| 1 | L1₹3.5 LAccepted-AOC 12 NO 12 IRATTAI PILLAYAR KOVIL STREET NEAR REAL VALUE FLAT VELACHERY 733 CHENNAI TAMIL NADU 600042 | CHENNAI | TAMIL NADU | 600042 | L1 | Accepted-AOC Being lowest bidder | |
| 2 | L2₹4.4 L+₹89,398 (25.3%)Rejected-Finance VILL JAMGAHAH PO JAMGARAH LAUDOHA BURDWAN BURDWAN EASTCHM WEST BURDWAN BARDHAMAN 713363 WEST BENGAL INDIA | BURDWAN | BURDWAN BARDHAMAN | WEST BENGAL | 713363 | L2 | Rejected-Finance Other than lowest bidder |
| Sl No | Description | Qty | Unit | Elite Enterprises L1 | M/S KARMAKAR AND COMPANY L2 |
|---|---|---|---|---|---|
| 1.00 | Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size 700mm x 600mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE. The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length, MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement. Minimum claerance from ground level is 450 mm complete all as specified and comprising :- (a) MCCB, 100 Amps, FP, 25 KA, 415 volts, 50 Hz - 01 No (in coming) (b) MCB, 40 Amps, TPN, 10 KA, 415 volts, 50 Hz, "C" Serie - 02 Nos ( outgoing) (c) MCB, 16 Amps, SPN, 10KA, 415 volts, 50 Hz, "C" Series - 02 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) with CTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f) LED phase indication lamps RYB-01 set (g) Aluminium bus bar TPN 200 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge). | 1 | Each Job | 80,000 ₹80,000 Lowest | 1,00,000 ₹1,00,000 |
| 2.00 | Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size 700mm x 600mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE. The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length, MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement. Minimum claerance from ground level is 450 mm complete all as specified and comprising :- (a) MCCB, 63 Amps, FP, 25 KA, 415 volts, 50 Hz - 01 No (in coming) (b) MCB, 20 Amps, TPN, 10 KA, 415 volts, 50 Hz, "C" Serie - 01 No ( outgoing) (c) Industrial plug and socket , 415V , 32Amps, 3P + E - 02 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) with CTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f) LED phase indication lamps RYB-01 set (g) Aluminium bus bar TPN 200 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge). | 1 | Each Job | 90,000 ₹90,000 Lowest | 1,00,000 ₹1,00,000 |
| 3.00 | Supply,laying, jointing and testing, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 50 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed.
(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). | 180 | RM | 465 ₹83,700 Lowest | 640 ₹1,15,200 |
| 4.00 | Supply,laying, jointing and testing, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 25 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete all as specified and directed.
(Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE). | 80 | RM | 295 ₹23,600 Lowest | 320 ₹25,600 |
| 5.00 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth not exceeding 10sqm on plan for laying of cable and foundation of poles stays and getting out in any type of soil complete all as specified and directed. | 56 | Cum | 160 ₹8,960 Lowest | 300 ₹16,800 |
| 6.00 | Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm (soil) thickness all as specified and directed. | 33.5 | Cum | 80 ₹2,680 Lowest | 250 ₹8,375 |
| 7.00 | Removing of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed. | 22.5 | Cum | 90 ₹2,025 Lowest | 200 ₹4,500 |
| 8.00 | M&L for dry sand cushioning to underground cable, provided with a layer 8 cm thick before and 15 cm deep after laying and stretching jointing and testing the cable complete all as specified and as directed.
(Note: Punned thickness of sand shall be measured and paid). | 16.85 | Cum | 1,100 ₹18,535 Lowest | 1,500 ₹25,275 |
| 9.00 | M&L for brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230mm x 115mm x 75mm, complete all as specified and as directed. | 1,664 | Each | 8 ₹13,312 Lowest | 15 ₹24,960 |
| 10.00 | M&L for 50mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection complete all as specified and directed. | 50 | RM | 450 ₹22,500 | 300 ₹15,000 Lowest |
Tender Value
₹3.9 L
EMD Value
₹7,840
Closing Date
6 Dec 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
GE AF PANAGARH
GE AF PANAGARH MES AF STATION PANAGARH PO BIRUDIAH WEST BENGAL 713148
PROVISION OF COMMERCIAL POWER SUPPLY POINT AT TECHNICAL AREA OF AIR FORCE STATION ARJAN SINGH UNDER GE (AF) PANAGARH
2025_MES_740566_1
C/8860/E8
Open Tender
Electrical and Maintenance Works
Item Rate
90 days
AF STATION PANAGARH
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹300
GE AF PANAGARH
₹7,840
9 Jan 2026
19 Nov 2025
8 Dec 2025
19 Nov 2025
6 Dec 2025
29 Nov 2025
Amount
Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size 700mm x 600mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE. The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length, MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement. Minimum claerance from ground level is 450 mm complete all as specified and comprising :- (a) MCCB, 100 Amps, FP, 25 KA, 415 volts, 50 Hz - 01 No (in coming) (b) MCB, 40 Amps, TPN, 10 KA, 415 volts, 50 Hz, "C" Serie - 02 Nos ( outgoing) (c) MCB, 16 Amps, SPN, 10KA, 415 volts, 50 Hz, "C" Series - 02 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) with CTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f) LED phase indication lamps RYB-01 set (g) Aluminium bus bar TPN 200 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge).
Design, fabrication,supply, insallation, testing and commissioning LT panel board (outdoor type floor mounted)of size 700mm x 600mm x 400mm suitable for working on 3 phase, 4 wire, 415 volts, AC, 50 Hz outdoor type, cubicle, floor mounted, free standing, dust and vermin proof, air ventilation, factory fabricated made out of 3.2mm thick CRCA sheet duly powder coated (seven tank process) and as approved by GE. The panel shall have front and rear opening, locking arrangement, bus bar chamber and switch gear compartment, hinged door with rubber gasket, botton cable entry holes for incoming and out going cables, earthing terminals, affix danger notice plate, aluminium bus bar duly covered with heat shrink sleeves colour coded duly fixed on DMC/SMC insulators, aluminium strip connection from bus bar to outgoing MCCBs and copper conductor cable of adequte size of MCBs, housed in a separate bus bar chamber and control wiring adequate size and length, MCCBs shall have extended bus bar links and panel mounted on 50x50x5mm size MS angle iron frame duly painted in and including PCC 1:2:4 type B-1 (using 20mm graded stone aggregate) in foundation design subject to approval of GE as per as site requirement. Minimum claerance from ground level is 450 mm complete all as specified and comprising :- (a) MCCB, 63 Amps, FP, 25 KA, 415 volts, 50 Hz - 01 No (in coming) (b) MCB, 20 Amps, TPN, 10 KA, 415 volts, 50 Hz, "C" Serie - 01 No ( outgoing) (c) Industrial plug and socket , 415V , 32Amps, 3P + E - 02 Nos (outgoing) (d) Digital multi-fuctional meters for measuring current, voltage and frequency including CTs of suitable rating and class- 01 No (as out going) (e) Digital voltmeter (0-500V) with CTs and VSS-01 set, Digital Ammeter (0-100A), with CTs & ASS-01 set (f) LED phase indication lamps RYB-01 set (g) Aluminium bus bar TPN 200 Amps rating - 01 set (Note: LT panel drawing to be approved by GE duly recommended by Engr-in-Charge).
Supply,laying, jointing and testing, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 50 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete. all as specified and directed. (Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE).
Supply,laying, jointing and testing, XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, armoured heavy duty electric cable with aluminium conductor 1100 volts grade of size 25 sqmm 3.5 core laid in trenches/ on wall, ducts, pipes, on poles and connection with necessary cables lugs, glands, suitable for mild steel saddle clips (were cable laid in ceilings/wall without cable duct) nut bolts complete all as specified and directed. (Note :- Excavation of earth work, removing, returning filling in, sand cushioning, concrete cable cover and protection GI pipe shall be measured and paid separately and length of cable shall be one length unless otherwise as directed by GE).
Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth not exceeding 10sqm on plan for laying of cable and foundation of poles stays and getting out in any type of soil complete all as specified and directed.
Returning, filling in including spreading, leveling, watering and well ramming in layers not exceeding 25 cm (soil) thickness all as specified and directed.
Removing of excavated material (soil) to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed.
M&L for dry sand cushioning to underground cable, provided with a layer 8 cm thick before and 15 cm deep after laying and stretching jointing and testing the cable complete all as specified and as directed. (Note: Punned thickness of sand shall be measured and paid).
M&L for brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230mm x 115mm x 75mm, complete all as specified and as directed.
M&L for 50mm dia galvanized steel tubing (light grade) with complete all fittings such as elbow, unions, nipples, tees, bends, short pieces, connections, check-nuts, caps, plugs, diminishing pieces and flanges etc as in pole, crossing of roads, laid in trenches, fixed on walls for cable protection complete all as specified and directed.
M&L for boring of holes under road, pavement, hard standing by trenchless technology/manual excavation as necessary including machine, tools etc as per site requirement complete all as specified and directed.
M&L for PCC (1:4:8) type D-2 with 40mm graded aggregate as in foundation filling & mass concrete in column & wall foundation complete all as specified.
M/S KARMAKAR AND COMPANY (BID ID -3491237)
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.22 MB
BOQ_829257.xls
BOQ • 2.32 MB
Tender8860.pdf
Tender Documents • 0.75 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .