40mm Dia 1.30mtr horizontal member ,including letter writing (100 to 150 words) , logo/drawing made with computerized printing of fully retro reflective with high intensity prismatic tape pasted on sheet with single side writing including frame emmebedded in 0.30x0.45mtr in PCC (1:3:6 ) type C-1 complete all as specified and directed by the Engineer-in-charge Note : (i)The cost of Excavation post hole, earth work , PCC for foundation etc shall be deemed to be included in the unit rate of this item. Nothing extra shall be admissible on this account.(ii) The letter size of Main heading shall be minimum100mmx10mm and sub heading letter size shall be minimum 50mmx5mm.(iii) The drawing and colour of writing work shall be got approoved by Engineer in charge.
S&F in repair Decorative LED 30watt Post top lantern luminaire with diffuser and painted aluminium deflector complete including taking down existing any type of lantern and connecing up with suitable size of copper flexible cable.LED30 WATT as per cat no LTGL30-24X1HPLED MAKE-C&S/BAJAJ/PHILIPS
S&F street light bracket made out of 40mm dia, 1.50 mtr long GI tubing, "medium grade" ISI marked, bend into required shape and at an angle as site requirement and including M&L for MS clamps size 32 x 6mm for fixing street light fittings and bracket including nut, bolt and washers duly painted with two coats of aluminium paint over a coat of red oxide primer including taking out existing rusted GI bracket complete all as specified and as directed.
Trimming of tree branches and vegetation along LT OH line and near to pole 2 Mtr clearance on either side complete all as specified and as directed by Engr-in-Charge
S & Laying for XLPE insulated , screened , PVC.bedded galvanized steel strip or wire armoured electric power cables ( heavy duty ) with aluminium conductot ,1100 volt grade , cross sectional area 10 Sq mm , 2core laid in trenches after taking down old u/s cable any complete all as specified and as directed. Make : PLAZA /GLOSTER /FINOLEX/HAVELL’s.(Note :- Excavation, earth work, brick protection, sand cushion & GI pipe shall be measured & paid separately)
M & L for MCCB, TPN, 400 Amp, 415 volt ,Adjustable type thermal magnetic release breaking capacity 35 KA as in repair complete all as specified and as directed by Engineer-in –charge.Make: Legrand/BCH/Schneider/L&T.
M & L for MCCB, TPN, 250 Amp 415 volt ,Adjustable type thermal magnetic release breaking capacity 25 KA as in repair complete all as specified and as directed by Engineer-in –charge.Make: Legrand/BCH/Schneider/L&T.
M & L for MCCB, TPN, 200 Amp 415 volt ,Adjustable type thermal magnetic release breaking capacity 25 KA as in repair complete all as specified and as directed by Engineer-in –charge.Make: Legrand/BCH/Schneider/L&T. Note for item No 70 to 72 above: Make and frame size of MCCB shall be as per existing so that the same can be fitted in panel properly.
M & L for MCCB, TPN, 160 Amp 415 volt ,Adjustable type thermal magnetic release breaking capacity 36 KA as in repair complete all as specified and as directed by Engineer-in –charge.Make: Legrand/BCH/Schneider/L&T. Note for item No 73: Make and frame size of the new MCCB should be as per the existing unsv MCCB so that new MCCB can be fixed and connected properly in the panel
Supply & Fix as in repair incl testing and Commissioning of dozing pump high pressure single head, adjustable dozing pump and high pressure range 0 to 12 Kg/ Sqcm , Power 230 volts, 50 Hz, 44 RPM 1/30 HP functional output adjustable up to 17 Ltrs / hrs (Max pressure) self priming with vertical or Horizontal mounting type Make Varima model No VDP1217 /Aquafit any product approved
S&F FASDS suitable for 40 HP Submersible electric driven pump set ,3 Phase , AC 415 volt ,50 HZ with MS enclouser with Std proction ie single phase, over volt /under volt etc complete Make : BCH/Seimens/scheneider/havells
S&F FASDS suitable for 15 HP Non clog Submersible electric driven pump set ,3 Phase , AC 415 volt ,50 HZ with MS enclouser with Std proction ie single phase, over volt /under volt etc complete Make : BCH/Seimens/scheneider/havells
S& F for as in repair PVC insulated ,unsheathed copper conductor cable 16 Sq mm ,3 core , flat in shape suitable for submersible pump motor complete all as specified and as directed by Engineer-in-Charge. Make : KALINGA / FINOLEX / PALAZA / HAVELLS
Supply, fixing connecting and testing in repair Motor protection unit(MPU) three phae 415 volt , 50 HZ ,automatic phase sequence corrector automatically correct inut reverse phase, single phase protection, LV, HV, LIV, Auto of loft, timer, Dry running under & over current, unbalancing ,float switch with built in CTs (Automatic-RTM ) complete all as specified. & directed
Disconnecting and taking down carefully old UNSV/ non functional aviation light fitting of any pattern any description and in any position complete and supply, installation, commissioning and testing on over head reservior new LED aviation obstruction lights, comprising of die cast aluminium alloy housig, finished in avaitation yellow colour, polycarbonate enclosures in red colour , with and including 302 Nos LED and accessoried complete all as specified and directed cat part No BGAV 302 LED of BAJAJ Note : Rate for any preparatory works, T&P and other resources reqd for dismantling /repair/ fixing of aviation obstruction light, air termination rod etc on the top of OHR at the height of 20 to 25 m from Ground level is deemed to be included in the scope of above item.
Taking down existinng U/S worn out Busbar chamber from the position after carefully disconnecting the cable terminals &supply fixing and connecting up complete bus bar chamber 100Amps capacity with copper bus bar 4way out going all as per cat no IHBB010004 make-Havells or equivalent in L&T/legrand to be fixed/ partly flushed in wall complete all as directed by ENGINEER- IN CHARGE.
Supply only heavy duty ,temper proof , industrial type pad , corrosiion resistant, 10 livers padlock having double locking security rating 5 with 03 Nos keys 65 mm dia. Make : harrison/Godrej/Link
M&L Chequered cement concrete tiles 20cm x 20cm x 25mm thick, set, jointed and pointed in neat cement slurry in floors comlete ncluding including 15mm thick bedding of layer of cement sand mortar (1:6) and demolation of old unsv chequered tiles
M&L in repair for Non skid Ceramic coloured/printed 7to 8 mm thick(square/ rectangular) area of each the exceeding 0. .06 sqm but not exc 0.11 Sq m laid as in floors, setting and jointed with cement slurry bedded over & including 15mm thick bedding of layer of cement sand mortar (1:6) and pointed with coloured cement to match with surfaces of tiles complete all as specified and as directed by Engineer-in-charge . Make : KAJARIA/ORIENT BELL / JOHNSON.
M&L Glazed ceramic tiles in vertical surface 350x 250x 7 mm/ 450X 350X 7mm thick set and jointed in neat cement slurry and pointed in white or colour cement to match as in skirting/dado complete all as specified and as directed by Engineer-in-Charge. Make : KAJARIA/ORIENT BELL/JOHNSON/SUNHEART/ASIAN
M&L for Mild steel work of angle iron section or any section as in posts & struts for cattle/security fencing/ including cutting top to shape, drilling holes, notching for wires etc, flat iron fillets (for securing wire mesh etc) including as in fencing post, including all necessary drilling, bolting or riveting etc and similar work conforming to Fe-410-w( GraeE-250quality –A) complete including painting with one coat of red oxide as primer and two coats of synthetic emanel black paint all as specified and as directed by Engineer –in- charge
Framed work as in doors or gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete including painting with one coat of red oxide as primer and two coats of synthetic emanel black paint and taking out old unsv gate.
Steel work in tubular trusses including special shaped washer etc. complete using ERW or induction butt welded tubes conforming to I. S.1161- 1979 grade St.-240 complete including painting with one coat of red oxide as primer and two coats of synthetic emanel black paint→→
Supply only Chain link fencing conforming to IS-2721- 1979,Chain link MS galvanisd fencing, any size or type complete all as specified and as directed by Engineer-in-Charge.
Fixing only chain link fencing including line wires, any mesh, size and type to any type of standards, rails, straining bolts, etc including provission of binding wire
Taking down cement plaster on brick or concrete or stone wall surfaces including racking out joints, hacking for keys, scrubbing down with water etc complete all as specified and as directed by Engineer-in-charge
15mm thick cement plaster with cement sand mortar (1:6) on fair faces of brick or concrete surfaces finished even & smooth without using extra cement complete all as specified and as directed.
All as per above item No 91 hereinbefore but 15mm thick plaster with CM (1:4)
M&L for PCC 1:2:4 type B-1 using 20mm graded crushed stone aggregate as in roof kerbs , benching etc complete all as specified and as directed by Engineer-in-Charge.
S & F in repair Pre-painted galvalume aluminium zinc coating GI based corrugated steel sheet 0.50mm of an colour having tensile strength of 550Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
Demolition of brick tiles or terracing tiles single layers as on roof including any treatment complete all as specified and as directed.
Demolition of mud of any thickness including plastering and leeping whether full thickness removed or only a part there of(average depth 80 to 100 mm) complete all as specified and as directed.
M& L for 50 mm average thick cement concrete 1:2:4 type B1 using 20mm graded stone aggregate as in roof padding finished the surface even and smooth without using extra cement complete all as specified and as directed.
M&L Providing & laying 3mm thick APP (Atactic poiypropylene polymer) modified prefabricated five layer, weight not less than 3.60 Kg/sqm water proofing membrane, black finished, reinforced with non-woven polyster matt make as approved, consisting of a coat of bitumen primer @ 0.40 Ltr/Sqm by the same membrane manufacture, of density 0.87 to 0.89 Kg/ltr at 25 degree C temperature and viscosity 70-160 cps. Over the primer coat, the layer membrane shall be laid using butane torch and sealing all joints etc after preparing the surface complete as per standard practise as per manufacturer`s instructions. The vital physical and chemical parameters of the membrane shall be as under :- (i). Joints strength in longitudinal and transverse direction at 23 degree C as 650 /450N/5 Cms. (2) Tear strength in longitudinal and transverse direction as 300/250/5 Cms. Softening point of membrane not less than 150 Degree C. Cold flexibility upto 20 degree C when tested in accordance with ASTM (D-5147). (3) The Laying of membrane shall be got done through the authorized applicator of manufacturer of membrane only.
Laying only 40 mm thick old brick tiles laid and bedded in 15mm thick cement mortar 1:6 and joints grouted flush in cement mortar (1:3) mixed with 5% of crude oil by weight of cement including cleaing of old brick tiles for re-use.
M&L for 40mm thick brick tiles laid cement mortar 1:6 and joints grouted flush in cement mortar (1:3) mixed with 5% of crude oil by weight of cement complete all as specified and as directed.
S&F in repair for Galvanized, two strand, steel barbed wire, 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails, straining bolts including securing or tying at crossings with and provision of galvanized mild steel wire, staples or steel pins, etc complete all as specified and directed by Engineer-in-Charge (Each line of wire to be measured).
Restraining , resecuring incl making good staples of Galvanized, two strand, steel barbed wire, 2.24mm dia barbed with 2mm dia barbs complete all as specified and directed by Engineer-in-Charge (Each line of wire to be measured).
Preparation of new steel surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint ( Ist quality) over a coat of red oxide primer complete all as specified and directed by Engineer-in-charge. Make : NEROLAC/ASIAN/BERGER.
Preparation of old steel surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint ( Ist quality) complete all as specified and directed by Engineer-in-charge. Make : NEROLAC/ASIAN/BERGER.
Preparation of new wooden surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint ( Ist quality) over a coat of red oxide primer complete all as specified and directed by Engineer-in-charge. Make : NEROLAC/ASIAN/BERGER.
Preparation of old woodenl surfaces of any description over 10cm in width or girth and applying two coats of synthetic enamel paint ( Ist quality) complete all as specified and directed by Engineer-in-charge. Make : NEROLAC/ASIAN/BERGER.
Supply and Laying in repairs steel water tubing complete with all fittings size 15mm bore medium grade ISI marked IS-1239-1976 pipe laid in trenches on walls or in any position incl taking down complete all as directed by Engr-in-charge. Make :---- JINDAL/SWASTIK/SURYAPARKASH.
Supply and Laying in repairs steel water tubing complete with all fittings size 20mm bore medium grade ISI marked IS-1239-1976 pipe laid in trenches on walls or in any position incl taking down complete all as directed by Engr-in-charge. Make :---- JINDAL/SWASTIK/SURYAPARKASH.
S&F for Ball valves high pressure of PTMT with epoxy coated Aluminium rod & highdensity plastic ball screwed for iron pipe and fixed. (Minimum weight 15mm-142gms/ 2 0 m m - 2 1 0 g m s . / 25mm-455gms/ 40mm - 690 gms)
S&F bib tap, cast copper alloy with crutch or butterfly handle, screwed down, screwed for 15mm bore iron pipe and fixed complete all as specified and as directed. Make :---- SOMA/ PARKO/ESS-ESS
S&F for stop valve cast copper alloy screwed down high pressure with crutch or butterfly handle screwed both ends for 15mm bore iron pipe or for union and fixed complete all as specified and as directed. Make :---- SOMA/ PARKO/ESS-ESS.
S&F for 45cm long, 15mm bore low density polythene pipes or pressure rating 6 kg/Sq cm including two PTMT union to connect iron to ploythene connection pipe complete all as specified and directed by Engineer-in-charge.
S & F for PVC flushing cistern of 10 ltr capacity valveless, syphonic action type, flushing cistern, low level, white, with inlet, ball valve, float and handle including flush pipe of 32mm bore MS chromium plated and connection to pipes etc complete all as specified and directed by Engineer-in-charge. Make : HINDWARE/CERA/PARRY WARE Note :- Colour of flushing cistern shall be match with the wash down closet pan.
S&F Plain framed, panelled shutter (two panel) with lock rail and panel of 9 mm B.W.P. commercial ply or 12 mm veneered particle board with commercial veneering on both faces. The size of rail and stile as per IS : 1003 (Part I), kiln seasoned and chemically pressure treated
M&L for Pressed steel frames of size 125 x 60mm for doors with one or more rebates including necessary fixing lugs, hinges, lock strike plate,etc., complete, as specified and directed by Engr in charge
M&l for Glazed and skeleton shutters 35mm thick, open rebated and prepared to receive glass,gauze, etc. (without sash bars,framing plain,edges of framing plain chamfered or rounded. fitted with cut and mitred beads for securing glass,etc.; of shutters as sizes of me-mbers specified in SSR PartI, Section 8, clause 8.24 (a); supplied and fitted to chowkats
M&L for Stainless steel wire cloth.0.36mm nominal dia of wire and average width of aperture 1.40mm and fixed with stainless steel wire staples including tang down old wire mesh.
Supply and fix in repair aluminium steel barrel tower bolts 150mm long stove enamelled black, with bright bolt and fixed
Aluminium sliding door bolts,300mm long plate type, stove enamelled black, with bright bolt not less than 12mm dia with and including a minimum of 6 bolts and nuts, four on bolt plate and two on staple plate and fixed
M&L for Butt hinges 100mm, heavy weight, cold rolled mild steel, including fixing hardware.
M&L for Mild steel pressed handles 150mm, oval type, stove enamelled
M&L for Steel windows with side hung shutters including projecting type hinges with steel handle, and steel peg stay,complete with glazing bars,dovetailed or welded
M&L for Sheet glass,Sheet glass 3mm thick,ordinary and glazing with oil putty in square mtr exc 0.5 sq. in each pane
Dismantling posts or struts ( wood ,steel or RCC ) any section , including taking out embedded portion and making good to disturbed ground embedded in natural ground complete all as specified and as directed by Engineer-in-Charge.
Steel rolling shutters, with out ball bearing, as specified including top cover, an- choring rod, hasp and staple and one shop coat of primer; erected in position as indi- cated, complete: push pull or manual type incl demolation of unsv roling shutter
M&L for preparing surfaces and applying two coats of of cement base paint on new plastered surface of walls
M&L for preparing surfaces and applying one coat of whiter washing on old surfaces of walls /ceiling.
M&L for preparing for old plastered surfaces and applying one coat of cement base paint on walls
M&L for distempering on old surface of walls with oil emulsion distemper in two coats complete.
M&L for distempering on new plastered surface of walls with oil emulsion distemper in two coats complete.
M&L preparing plastered or unplastered surface by washing with bio wash using 10 % bleaching powder in water, applying acrylic primer and applying two coats of plastic emulsion external weather proof complete all as specified and as directed.
Precast RCC type B-1 (1:2:4), using 20 mm graded crushed stone aggregates landings, cover slabs (for manholes etc.) chullah hoods, chajjas, water troughs, mangers, shelves and similar articles with plain faces including all mouldings but excluding frame, set in cement mortar 1:4 complete all as specified. incl foam work and demolation of RCC Note :- Reinfrocement shall be measured & paid separetly.
MS TMT bars 10 mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed ) not less than 0.9 mm dia all as directed and specified.
M&L for Brick work with subclass‘B’ bricks,straight or curved on plan exc 6m mean radius, built in cement mortar 1:6 incl demolation of old brick work
S & F Pre-painted galvalume aluminium zinc coating GI based plain steel sheet 0.50mm of an colour having tensile strength of 550Mpa as in roof covering/cladding to wall, fixed with self tapping screws complete all as specified and as directed.
Taking down copper /aluminum point wiring (light,fan,socket or power ) complete, including fixture and fitting such as switches,ceiling rose ,holders regulators,sockets any type light fitting etc for taking credit,removing from site of work and making good to the disturbed surfaces of walls/floors etc complete all as specified and as directed by Engineer - in -Charge.
Taking down carefully sub main wiring any sizes and runs including PVC conduit etc and making good to the disturbed surfaces of walls/floors etc complete all as specified and as directed by Engineer - in -Charge.
M&L for Point wiring with copper conductor, single core, PVC insulated, unsheathed stranded FRLS cable (IS 694), including PVC insulated copper multi-stranded conductor cable, unsheathed, of size 1.5 sqmm and one single core earth continuity multi-stranded conductor size 1.5 sqmm green in colour to common earth and connecting to earth dolly with copper crimp of suitable size and including PVC casing caping with accessories on walls/ Ceiling / floor etc., including MS box 1.6 mm thick with 3mm hylem sheet cover for fixing of switches/sockets/fan regulators etc, complete all as specified for One light point controlled by one switch 5 Amp SP one -way
As per item No 138 above but One fan point controlled by one switch 5 Amp SP one -way
All as per item No 138 above but One bell point controlled by one switch 5 Amp bell push
All as per item No 138 above but One 3 pin socket outlet point 5 Amp on same board .
All as per item No 138 above but One 3 pin socket outlet point 5 Amp on independent board.
All as per item No 138 above but but wiring with 2.5 Sqmm nominal area cable for 15 Amp socket outlet three pin Independent point with 2.5 Sqmm copper conductor for earthing (green colour).
S&F in repairs ceiling rose surface bakelite 65x50mm three terminals complete all as specified ISI marked.
S&F in repairs electric bell ,AC 230V, single pole, complete all as specified.
S & F in repairs Bell Push flush type, 230 Volt, single pole, 5 Amps, (ISI marked), complete all as specified.
S & F in repairs one way switch piano flush type 230 Volt, single pole, 5 Amps, ISI marked,complete all as specified.
S & F in repairs socket 2 pin 5 Amps, 3 pin 5 Amps flush type, 230 volt single pole, (ISI marked), complete all as specified.
S&F in repairs switch Pino flush type 15 Amps 230 volt, (ISI marked) complete all as specified.
S & F in repairs multi socket 2 in 1, 3 pin 5 Amps and 3 pin 15 Amps 230 volt, (ISI marked), complete all as specified.
S & F in repairs fan regulator flush electronic step type Any modle complete all as specified
S&F in repair tube light fitting Box type made of CRCA sheet 18 To20 Watt, including 1 x 18 To 20 watt retro LED tube rods and pre-wired with high efficiency electronic driver and connecting with three core PVC copper flexible cable of size 23/.0076 from ceiling rose to connector block complete all as specified.
S&F in repairs batten holder bakelite complete with LED lamp 10 watts (Cool light) all as specified (ISI Marked).
S&F in repairs LED light fitting 1x10 watt bulk head luminaries with opel diffuser 10 watt LED IP 65 ,230V 50 Hz.
S &F energy saving LED Flood light 150 to 160 watt luminaire with high power LEDs lens of beam angle of 120 degree,luminaire made of pressure die cast aluminium body with built in heat sinks, enclosed with toughened glass including separate compartment for cable and incl sealed /compact driver for easy access during maintenance,suitable for operating on voltage 120 - 270 volt,AC,50 HZ,covered with inbuilt surge protection device having maximum discharge surge current( Imax) -10kA (8/20 µs) ,Nominal discharge surge current ( In)-5kA (8/20 µs) and protection level (Up) upto 10 kv , out put Luminous efficacy not less then120 Lumen/Watt , CRI more then 70, conforming to IP 66, protection class 1 complete all as per Manufacturer's specifications and including necessary fixing arrangment, complete all as directed by Engr-in-Charge. Make :- Philips / Bajaj / Osram/ C&S/CG/Halonix
S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door) 4 way SPN suitable for MCB DB's 240 Volts with 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting as in repair complete all as specified and directed.
S&F epoxy powder coated or polystrene insulated material sheet metal enclosure factory made (double door) 8 way SPN suitable for MCB DB's 240 Volts with 200 Amps rated busbar, neutral & earthing link bar, flush/surface mounting as in repair complete all as specified and directed.
S&F MCB single pole ISI marked ISI Marked `B' series working on 240 Volts 50 HZ AC supply for incomming and out going controlling cercuit of capacity 6-32 Amp breaking capacity 10 KA as in repair etc all as specified and directed.
S&F MCB single pole and neutral ISI marked `B' series working on 240 volts 50HZ AC supply for incomming & out going controlling system of capaicty 40-63 Amps 10 KA breaking capacityas in repair etc all as specified and directed.
S&F MCB triple pole and neutral ISI marked `B' series working on 240 volts 50HZ AC supply for incomming & out going controlling system of capaicty 40-63 Amps 10 KA breaking capacity as in repair etc all as specified and directed.
S&F in repairsLED Bollard 10Watt with die cast aluminium housing with polycarbonate housing and cylinder diffuser IP 65 conforming to cat part No HLOB -03-10-CW of Halonix or equivalent in Cromption/Bajaj/C&S complete with 10 watts LED, Driver and surge protector including making new connection with three core PVC copper flexible cable of size 23/.0076
M&Lfor sub main wiring with two single core, PVC insulated,ISI marked, unsheathed, 1100 volts grade multistranded copper conductor cable drawn into and including suitable size non metalic rigid pvc concealed conduit (ISI marked) concealed/surface with all accessories and including one single core pvc insulated multistranded unsheathed 1100 volts grade copper conductor cable as earth wire of 2x4.0 sqmm + 1x4 sqmm earth wire size as in repair incl cutting and chasing and making good thw disturbed surface to match the existing complete all as directed & specified.
Repair to door hinges and door locks of LT panel board/Feeder pillar boxe . Scrubing /scratching of old rusted paint by burning through blow lamps . Painting of LT Panel board/Feeder pillar box any size any description , externally and internally with 02 coats of aproved colour of paint with two coats of superior quality synthetic enamel paint over a acoat of red oxide as primer complete al as specifired and as directed all as as directed by Engr-in-Charge
Supply, install single phase 220 volts 50 Hz pressure booster pump in repair 0.5 HP (0.37 KW) suitable for 1-2 bath rooms max 02 shower Flow rate 33 Ltrs per minute complete with incoming and outgoing pipe connections with GI pipes 15 mm and NRV all as specified and as directed.Make: CRI/Kirloskar/Servo/Crompton/Shakti.
GS Engineers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .