| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹2.2 LAccepted-AOC AT DHORI STAFF QTR PO DHORI DIST BOKARO | L1 | Accepted-AOC Techno commercillay qualified | |
| 2 | L2₹1.9 L+₹2,920 (1.54%)Rejected-Finance AT PO PICHHARI DIST BOKARO | L2 | Rejected-Finance Techno commercially not qualified | |
| 3 | L3₹2.0 L+₹11,252 (5.95%)Rejected-Finance 00 KIWADI SAFEDABAD BARABANKI BARABANKI UTTAR PRADESH 225001 | BARABANKI | UTTAR PRADESH | 225001 | L3 | Rejected-Finance Techno commercially not qualified |
Tender Value
Refer Docs
EMD Value
₹2,800
Closing Date
20 Mar 2025, 12:00 pmClosed
MADHU RANJAN KUMAR,PE(EnM),TARMI OCP
OFFICE OF THE PROJECT OFFICER,TARMI OCP,DHORI AREA,CCL
Repair and maintenance of wiring at Tarmi OCP Sub-station, Karipani Sub-station, Durga Mandap and rest shelter and making safety board under Tarmi OCP .
2025_CCL_331856_1
TOCP/PE(EnM)/e.NIT/24-25/17 DT.09.03.2025
Open Tender
Electrical and Maintenance Works
Item Wise
7 days
TARMI OCP
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,800
15 Apr 2025
10 Mar 2025
21 Mar 2025
10 Mar 2025
20 Mar 2025
10 Mar 2025
10 Mar 2025 - 13 Mar 2025
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required: Group A a) Bulb point-27 Nos b) Fan point-9 Nos c) Tube light point-9 Nos
Supplying and fixing metal box of 180 mm x 100 mm x 60 mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection, etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/isolator). : 6 way, double door.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, ‘’C’’ curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole & neutral.
Providing and fixing following capacity TP&N disconnector fuse switch unit inside the existing panel board with ISI marked HRC fuses including drilling holes in cubicle panel, making connections, etc. as required. 32 Amp TP&N.
Supplying and fixing stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate as required.
Earthing with G.I. earth plate 600 mm x 600 mm x 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long with charcoal/ coke and salt as required.
Providing and fixing 25 mm x 5 mm dia G.I. strip on surface or in recess for connections etc. as required.
Supplying and drawing following sizes FRLS PVC insulated copper conductor, single core cable in existing surface/ recessed steel/ PVC conduit as required. : 3 x 4 sq.mm
Supplying and fixing 3 pin, 5 amps ceiling rose on the existing junction box/wooden block including connection etc. as required.
Supplying and fixing brass batten/ angle holder including connection etc. as required.
Earth work in excavation by mechanical means (Hydraulic Excavator )/ manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan) including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m. All kinds of soil.1m x 0.5m x 0.5m x 2 post x 6 nos. = 3.00 cum
PCC/Muffing, fixing and cost of centering, shuttering, fixing 1:2:4 mix.6 x 0.5 x 0.5 x 2 = 3.00 cum
Total length of M.S. angle (50 x 50 x 6mm) 9.65 mtrs, weight of the M.S. angle (50 x 50 x 6) = 9.65 x 4.5 Kgs. = 43.42 Kgs.M.S. plate (3.15mm) = 12 sft. = 1.12 sqm, weight of M.S. plate (3.15mm) = 1.12 sqm x 24.7kg/sqm = 27.66 Kgs.Total weight of the steel structure board = 43.42 x Plate 27.66 Kgs. = 71.08 Kgs. X 6 nos. = 426.48 Kgs.
Finishing with Epoxy paint (Two or more coats) at all locations prepared and applied as per manufacturer’s specification including appropriate priming coat, preparation of surface etc. complete : On steel work.(1.12 sqm x 2) + (9.65 m x 0.20m) x 6 nos.
Writing of safety slogans, instructions, warnings etc.
Total impact of GST for the purpose of CTC
M/s Saloni Sales (BID ID -1139032)
M/S KUMAR ENTERPRISES (BID ID -1139765)
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .