Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.3 LAccepted-AOC | L1 | Accepted-AOC LOWEST BIDDER | |
| 2 | L2₹23.8 L+₹86,846 (3.79%)Rejected-AOC | L2 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 3 | L3₹25.4 L+₹2.5 L (10.7%)Rejected-AOC | L3 | Rejected-AOC OTHER THAN LOWEST BIDDER | |
| 4 | L4₹26.6 L+₹3.6 L (15.9%)Rejected-AOC | L4 | Rejected-AOC OTHER THAN LOWEST BIDDER |
Tender Value
Refer Docs
EMD Value
₹40,000
Closing Date
28 Mar 2020, 6:00 pmClosed
GE of GE (SOUTH) AKHNOOR
GE SOUTH AKHNOOR C/O 56 APO PIN- 900234
REPAIR TO TRANSFORMERS, VOLTAGE STABLIZERS, DG SETS AND OTHER CONNECTED ITEMS INSTALLED AT VARIOUS LOCATIONS UNDER GE (SOUTH) AKHNOOR.
2020_MES_329824_1
NIT-13
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE (SOUTH) AKHNOOR
Class E and Category b(ii)
8 documents required · 8 mandatory
₹500
GE SOUTH AKHNOOR
₹40,000
Yes
17 Jun 2020
9 Mar 2020
30 Mar 2020
9 Mar 2020
28 Mar 2020
16 Mar 2020
Amount
SCHEDULE 'A' PART-I: BOQ OF WORKS FOR E/M WORKS.
Disconnecting electrical connections from HT and LT sides of old serviceable/ damaged/ burnt step down transformers of any descriptions, capacity exceeding 25 KVA but not exceeding 100 KVA, any type and taking down from the platforms or mounted on exisiting position (four poles/ two pole structure) by hydraulic cranes of suitable capacity and transporting by truck/ lorry to the workshop, opening top cover, draining out the transformer oil in clean barrels, cleaning of sludge from oil tank and conservator tank, cleaning and polishing of tapping contact point, opening carefully copper wire/ strip wound LT coils and rewinding the same after providing new necessary insulating packing material by using the same old strip/ wire, refitting top cover with replacement of studs, nuts, bolts, washers and gasket after repairs/ replacement of unserviceable parts and cleaning the transformer and making the transformer absolutely leak proof, pouring in the insulating oil in the transformer, placing in original position on four pole/ two pole structure/ platform at site and making all HT/LT connections including testing the transformer after necessary repairs, complete all as specified and as directed by Engineer-In-Charge. Note: Spares required for repair/ replacement of unserviceable parts shall be measured and paid separately under relevant items of BOQ.
Description all as serial item No- 2.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 160 KVA.
Description all as serial item No- 2.00 here-in-before but for transformer of capacity exceeding 160 KVA but not exceeding 250 KVA.
Description all as serial item No- 2.00 here-in-before but for transformer of capacity exceeding 250 KVA but not exceeding 400 KVA.
Replacement of old unserviceable/ damaged core with new core, mild steel, of existing specifications, shape and sizes including cuting and fixing, suitable for transformers of any type and capacity, complete all as specified and as directed by Engineer-In-Charge.
Supply and fixing in replacement of HT coil of transformer capacity 25 KVA to 400 KVA, made of super enameled copper winding wire/ strip of existing insulation, gauge and specifications, complete all as specified and as directed by Engineer-In-Charge. Note: HT coil shall have same number of turns of winding wire and with matching to manufacturer design. Make: ATLAS/ HTP/ BIC.
Supply and fixing in replacement of LT coil of transformer capacity 25 KVA to 400 KVA, made of super enameled copper winding wire/ strip of existing insulation, gauge and specifications, complete all as specified and as directed. Note: LT coil shall have same number of turns of winding wire and with matching to manufacturer design. Make: ATLAS/ HTP/ BIC.
Replacement of old unserviceable/ damaged HT bushing assembly with new HT bushing assembly (Set of three) with insulated brass stud including nuts, bolts and washers, suitable for transformer of any type, capacity 25 KVA to 100 KVA, complete all as specified and as directed.
Description all as serial item No- 9.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 9.00 here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Replacement of old unserviceable/ damaged LT bushing assembly with new LT bushing assembly (Set of Four) with insulated brass stud including nuts, bolts and washers, suitable for transformer of any type, capacity 25 KVA to 100 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 12.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 12.00 here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Replacement of old unserviceable/ damaged cork sheet gasket with new cork sheet gasket, suitable for transformer of any type, capacity 25 KVA to 100 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 15.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 15.00 here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Replacement of old unserviceable/ damaged tap changing assembly with new tap changing assembly, off load, on HT winding to vary the voltage ±7.5%, in steps of 2.50%, including necessary connection, HT winding, re-insulation for complete functioning of tap changer, transformer capacity 25 KVA to 100 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 18.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 18.00here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Dehydration and filtration of transformer oil after draining out oil from transformer by the dehydration machine at site or nearby transformer workshop to achieve di-electric strength 40 KV at 4mm gap, complete all as specified and as directed by Engineer-In-Charge. Note: (i) Cost of transportation of dehydration machine and other required materials and tools, plants shall be deemed to be included in the quoted rates. (ii) Test certificate of di-electric strength shall be produce before and after dehydradation and filtration process.
Replacement of old unserviceable/ damaged air breather assembly with new air breather assembly with silica gel suitable for 11/0.433 KV transformer including nuts, bolts and washers, suitable for transformer 25 KVA to 100 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 22.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 22.00 here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Supply only fresh transformer oil to top-up and filling in the existing transformer, di-electric strength not than 45 KV, meeting Bureau of Indian Standards: IS 335-1993 (Reaffirmed-2005) specification, examined in a 100mm thick layer at 270°C, clear, transparent and free from all type of suspended matter or sediment, complete all as specified and as directed by Engineer-In-Charge. Make: IOCL/ HPCL/ BPCL/ Reliance.
Preparation of old, external surface of transformers capacity 25 KVA to 100 KVA, by removing the scrap, rust, washing including cleaning and spray painting with two coats of synthetic enamel paint including numbering MES No in white colour synthetic enamel paint, at site or at workshop, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 26.00 here-in-before but for transformer of capacity exceeding 100 KVA but not exceeding 200 KVA capacity.
Description all as serial item No- 26.00 here-in-before but for transformer of capacity exceeding 200 KVA but not exceeding 400 KVA capacity.
Disconnecting electric connections of servo voltage stabilizers, capacity 15 KVA to 30 KVA, draining out the transformer oil in clean barrels for re-use, cleaning of sludge from oil tank and transporting to workshop for repairs and return back to it's original position after repairs including loading and unloading by mechenical means, complete all as specified and as directed by Engineer-In-Charge. Note: Spares required for repair/ replacement of unserviceable parts shall be measured and paid separately under relevant items of BOQ.
Description all as serial item No- 29.00 here-in-before but for servo voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 29.00 here-in-before but for servo voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Replacement of old unserviceable Printed Circuit Board (PCB) with new Printed Circuit Board (PCB) of voltage stabilizer as per existing make and type, capacity 15 KVA to 30 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 32.00 here-in-before but for servo voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 32.00 here-in-before but forservo voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Replacement of old unserviceable carbon bushes with new carbon bushes of voltage stabilizer as per existing make and type, capacity 15 KVA to 30 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 35.00 here-in-before but for servo voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 35.00 here-in-before but for servo voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Replacement of old unserviceable servo motor with new servo motor of voltage stabilizer as per existing make and type, capacity 15 KVA to 30 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 38.00 here-in-before but for voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 38.00 here-in-before but for voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Push button suitable for servo voltage stabilizers of any capacity, as per existing design and range, fixing in repairs, complete all as specified and as directed by Engineer-In-Charge.
Digital voltmeter, range 0-500 Volts, size 96mmx96mm, flush type, complete all as specified and as directed by Engineer-In-Charge.
Digital ammeter, range 0-100 Amps, size 96mmx96mm, square shape, complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable Servo Dimmer Booster Coil with new Servo Dimmer Booster Coil, for automatic voltage corrections, make, type and design as per site requirement, suitable for voltage stabilizer capacity 15 KVA to 30 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 45.00 here-in-before but for voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 45.00 here-in-before but for voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Earthing complete with galvanised iron earth plate electrode 600x600x6mm buried directly in ground (earth pit not less than 2.25mtr deep below ground level) with top edge of earth plate not less than 1.5mtr below normal ground level, connected with galvanised iron strip, size 25x4mm as earth lead, by means of bolts, nuts, check nuts and washers of galvanized iron or steel complete with 40mm dia GI light grade protection pipe, 20mm dia GI medium grade watering pipe with funnel including charcoal, dust, salt, PCC M-15, type B-1 in pit with precast RCC M-15(1:2:4), type B-1 (using 20mm graded crushed stone aggregates) in cover reinforced with XPM not less than 4.0 Kg per Sqm, test point etc. all as shown in electric plate No-3 of SSR Part-I (2009), complete with necessary earth work in any type of soil, removal to a distance not exceeding 50mtr, including testing on completion, complete all as specified and as directed by Engineer-In-Charge. Note: Earth pit chamber and RCC pit cover shall be painted with two coats of red synthetic enamel paint over one coat of primer including preparing of surfaces.
Replacement of old unserviceable Dimmer Gear set with new cast iron Dimmer Gear set, for automatic voltage corrections, make, type and design as per site requirement, suitable for voltage stabilizer capacity 15 KVA to 30 KVA, complete all as specified and as directed by Engineer-In-Charge.
Description all as serial item No- 49.00 here-in-before but for voltage stabilizer of capacity exceeding 30 KVA but not exceeding 60 KVA capacity.
Description all as serial item No- 49.00 here-in-before but for voltage stabilizer of capacity exceeding 60 KVA but not exceeding 100 KVA capacity.
Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/ pipe or fixed to poles or any other indicated situation for loop earthing etc. as required, aluminium strip 25x3.0mm with saddles and fixing, complete all as specified and as directed by Engineer-In-Charge.
Disconnecting all electric connections from alternator and fuel connection from engine, decoupling of engine and alternator, strip opening of diesel driven diesel generator of capacity 30 KVA, for repair, and complete for carrying out the overhauling after de-assembling the engine assembly, cleaning/ washing the engine block and other spare parts, replacing defective spare parts with new spare parts as required for smooth functioning of diesel engine and strip opening of alternator for repair by replacement of old defective spare parts including any type of metaling, welding, grinding, lath machine work required at site/ workshop to compete the repair the engine, all as required at site, re-assembling the engine in existing position complete and testing on completion all as specified and as directed by Engineer-In-Charge. Make: Serial No- Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of cleaning, welding, minor repair and special tools and plants required for dismantling engine will deemed to be included in quoted rate. (c) Transportation cost of diesel engine/ alternator to workshop shall deemed included in quoted rate.
Description all as per serial item No- 53.00 here-in-before but for engine of diesel driven diesel generator of capacity 40 KVA to 63 KVA.
Description all as per serial item No- 53.00 here-in-before but for engine of diesel driven diesel generator of capacity 100 KVA to 125 KVA.
Supply only following new spare parts required for repair of diesel engine of DG Set capacity 30 KVA :-
Piston with piston pin, connecting rod and lock assembly complete.
Cylinder liner with liner ring assembly complete.
Piston ring set.
Major overhauling gasket set with 'O' ring set.
Head valve inlet and exhaust.
Main Oil seal (Front and Rear).
Hose pipe with clips and joint set.
Fuel Filter.
Oil Filter.
Air Filter.
Solinoid switch
Supply only following new spare parts required for repair of diesel engine of DG Set capacity 40 KVA to 63 KVA :-
Piston with piston pin, connecting rod and lock assembly complete.
Cylinder liner with liner ring assembly complete.
Piston ring set.
Major overhauling gasket set with 'O' ring set.
Head valve inlet and exhaust.
Main Oil seal (Front and Rear).
Hose pipe with clips and joint set.
Fuel Filter.
Oil Filter.
Air Filter.
Solinoid switch
Supply only following new spare parts required for repair of diesel engine of DG Set capacity 100 KVA to 125 KVA :-
Piston with piston pin, connecting rod and lock assembly complete.
Cylinder liner with liner ring assembly complete.
Piston ring set.
Major overhauling gasket set with 'O' ring set.
Head valve inlet and exhaust.
Main Oil seal (Front and Rear).
Hose pipe with clips and joint set.
Fuel Filter.
Oil Filter.
Air Filter.
Water Pump Assembly.
Solinoid switch
Disconnecting all electric connections between alternator and panel, decoupling of engine and alternator, strip opening of alternator of diesel driven diesel generator of capacity 30 KVA, for repair, and complete for carrying out the overhauling after de-assembling the alternator assembly, cleaning/ washing the block and other spare parts, replacing defective spare parts with new spare parts as required for smooth functioning of diesel engine, repair alternator by replacement of old defective spare parts including any type of metaling, welding, grinding, lath machine work required at site/ workshop to compete the repair the engine/ alternator, all as required at site, re-assembling the engine in existing position complete and testing on completion all as specified and as directed by Engineer-In-Charge. Make: Serial No- Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of cleaning, welding, minor repair and special tools and plants required for dismantling engine will deemed to be included in quoted rate. (c) Transportation cost of diesel engine/ alternator to workshop shall deemed included in quoted rate.
Supply only following new spare parts required for repair of alternator of DG Set capacity 30 KVA :-
Slip ring assembly Bronze.
Carbon bush.
Carbon bush holder.
AVR (Automatic Voltage Rectifier/ Regulator).
Alternator and diesel engine coupling set.
De-assembling/ taking out radiator of DG set capacity 110 KVA, for cleaning and repair, using ‘K’ oil and radiator cleaning solution hydro-chloric acid by pressure of pump/ caustic soda with wire brush and necessary welding/ brazing of water tubes/ fins, whichever is required for cleaning and repairing, complete all as specified and as directed by Engineer-In-Charge.
Disconnecting all electric connections between alternator and panel, decoupling of engine and alternator, strip opening of alternator of diesel driven diesel generator of capacity 40 KVA to 63 KVA, for repair, and complete for carrying out the overhauling after de-assembling the alternator assembly, cleaning/ washing the block and other spare parts, replacing defective spare parts with new spare parts as required for smooth functioning of diesel engine, repair alternator by replacement of old defective spare parts including any type of metaling, welding, grinding, lath machine work required at site/ workshop to compete the repair the engine/ alternator, all as required at site, re-assembling the engine in existing position complete and testing on completion all as specified and as directed by Engineer-In-Charge. Make: Serial No- Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of cleaning, welding, minor repair and special tools and plants required for dismantling engine will deemed to be included in quoted rate. (c) Transportation cost of diesel engine/ alternator to workshop shall deemed included in quoted rate.
Supply only following new spare parts required for repair of alternator of DG Set capacity 40 KVA to 63 KVA :-
Slip ring assembly Bronze.
Carbon bush.
Carbon bush holder.
AVR (Automatic Voltage Rectifier/ Regulator).
Alternator and diesel engine coupling set.
Replacement of old unserviceable belts with new belts of DG set of following capacities:
Fan belt for DG sets of 30 KVA capacity.
Fan belt for DG sets of 40 KVA to 63 KVA capacity.
Fan belt for DG sets of 100 KVA to 125 KVA capacity.
Repair, calibration, checking and pressure testing of fuel injector pump assembly of DG set capacity 30 KVA including replacement of damaged/ defective parts, cups, barrel plunger and washers including transportation for workshop for repair, testing whole assembly after necessary repair and fixing in engine, complete all as specified and as directed by Engineer-In-Charge. Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of cleaning, welding, minor repair and special tools and plants required for dismantling and refixing with engine will deemed to be included in quoted rate.
Supply only following new spare parts required for repair of fuel injection pump (FIP) of diesel engine of DG Set capacity 30 KVA :-
Element for fuel injection pump.
Delivery valve for fuel injection pump.
Nozzle for fuel injection pump.
Feed pump for fuel injection pump.
Bearing for fuel injection pump.
Oil seal for fuel injection pump.
Diaphram valve for fuel injection pump.
Repair kit minor for fuel injection pump.
De-assembling/ taking out radiator of DG set capacity 63 KVA, for cleaning and repair, using ‘K’ oil and radiator cleaning solution hydro-chloric acid by pressure of pump/ caustic soda with wire brush and necessary welding/ brazing of water tubes/ fins, whichever is required for cleaning and repairing, complete all as specified and as directed by Engineer-In-Charge.
Supply and fixing in replacement of stator/ field coil of alternator of DG set of any capacities, made of super enameled copper winding wire of existing insulation, gauge and specifications, complete all as specified and as directed by Engineer-In-Charge. Note: Stator/ field coil shall have same number of turns of winding wire and with matching to manufacturer design/ specifications. Make: ATLAS/ HTP/ BIC.
Repair, calibration, checking and pressure testing of fuel injector pump assembly of DG set capacity 40 KVA to 63 KVA including replacement of damaged/ defective parts, cups, barrel plunger and washers including transportation for workshop for repair, testing whole assembly after necessary repair and fixing in engine, complete all as specified and as directed by Engineer-In-Charge. Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of cleaning, welding, minor repair and special tools and plants required for dismantling and refixing with engine will deemed to be included in quoted rate.
Supply only following new spare parts required for repair of fuel injection pump (FIP) of diesel engine of DG Set capacity 40 KVA to 63 KVA :-
Element for fuel injection pump.
Delivery valve for fuel injection pump.
Nozzle for fuel injection pump.
Feed pump for fuel injection pump.
Bearing for fuel injection pump.
Oil seal for fuel injection pump.
Diaphram valve for fuel injection pump.
Repair kit minor for fuel injection pump.
Dismantling/ taking out old serviceable alternator charger/ dynamo capacity 12 Volts, of DG set, for repair by replacing burnt spare parts, oiling greasing to movable spare parts, and testing after repairing including re-mounting the same, complete all as specified and as directed by Engineer-In-Charge. Note: Following spare parts shall be replaced: (a) Solenoid switch. (b) Re-windign of Armature and field coil. (c) Pinion steel.
Carryout periodic maintenance/ servicing of DG set capacity 30 KVA to 63 KVA by calibration of fuel injection pump including dismantling of radiator, radiator fan, water pump assembly, air cleaner, rocker cover housing rocker, oiling and greasing to movable spare parts such as bearing etc, replacement of old defective air filter, fuel filter, oil filter, insulation cover/ asbestos rope of exhaust pipe with new and manufacturer specified air filter, fuel filter and oil filter, insulation cover/ asbestos rope of exhaust pipe tightening the screws of hose and hose pipe set, strip opening of alternator cleaning of stator and field coils, rotor assembly, AVR unit and apply one coat of varnishing using ‘H’ class varnish and complete service work as required at site, re-assembling the engine/ alternator in existing position, and testing on completion all as specified and as directed by Engineer-In-Charge. Note: (a) New spare parts will be measured and paid separately as supply only under the respective items. (b) Cost of grease, filters (fuel, oil and air), AC/ insulating rope, cleaning, welding, minor repair and special tools and plants required for dismantling engine will deemed to be included in quoted rate.
Description all as serial item No- 71.00 here-in-before but for DG set of 100 KVA to 125 KVA capacity.
Supply only coolant fluid suitable for radiator of DG sets of any capacity and any make, complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged battery with new storage cell lead acid type 12 Volts, 180 AH including lead terminals and copper thimble, copper nuts, bolts for making necessary connections, complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged battery with new storage cell lead acid type 12 Volts, 150 AH including lead terminals and copper thimble for making necessary connections, complete all as specified and as directed by Engineer-In-Charge.
Replacement of old unserviceable/ damaged Change over switch with new Change over switch, off load, rating 200 Amps, four poles, 415 Volts, AC, 50 Hz, with side handle, conforms to IS:13947 (Part-3); IEC:60947-2, complete all as specified and as directed by Engineer-In-Charge. Make: Indo-Asian cat part No- OFFP0200 or equivalent in L&T/ Legrand/ Merlin Gerin/ Siemens.
Replacement of old unserviceable/ damaged Change over switch with new Change over switch, on load, rating 100 Amps, four poles, 415 Volts, AC, 50 Hz, with side handle, conforms to IS:13947 (Part-3); IEC:60947-2, complete all as specified and as directed by Engineer-In-Charge. Make: Indo-Asian cat part No- OFFP0100 or equivalent in L&T/ Legrand/ Merlin Gerin/ Siemens.
Replacement of old unserviceable/ damaged MCCB with new MCCB, four pole, 415 Volts, adjustable thermal and adjustable magnetic setting, 160 Amps with breaking capacity 36 KA, having indicating lamp, Ics=100% Icu as per IEC 60947-2, complete all as specified and as directed by Engineer-In-Charge. Make: Havells cat part No- IHA13EBF0160 or equivalent in L&T/ Merlin Gerin/ Siemens/ ABB.
Replacement of old unserviceable/ damaged MCCB with new MCCB, four pole, 415 Volts, adjustable thermal and adjustable magnetic setting, 200 Amps with breaking capacity 36 KA, having indicating lamp, Ics=100% Icu as per IEC 60947-2, complete all as specified and as directed by Engineer-In-Charge. Make: Havells cat part No- IHLLSEBF020 or equivalent in L&T/ Merlin Gerin/ Siemens/ ABB.
Supply only copper lead cable 2.0mtrs long, multi-stranded, with copper thimble for making necessary connections at both ends, suitable for 12/ 24 Volts, 180 AH battery including copper lugs, nuts, bolts and washers, complete all as specified and as directed by Engineer-In-Charge.
Supply only engine oil/ lubricant, 20 W 40 grade, suitable for diesel engine of DG set of any capacity and any make, complete all as specified and as directed by Engineer-In-Charge.
Amount of Schedule of credit of for Rs 3,60,460.00 shall be deducted from quoted amount.
THE PERFECT WATER SUPPLY SERVICES
M/S BIJRAL ENTERPRISES
M/S SHARMA ENTERPRISES
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .