Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹30.9 LAccepted-AOC | ₹30.9 L Quoted ₹32.5 L | L1 | Accepted-AOC Being lowest |
| 2 | L2₹33.6 LRejected-Finance 01 CHAWADI BAZAR ROAD INFRONT OF CHAWADI BAZAR POWER HOUSE BHAU KA BAZAR GWALIOR GWALIOR MADHYA PRADESH 474001 UDYAM MP 20 0071047 | GWALIOR | MADHYA PRADESH | 474001 | ₹33.6 L | L2 | Rejected-Finance Being 2nd lowest |
| 3 | L3₹34.8 LRejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹34.8 L | L3 | Rejected-Finance Being 3rd lowest |
| Sl No | Description | Qty | Unit | Sharma Electrical and Engineering Works L1 | Raman Electric Trading Co L3 | VIJAY ENTERPRISES L2 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide & not exc 1.5 mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and directed. | 150 | Cum | 140 ₹21,000 | 150 ₹22,500 | 110 ₹16,500 |
| 2.00 | Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick after the cable have been laid and tested complete all as specified and directed. | 95 | Cum | 80 ₹7,600 | 20 ₹1,900 | 30 ₹2,850 |
| 3.00 | Removal of excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed. | 65 | Cum | 80 ₹5,200 | 20 ₹1,300 | 30 ₹1,950 |
| 4.00 | M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying ( total 23 cm ) and compaction till 18 cm thick for measurement purpose complete all as specified and directed. | 45 | Cum | 300 ₹13,500 | 250 ₹11,250 | 400 ₹18,000 |
| 5.00 | M & L for common burnt clay bricks, sub class 'B' grade laid in trenches for protection of UG cables perpendicular to the direction of the cables complete all as specified and directed. | 5 | Per 1000 Nos | 4,500 ₹22,500 | 3,500 ₹17,500 | 3,000 ₹15,000 |
| 6.00 | M & L for Cement concrete (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation of pole or similar works complete all as specified and directed. | 0.1 | Cum | 4,500 ₹450 | 2,000 ₹200 | 4,500 ₹450 |
| 7.00 | M & L for Cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) in foundations, filling and mass concrete for fixing of pole complete all as specified and directed. | 1 | Cum | 4,500 ₹4,500 | 2,000 ₹2,000 | 4,000 ₹4,000 |
| 8.00 | M & L for cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) for copings of poles/stay/panels complete all as specified and directed. | 0.2 | Cum | 5,000 ₹1,000 | 2,000 ₹400 | 7,000 ₹1,400 |
| 9.00 | M & L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed. | 1 | Each | 5,500 ₹5,500 | 3,700 ₹3,700 | 5,000 ₹5,000 |
| 10.00 | M & L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed. | 1 | Each | 3,000 ₹3,000 | 1,900 ₹1,900 | 5,000 ₹5,000 |
Updated dates
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
5 Dec 2025, 6:00 pmClosed
SHRI PRASANTA KACHARI GE (AF) SARSAWA
Garrison Engineer (AF) Sarsawa, Distt. Saharanpur (U.P), PIN- 247232
REPAIR/ MAINT OF EXTERNAL ELECTRIC EQPTS, LT DISTRIBUTION EQPTS, COOLING/ HEATING APPLIANCES, LT SUPPLY/ DISTRIBUTION SYSTEM OF LT LINE AND ALLIED WORKS OF EXTERNAL ELECTRIFICATION, DG SET AND REPAIR/ REPLACEMENT OF INTERNAL ELECTRIC WIRING, LIGHT F
2025_MES_738739_1
8125/SAR-T-60/2025-26
Open Tender
Civil Works
330 days
GE(AF) SARSAWA
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
Yes
GE(AF) SARSAWA
₹90,000
Yes
11 Feb 2026
7 Nov 2025
12 Dec 2025
7 Nov 2025
5 Dec 2025
21 Nov 2025
7 Nov 2025 - 21 Nov 2025
Amount
Excavation in trenches in soft/loose soil not exceeding 1.5 meter wide & not exc 1.5 mtr deep and getting out for taking out/laying cable, poles & stay etc complete all as specified and directed.
Returning, filling in including spreading levelling watering and well ramming in layers not exceeding 25cm thick after the cable have been laid and tested complete all as specified and directed.
Removal of excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M & L for dry sand cushioning to underground cables with 8cm thick before laying of cables and 15cm thick after laying ( total 23 cm ) and compaction till 18 cm thick for measurement purpose complete all as specified and directed.
M & L for common burnt clay bricks, sub class 'B' grade laid in trenches for protection of UG cables perpendicular to the direction of the cables complete all as specified and directed.
M & L for Cement concrete (1:4:8) type D-2 (using 40mm graded stone aggregate) as in foundation of pole or similar works complete all as specified and directed.
M & L for Cement concrete (1:3:6) type C-2 (using 40mm graded stone aggregate) in foundations, filling and mass concrete for fixing of pole complete all as specified and directed.
M & L for cement concrete (1:2:4) type B-1 (using 20mm graded stone aggregate) for copings of poles/stay/panels complete all as specified and directed.
M & L Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed.
M & L Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed.
S & F Danger notice plate of 1.6mm thick mild steel sheet vitreous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for HT size 25 X 20 Cm and taking out of u/s one complete all as specified and directed.
M & L for Disc type insulator, porcelain, vitreous, white, brown or green insulator (Single disc assembly) of size 145 mm height, 255 mm dia ball socket type for working pressure 11 kv volts grade including one galvanised mild steel spindle, two galvanised iron washer and one galvanised iron nut and taking out of u/s one complete all as specified and directed.
S & F lightening arrestor linear resistance type distribution class 9 KV RMS suitable for 11 KV system pole mounting type conforming to IS - 3070 Part-I including taking down existing u/s one complete all as specified and directed.
S & F drop out fuse assembly complete set with Insulator-06 Nos and connected accessories for 11000 V grade of 400 Amp s capacity including taking down u/s DO fuse assmbly complete all as specified and directed.
All as per Item No 14.00 here-in-above but for Expulsion fuse single pole capacity of Voltage 11KV and current up to 25 Amps complete all as specified and directed.
All as per Item No 14.00 here-in-above but for capacity of Voltage 11KV and current above 25 & upto 50 Amps complete all as specified and directed.
All as per Item No 14.00 here-in-above but for capacity of Voltage 11KV and current above 50 & upto 100 Amps complete all as specified and directed.
Taking down and repairing/overhauling of air break gang operated switch with DO fuse unit 200 Amp/400 Amp capacity triple pole mechanically operated mounted on insulators and steel frame installed vertically / horizontally, replacement of broken/worn-out components, oiling and greasing of mechanical moving parts, smoothing and polishing of electric contacts with providing conducting jelly of contacts refixed the same after repair including proper allienment complete all as specified and directed. Note: Warn out component/ insulators shall be measured and paid separately.
Supply only following components to incorporated for repair of air break gang operated switch complete all as specified and directed:- (a) Female contact or fixed contact heavy duty and high conductive metal complete capacity 200A/400 Amp11 KV.
(b) Male contact or Moving contact heavy duty and high conductive metal complete capacity 200A/400Amp 11 KV.
(c) Tinned copper flexible jumper 200A/400A
(d)Fixed top contact & Fixed bottom contact 11 KV 400 Amp for DO fuse unit.
(e) Fiber glass tube with metalic fittings both ends suitable for DO fuse 11KV
(f) Supply only mild steel jumper carrier as per sample.
(g) Supply only back connector plate as per sample.
(h) Supply only post insulator 11 KV as per sample.
Disconnect HT & LT connections from any type of transformers indoor/outdoor, plinth/ pole mounted in any location in the restricted areas of PTS shifting to workshop for carry out any repair works, as directed install back in original location including re-connection of HT & LT supply system of capacity complete all as specified and directed. (a) 200 KVA Note: (a) Required tools & plant including lifting arrangement, transport etc shall be included in the rate quoted. (b) Any damage occurred during lifting/ transporting, the firm will be responsible to rectify such defect free of cost.
All as per Item No 27.00 here-in-above but for dry type 315 KVA complete all as specified and directed.
Shifting of trolly mounted transformer to the site and disconnecting the defective transformer from HT and LT side connection and connecting the trolly mounted stand by transformer by making neccessary HT /LT side connection properly for temporary basis and disconnecting the same after repair of removed /issolated transformer and connecting work shop repaired transformer complete all as specified and directed.
Repair / Servicing / maintenance of transformer 11 / 0.433 KV indoor / outdoor type, plinth / pole mounted type including the following work services :- (a) Disconnecting transformer from electric system and providing electric power to user from alternative arrangement including taking out from existing position. (b) Decanning of transformer oil, opening top cover, disconnecting of all internal connections , lifting and taking out of core assemble, LT / HT bushsing , Tap changer etc, cleaning and inspection of core and winding , segrigetion of serviceable and unsv items, removing of sludge and cleaning tank and cooling pipes / fins /tanks with pressure water and drying the tank complete. (c) Replacing Unsv LT / HT bushing by replacing rubber / cork oil seals and damage terminal rod & replacement of Transformer cover gasket of rubber cork sheet. (d) Re installation of TFR including reassembling of core / winding assebly complete including replacement of unsv parts, repair the defective parts and tighting of all loose / sparks wire / nut bolts etc and refixing the to the existing position , connecting with HT/LT cables and earthing strip and testing complete including necessary Transportation (If required) to the work shop and back and including Dehyderation and refilling of existing or new transformer oil of required quantity. Transformer capacities 200 KVA NOTE: (i) Dehydration of oil and new Transformer oil shall be measured and paid seperately. (ii) Transportation of TFR measured and paid seperately. (iii) HT & LT Busing , Tap Changer will be measured & Paid separataly. (iv) In case HV / LV Winding found damages then Contactor shall be made serviceable with new winding and the same will be measured and paid seperately . (v) The rate of corck sheet & Packing Material for following cap of TFR are included in coated rate for 200 KVA transformer.
As per Item No 30.00 here-ina-bove but for Transformer of capacity 315 KVA complete all as specified and directed.
M & L for removing of existing damage insulating material from LV Winding , Cleaning the winding and reinsulating the LV Winding with approved grade and make of insulating paper and heating the coil in the heat chamber to obtained desired result of insulating resistence complete and re-installation complete all as specified and directed.
M & L for winding of HV side copper winding with super enammeled copper wire of existing size , gauge and weight of approved grade wire including necessary insulating material and heating the coil in the heat chamber to obtained desired result of insulating resistence complete and re-installation complete all as specified and directed.
M & L for winding of LV side copper winding with existing size / type and weight of copper strip winding of approved grade including rapping of insulating tap and insulating material and heating the coil in the heat chamber is obtained desired result of insulating material complete all as specified and directed. NOTE FOR ITEM NO 33 & 34: (i) Contractor shall be open the core assrmbly and segrigatted the serviceable / unser winding and shown to the EIC before and after incorportation to the TFR. (ii) Actual weight of the new winding shall be measured and paid. (iii) In case of damages of the LV Windings and required re insulation of LV Winding then shall be measured and paid separately.
Supply and replace of silica gel cristal complete all as specified and directed.
S & F in repalcement of heavy duty breather assembly with Silica jel cristal for Transformer as per existing shape and size complete all as specified and directed.
Supply and fixing of new temprature guage (0 degree to 120 degree C) range dial temprature as directed including taking down old unserviceable guage complete all as specified and directed.
M & L for transformer oil level indicator assembly complete with iron frame, glass, rubber packing sheet, nuts, bolts and washers etc as per existing complete all as specified and directed.
M & L for Synthetic insulating rubber mat of size 2 m x 1m x 2.5 mm thick with ISI mark suitable for 11 KV rating in red colour complete all as specified and directed.
M & L for removing the burnt out/ damaged LV bushes with porcelain insulator and replace with Brass LV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity 200 KVA complete all as specified and directed.
All as per Item No 40.00 here-in-above but capacity of transformer 315 KVA complete all as specified and directed.
M & L for removing the burnt out/ damaged HV bushes with porcelain insulator and replace with Brass LV bushes, nuts , check nuts, rubber washer etc complete as per the existing size / model, for transformers of capacity 200 KVA complete all as specified and directed.
All as per Item No 42.00 here-in-above but capacity of transformer 315 KVA complete all as specified and directed.
Dehydration of 11 KV existing transformers oil minimum three cycles to achieve dielectric strength up to 60 KV in 2.5 mm gap electrode including toping up of oil if required at site complete all as specified and directed. Note: (i) Dehydration of transformer oil shall be carried out at site and contractor shall be taken the testing result before and after dehydration of oil and shown to the EIC at site and maintain necessary documents for record. (ii) Dehydration Machine with all T&P & Transformer oil testing machine for dehydration of Transformer oil and necessary transportation for the machines is arrange by contractor. (iii) Oil required for topping up the transformer stabilizer will be measured & paid separately.
Supply and topping up of new low viscosity transformer oil from sealed drums confirming to IS 335-1993 Part-II after testing the correct dielectric strength up to 60 KV at 2.5 mm gap duly de-hydrated complete all as specified and directed.
S & F off load Tap changer switch of existing model / type of Transformer of capacity 200 KVA complete all as specified and directed.
S & F off load Tap changer switch of existing model / type of Transformer of capacity 315 KVA complete all as specified and directed. Note: (i) Fixing charges will be includede in item coated for Sl Item No 46 & 47.
M & L for preparation of old painted surfaces steel by brushing/changing stain, greasy spots with thinner and apply two coats of spray painting with super enameled smokes grey colour paint of approved make by Dept.for indoor/outdoor transformer installed at various different locations complete all as specified and directed. (a) 200KVA
All as per Item No 48.00 here-in-above but for CSS 315 KVA complete all as specified and directed.
M & L for Calibration of Protective relay programmable type in CSS panel with carrying out secondary injection test, set the relays in accordance with the supply agency Protection/Tripping range so as to trip the MES breaker before tripping the fault to supplier grid/ system. All parameter in MES breaker tripping setting in relays shall be arranged in such away that any fault occured in the feeders after the recieving station must not transfer to the suppliers system complete all as specified and directed.
S & F in repair 3 phase 24 -240 Volts AC/DC supply over current + earth fault relay with high set having define time characteristics and last 30 trips data recording with date and time as well as password protection complete including necessary electric connections and testing complete all as directed and specified.
S & F in repair heavy duty Contractor for three phase capacitors including necessary connections all as directed for the following capacity complete all as specified and directed:- (a) 3 pole power contactor type MNX-110.
All as per Item No 52.00 here-in-above but for 3 pole power contactor type MNX-70 complete all as specified and directed
All as per Item No 52.00 here-in-above but for 3 pole power contactor type MNX-32 complete all as specified and directed
All as per Item No 52.00 here-in-above but for 3 pole power contactor type MNX-18 complete all as specified and directed
M & L for Earthing to Sub stn with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI wire 4 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 of MES Schedule pt-I 1991, GI earth lead wire protected by GI pipe 15mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed. Note : Main earth lead beyond 7.5 meter shall measured and paid saperatly.
S & F in repair ACB 4 pole 415 volts , 630 amps , AC 50 Hz with breaking capacity 50 KA conforming to IS/IEC-60947-2 with themal magnetic release and manual drawout type (Thermally adustable type) inclding electrical connection as per site requirement complete all as specified and directed.
M & L Cable jointing kit for 11 KV (Earthed) grade cable for straight through heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armourend aluminium conductor cable of size 240 sqmm to 400 sqmm complete all as specified and directed.
Supply, laying & testing in repair for XLPE insulated, armoured, heavy duty electric cable with stranded aluminium conductor, 1100 volts grade, laid in trenches, sleeving through pipes or fixed on poles & walls or laid under floors including jointing with suitable size aluminium lugs complete of size 16 Sqmm nominal cross section x 2 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 25 Sqmm X 3.5 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 35 Sqmm X 3.5 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 70 Sqmm X 3.5 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 95 Sqmm X 3.5 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 120 Sqmm X 3.5 core complete all as specified and directed.
All as per Item No 59.00 here-in-above but for size of cable 240 Sqmm X 3.5 core complete all as specified and directed.
S & F in repair GI tubing, light grade, 40 mm bore with all fitting lais in trenches / pole / wall for protection of cables complete all as specified and directed.
S & F in repair GI tubing, light grade, 80 mm bore with all fitting lais in trenches / pole / wall for protection of cables complete all as specified and directed.
S & F in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 25 to 50 sq mm complete all as specified and directed.
S & F in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 70 to 150 sq mm complete all as specified and directed.
S & F in repair cable jointing kit for 1.1 KV grade cable for straight through joint complete with Jointing material of tubular sleeve version and accessories suitable for 3½/ 4 core XLPE armoured Al conductor cable of size 185 to 400 sq mm complete all as specified and directed.
S & F steel tubular pole, swaged, complete with cast iron base plate, finial taper plug, bolts, nuts, washer and screws including painting with two coats of aluminium paint over one coat of red oxide primer on all exposed surfaces and tarring with black bituminous paints to portion embedded in PCC including numbering of poles with two coats of synthetic enamel paints, type 410-SP-31 (9 meter long) complete, Including disconnecting and taking out old damage PCC pole complete all as specified and directed. Note: Earth work and PCC shall be measured and paid separately.
S & F ON load four pole changeover switch with front handle of 4 pole 415 volt 50 Hz 250 amps in SS Enclosure and Conforming to IS/IEC : 60947-1 & 3 complete all as specified and directed.
All as per Item No 72.00 here-in-above but for 4 pole 415 volt 50 Hz 200 amps complete all as specified and directed.
All as per Item No 72.00 here-in-above but for 4 pole 415 volt 50 Hz 125 amps complete all as specified and directed.
All as per Item No 72.00 here-in-above but for 4 pole 415 volt 50 Hz 100 amps complete all as specified and directed.
Supply only Aluminium lugs of any type complete all as per of sample of following sizes complete all as specified and directed:- (a) 16 Sqmm
All as per Item No 76.00 here-in-above but for size of 25 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 50 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 70 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 95 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 120 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 150 Sqmm complete all as specified and directed.
All as per Item No 76.00 here-in-above but for size of 240 Sqmm complete all as specified and directed.
S & F in repair including making connection testing and commissioning of new MCCB 3 Pole, 415 V, fixed type, 25 to 100 Amps with breaking capacity 16 KA complete all as specified and directed. Note: (a) make of MCCB shall be L &T , Havells, Strandard, crompton, C & S, Schneider or any other make as per the make in the existing plannel board or exactly suitable to the existing frame size. In case only one particular make is procuring by the bidder necceasry alteration required to fix the same at no extra cost shall be done by the bidder. (b) Type of MCCB weather with operating knob or handle type shall be procured as per site requirement.
All as per Item No 84.00 here-in-above but for MCCB TP 160 Amps, 36 KA with adjustable thermal setting ( 80 to 100 %) complete all as specified and directed.
All as per Item No 84.00 here-in-above but for MCCB TP 250 Amps, 36 KA with adjustable thermal setting ( 80 to 100 %) complete all as specified and directed.
All as per Item No 84.00 here-in-above but for MCCB TP 125 Amps, 36 KA with adjustable thermal setting ( 80 to 100 %) complete all as specified and directed.
All as per Item No 84.00 here-in-above but for 4 Pole, 415 V, Adjustable type, 160 Amps with breaking capacity 36 KA complete all as specified and directed.
All as per Item No 84.00 here-in-above but for 4 Pole, 415 V, Adjustable type, 250 Amps with breaking capacity 36 KA complete all as specified and directed.
All as per Item No 84.00 here-in-above but for 4 Pole, 415 V, Adjustable type, 400 Amps with breaking capacity 36 KA complete all as specified and directed.
All as per Item No 91.00 here-in-above but for capacity of 250KVA complete all as specified and directed.
S & F in replacement oil pipe (Copper flexible tube) with check nuts for DG sets of any make / capacity complete all as specified and directed.
Supply and replace 'V' belt as per sample for DG sets of capacity 125/100 KVA complete all as specified and directed.
All as per Item No 94.00 here-in-above but for capacity of DG Set 250 KVA complete all as specified and directed.
Supply and replace fuel flexible pipe, FIP to Filter, heavy duty with check nuts and benjo bolts, for DG sets of capacity upto 250 KVA complete all as specified and directed.
Supply and replace air cleaner filter assembly complete suitable for DG set of capacity 125/100 KVA complete all as specified and directed.
All as per Item No 97.00 here-in-above but for capacity of 250 KVA complete all as specified and directed.
S & F in repair oil pressure gauge complete all as specified and directed.
S & F in repair temperature gauge complete all as specified and directed.
S & F in repair lub oil filter for DG sets of any make / capacity complete all as specified and directed.
S & F in repair fuel filter for DG sets of any make / capacity complete all as specified and directed.
S & F in repair ignition switch, 12 V with keys complete all as specified and directed.
Dismantling and taking down radiator assembly from engine of DG Set of capacity 125/100 KVA for repairs including de-scaling, bracing of inner tubes and body as required to plug leakages, repairs to radiator frame and tank including cutting and removing deteriorated inner tubes, chamber, frame etc. and re-constructing the same with same material in original size and shape, cleaning / straightening of fins and re fixing after repairs including replacement of worn out nut bolts, washers, aluminium water elbow, radiator cap, radiator beds etc, and pressure testing for leakage complete all as specified and directed.
All as per Item No 104.00 here-in-above but for capacity of DG Set 250 KVA complete all as specified and directed.
S & F in replacement radiator assembly complete including all accessaries such as radiator core comprising copper tubes, fins, upper and lower tanks, radiator frame, inlet and outlet pipes, radiator cap etc for DG set of capacity 125/100 KVA complete all as specified and directed. Make - Kirloskar.
All as per Item No 106.00 here-in-above but for capacity of DG Set 250 KVA complete all as specified and directed.
S & F in replacement of maintanance free unserviceable battery 12 V, 150 AH with initial charging and testing complete all as specified and directed.
All as per Item No 108.00 here-in-above but for size of battery 12 V, 90 AH complete all as specified and as directed.
M & L for cleaning of fuel tank of DG sets of capacity 125/100 KVA emptying the fuel carefully and removing all sedimented particles including scales using wire brushes and kerosene including replacement of worn out transparent fuel level indicating tube including necessary fixing arrangements and marking fuel levels on the tank using white synthetic enamel paint all as specified and directed.
All as per Item No 110.00 here-in-above but for capacity of DG Set 250 KVA complete all as specified and directed.
M & L for replacement of battery terminal of brass suitable for 12V, 90 AH to 150 AH battery complete all as specified and directed.
M & L for replacement of battery lead, copper conductor, single core, 25 Sq mm, multi stranded, PVC insulated with suitable terminals at both ends of lengths as per site requirements all as specified and directed.
S &F in repairs rubber hose pipe kit complete for radiator suitable for DG Sets capacity 125/100 KVA complete all as specified and directed.
All as per Item No 114.00 here-in-above but for capacity of DG Set 250 KVA complete all as specified and directed.
Supply and fillling coolent suitable for DG set complete all as specified and directed.
Supply in replacement, Engine oil, multi grade 20 W 40 or equivalent grade complete all as specified and directed.
M & L for attending complatints of street light, flood light, mounted at any height in pole/hanger in old/new camp of PTS by checking connection , serviceability of fittingd, SMC boxes , MCB, thimbles or any other minor fault complete all as specified and directed. Note: (a) Arrangement of Ladder shall be done by contractor. (b) Arrangement of hydra or other T&P for attending complaints of Hanger light shall be done by contractor.
S & F 35 watt LED type street light 230 volts AC outdoor type with t IP 65 class protection with aluminium die cast housing glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours complet all as specified and directed.
All as per Item No 119.00 here-in-above but for street light of capacity 60 watt complete all as specified and directed.
All as per Item No 119.00 here-in-above but for street light of capacity 90 watt complete all as specified and directed.
S & F 90 watt LED type flood light 230 volts AC outdoor type with t IP 65 class protection with aluminium die cast housing glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours complet all as specified and directed..
All as per Item No 119.00 here-in-above but for flood light of capacity 70 watt complete all as specified and directed.
All as per Item No 119.00 here-in-above but for flood light of capacity 100 watt complete all as specified and directed.
All as per Item No 119.00 here-in-above but for flood light of capacity 120 watt complete all as specified and directed.
S & F 40 watt post top lantern LED 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 class protection with aluminium die cast housing cum heat sink circular canopy and clear acrylic cover for 360 degree indirect uniform glare free light distribution impact and corrosion resistant operating voltage range 140v to 270 V, total system lumen not less than 3200 lumens lumen efficiency =80 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 5 Kv, 50000 Hrs burning hours complet all as specified and directed.
S & F in replacement of PVC SMC boxes with hinged door fixing of size 333mm x 233mm x 120 mm with MS clamp made to shape with necessery nut bolts and washers complete comprising of Aluminium busbar 63 Amps capacity of suitable size mounted over porcelain insulator with nut bolts & washers incl MCB 6 Amps and making incoming and outgoing connections by taking out loops of cable of any size incl necessary excavations and other civil works complete all as specified and directed. Make: Sintex/ Universal / SMS
S & F in repair/replacement of cable PVC insulated unarmored for connection 2.5 Sqmm 3 core copper conductor duly drawn from junction box to street light fitting on poles in PVC Flexible pipes complete all as specified and directed.
M & L for scrapping of surface of steel tubular poles of any size with emery paper and painting of poles with one coat of primer and two coats of aluminium paint of approved make incl writing pole nos on white backgrounds with black paint complete all as specified and directed.
S & F driver circuit of any make or any model on existing LED street light luninatrie of wattage 45 to 120W complete all as specified and directed.
S & F driver circuit of any make or any model on existing LED Flood light luninatrie of wattage 60 to 180W complete all as specified and directed.
S & F surge protector of any make or any model on existing LED street/Flood light luninatrie of wattage 45 to 120W complete all as specified and directed.
M & L for replacement of street light bracket made out of 40 mm dia light grade GI pipe bend to shape not less than 1.8 mtr length along with 02 Nos fixing clamps properly shaped and fabricated out of 50 x 5 mm thick MS flat nut & bolts duly painted with 2 coats of aluminium paint over 1 coat of red oxide complete all as specified and directed.
M & L for comprehensive, preventive and periodical maintance of 32 nos Motorised outdoor camera (5 MP and 2 MP) electrically operated including DVR system, stand, HDMI cable, Recording Device, storage device with reliable and efficient operating condition by regularly examine all the parts and other electrical parts including complete servicing of any make and size by using techniques and expertise consultancy including replacement of any type of spares parts electrical or electronic as and when required all as directed and specified to the entire satisfaction of Enginee-in-Charge. Note: (i) Agency Rep will visit once in a month for entire period of contract and report for checking / replacement of Parts shall be submitted to Engr-in-Charge. (iii) Contractor has to submit the AMC documents to the Engr-in-Charge within 15 days from the award of contract. Failing which shall attract the penalty of Rs 500.00 Per day. (iv) AMC shall be done through OEM or any expert agency in the field.
S & F Cat6 Ethernet Cable/LAN Cable/Network Cable for CCTV, PC & Networking, complete all as specified and directed.
S & F Motorised outdoor camera 5 MP AI IR Bullet Camera 3.2 ~ 10.2mm (H: 95°~29° / V: 69°~21°) motorized varifocal lens 30fps@all resolutions (H.265/H.264), Triple codec H.265/H.264/MJPEG with Wisestream III (Based on AI engine), WiseNRII(Based on AI engine), WDR 120dB, Defocus detection, Appear/Disappear, Tampering, Motion Detection based on AI engine, AI Object Detection - Classified object type: Person/Vehicle (vehicle type: car/bus/truck/motorcycle/bicycle); IVA events based on AI engine: Virtual line (Crossing/Direction), Virtual area (Loitering/Intrusion/Enter/Exit) and IP 66 weather proof complete all as sepecified and directed. Make: Hanwha QNO-C8083R.
Taking down carefully copper / aluminium point wiring light / fan, socket or power point complete including fittings such as switches, sockets, ceiling rose, bell push bell buzzer lamp holder bracket etc. removing from site and making good disturbed surface of wall, floor etc complete all as specified and directed.
M & L for replacement of concealed point wiring complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade in and including rigid PVC conduit ISI marked medium grade not less than 20 mm dia, with MS stove enamelled sunken boxes (normal and modular type as required) including earth dolly with plastic laminated sheet top cover (cover plate with frame in case of modular) of approved make and colour including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and directed for the followings :- One light / fan point controlled by one way switch.
All as per Item No 139.00 here-in-above but for one 5 Amp socket outlet on independent board complete all as specified and directed.
All as per Item No 139.00 here-in-above but for one 5 Amp socket outlet on same board complete all as specified and directed.
All as per Item No 139.00 here-in-above but for one bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per Item No 139.00 here-in-above but for one light point controlled by two 2-way switch complete all as specified and directed.
All as per above Item No 139.00 here-in-before but using 2.5 sqmm single core multi stranded copper conductor PVC insulated and unsheathed, FRLS cable for 15 Amp socket outlet on independent board including 2.5 sqmm multi stranded copper conductor cable of green colour as continuous earth wire with lugs etc as required complete all as specified and directed.
M & L for replacement of point wiring in casing caping on surfaces of wall/ceiling floor etc complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade with PVC rectangular block of suitable size including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and as directed for the followings:- One light / fan point controlled by one way switch
All as per Item No 145.00 here-in-above but for one 5 Amp socket outlet on independent board complete all as specified and directed.
All as per Item No 145.00 here-in-above but for one 5 Amp socket outlet on same board complete all as specified and directed.
All as per Item No 145.00 here-in-above but for one bell/buzzer point controlled by one bell push complete all as specified and directed.
All as per Item No 145.00 here-in-above but for one light point controlled by two 2-way switch complete all as specified and directed.
All as per above Item No 145.00 here-in-before but using 2.5 sqmm single core multi stranded copper conductor PVC insulated and unsheathed, FRLS cable for 15 Amp socket outlet on independent board including 2.5 sqmm multi stranded copper conductor cable of green colour as continuous earth wire with lugs etc as required complete all as specified and directed.
M & L for replacement of existing conduit point wiring complete with PVC insulated and unsheathed FRLS cable of 1.5 sqmm (nominal area) with multi stranded copper conductor single core 1100 volts grade drawn through existing conduitwith MS stove enamelled sunken boxes (normal and modular type as required) including earth dolly with plastic laminated sheet top cover ( cover plate with frame in case of modular) of approved make and colour including 1.5 sqmm multi stranded FRLS copper conductor cable of green colour as continuous earth wire with lugs and accesseries and making good disturbed surfaces of walls/floor etc complete all as specified and directed for the followings :- One light / fan point controlled by one switch.
All as per Item No 151.00 here-in-above but for one bell point controlled by one bell Push complete all as specified and directed.
All as per Item No 151.00 here-in-above but for one 5 Amps socket out let point controlled by one switch on independent board complete all as specified and directed.
All as per Item No 151.00 here-in-above but for one 5 Amps socket out let point controlled by one switch on same board complete all as specified and directed.
All as per Item No 151.00 here-in-above but with 2.5 Sqmm nominal cross sectional area electric cable for 15 Amps socket outlet point controlled by one switch on independent board complete all as specified and directed.
S & F in replacement switch piano type 5 amp one way ISI Marked complete all as specified and directed.
S & F in replacement switch piano type15 Amps one way ISI Marked complete all as specified and directed.
S & F in replacement socket outlet 5 pin 5 Amps flush type complete all as specified and directed.
S & F in replacement socket outlet 2-in-1, 6 pin 5 amp and 15 amps complete all as specified and directed.
S & F in replacement socket outlet 6A-2/3 Pin combined 2 module modular type complete all as specified and directed.
S & F in replacement socket outlet 6A/16A-2/3 pin combined 2 module modular type complete all as specified and directed.
S & F in replacement switch 6 amps modular type one one way complete all as specified and directed.
S & F in replacement switch 16 amps modular type one one way complete all as specified and directed.
S & F in replacement electronic fan regulator Step type complete all as specified and directed.
S & F in replacement bell push flush type 5 amp one way ISI Marked complete all as specified and directed.
S & F in replacement modular type bell push 6 amp one module ISI Marked complete all as specified and directed.
S & F in replacement Bell, DING DONG AC 230 Volts single pole type complete all as specified and directed.
S & F in replacement of Lamp holder bakalite type with back plate suitable for batten fittings complete all as specified directed
S & F in replacement of ceiling rose surface bakelite 63 x50mm three terminals complete all as specified and directed.
S & F in replacement of sub main wiring with PVC insulated, FRLS unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 4.0 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 4.0 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and directed. Note: Two runs of 4.0 sqmm cable and one run of 4.0 sqmm cable of earth continuity conductor and conduit shall be a unit length.
S & F in replacement of sub main wiring with PVC insulated, FRLS, unsheathed two single core cable 1100 volts grade with stranded copper conductor of size 6.0 sqmm (Nominal area) drawn in and including PVC conduit of suitable size as directed with and including one run of 6.0 sqmm multi stranded copper conductor single core PVC insulated, unsheathed cable of green colour as continuous earth wire including lugs etc connected and tested complete all as specified and directed. Note: Two runs of 6.0 sqmm cable and one run of 6.0 sqmm cable of earth continuity conductor and conduit shall be a unit length.
All as per Item No 172.00 here-in-above but for bus bar 8 ways 240 V complete all as specified and as directed.
All as per Item No 172.00 here-in-above but for bus bar 4 ways 240 V complete all as specified and as directed.
S & F in replacement of single pole and neutral enclosure with 2 pin and metal earth plug and socket complete with one single pole MCB 25 Amp complete all as specified and directed.
S & F in replacement of Double door three phase distribution board 4 way loadline VTPN when MCCB to be used as incomer and made out of CRCA sheets 1.6 mm thick, phosphatised powder coated with Bus Bar 200 Amps, 415 V, Earth Stud, Din Rail, Polymide terminal blocks for incoming and outgoing circuits, inbuilt loose wire box, ground terminal blocks , poly layer for protection complete all as specified and directed. Note: (a) MCCB and MCBs are to be measured and paid for seperately. (b) Make of MCBs and DB should be same.
S & F in replacement of Double door distribution board 4 way TPN when MCB to be used as incomer powder coated with Bus Bar 200 Amps, 415 V, Earth Stud, Din Rail, complete all as specified and directed. Note: (a) MCBs are to be measured and paid seperately. (b)Make of MCBs and DB should be same.
S & F in replacement MCB SP 5 to 32 Amps, 240 volts curve 'B',breaking capacity 10KA complete all as specified and directed.
All as per Item No 178.00 here-in-above but for MCB SPN 16 to 40 Amps complete all as specified and directed.
All as per Item No 178.00 here-in-above but for MCB SPN 50 to 63 Amps complete all as specified and directed.
S & F in replacement MCB TPN 63 Amps, 415 volts, curve 'B', breaking capacity 10 KA, complete all as specified and directed.
S & F in replacement MCCB , 125 Amps, 4Pole with adjustable thermal setting and rupturing capacity 16 KA complete all as specified and directed.
S & F in replacement of modular switch 2 way, 6 Amp,1 module ISI Marked complete all as specified and directed.
S & F in replacement of modular Fan Regulator fan step regulator,120W- single module ISI Marked complete all as specified and directed.
S & F in replacement of Piano type switch 2 way, 5 Amp,1 module ISI Marked complete all as specified and directed.
S & F in replacement of modular blanking plate, 1 module ISI Marked complete all as specified and directed.
S & F in replacement metal flush box 3 module complete all as specified and directed.
All as per Item No 187.00 here-in-above but for 4 module all as specified and directed.
All as per Item No 187.00 here-in-above but for 6 module all as specified and directed.
All as per Item No 187.00 here-in-above but for 8 module all as specified and directed.
All as per Item No 187.00 here-in-above but for 12 module all as specified and directed.
S & F in replacement for white cover plate with frame, 3 module complete all as specified and directed.
All as per Item No 192.00 here-in-above but for 4 module all as specified and directed.
All as per Item No 192.00 here-in-above but for 6 module all as specified and directed.
All as per Item No 192.00 here-in-above but for 8 module all as specified and directed.
All as per Item No 192.00 here-in-above but for 12 module all as specified and directed.
M & L in repair for Earth continuity conductor or main earthing lead of 4.0 Sqmm galvanized iron wire, buried in ground or fixed to wall in and including 15 mm bore GI pipe medium grade for protection of earth wire complete all as specified and directed.
S & F in replacement enviroment friendly,ultra modern,energy saving surface mounted decorative 10 Watt LED bulkhead fitting modular type with polycarbonate housing ,high efficient LEDs with opal diffuser and IP65 protectio, lumen efficacy 85 lm/watt with colour temerature 6500K, THD≤ 20 CRI>80,2.5 kV surge protection complete all as specified and directed.
S & F 9 watt LED bulb with B22 Base cap, 1200 lumens ,Colour rating Index 80,colour temp F 6500K,satrtup time less than 2 sec,In built surge 3.0 kV, voltage range 140V to 270 V , Lamp life 15000 hours complete all as specified and directed.
S & F 12 watt LED bulb with B22 Base cap, 1200 lumens ,Colour rating Index 80,colour temp F 6500K,satrtup time less than 2 sec,In built surge 3.0 kV, voltage range 140V to 270 V , Lamp life 15000 hours complete all as specified and directed.
S & F in replacement of enviroment friendly indoor decorative 20 Watt LED Polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessories complete all as specified and directed.
All as per Item No 201.00 here-in-above but for 9/10 Watt LED complete all as specified and directed.
S & F in replacement enviroment friendly recess/surface mounting 36 watt LED flat panel 2'x2' fabricated CRCA sheet steel duly powder coated housing cool white with high efficient LEDs & glare free opal diffuser PF>0.95 , lumen efficacy>100 lm/W, THD<10% operating range 220v to 240V,CRI>80 including connection with existing wire and all accessories complete all as specified and directed.
S & F in replacement enviroment friendly recess/surface mounting 24 watt LED flat panel 1'x1' fabricated CRCA sheet steel duly powder coated housing cool white with high efficient LEDs & glare free opal diffuser PF>0.95 , lumen efficacy>100 lm/W, THD<10% operating range 220v to 240V,CRI>80 including connection with existing wire and all accessories complete all as specified and directed.
S & F in replacement of enviroment friendly indoor decorative 5/6 Watt LED polycarbonate Batten with opal diffuser , operating voltage range 140v to 270 V, Driver efficiency 88%, lumen efficiency =100 lm/watt , THD≤ 20 CRI>80 , colour temperature 6500 K, inbuilt surge protection = 2.5 Kv, isolation=3.75, and with zero mercury content including all accessories complete all as specified and directed.
M & L for flame proof wiring with single core PVC insulated and unsheathed 1100 volt grade FRLS electric cable with multi stranded copper conductor of size 2.5 Sqmm phase and neutral drawn in and including ERW rigid steel stove enameled black conduit heavy duty ISI marked of size 20mm dia on surface/wall/ceiling including all flame proof conduct fittings and accessories such as tees junction boxes, bends duly tested by CMRI Dhanbad suitable for one light /fan point controlled by one flame proof rotary switch SP one way and including drawing continuous earth wire FRLS PVC insulated unsheathed 1100v grade cable with stranded copper conductor of size 2.5 Sqmm and connected to earth dolly complete all as specified and directed.
S & F flame proof/weather proof direct entry type rotary switch single pole on & OFF rotary motion switch in cast aluminum alloy LM-6 enclosure epoxy powder coated single pole 230Volts 10 Amps, AC ON/OFF switch operated externally by Knob having 02 Nos of M-20 cable entries, earthing terminals suitable for mounting on Wall/Steel structure etc complete all as specified and directed. Make: Flexpro/ Sudhir/ Baliga/ Shyam
S & F in replacement of LED light fitting 1x16 Watt flame proof, CMRI certified recommended for gas/ vapor group of IIA & IIIB, Zone 1 & 2 and IP 65 protection with die cast aluminum hosing with heat resistant toughened glass with LED tube light fixtures driver,holders, connector etc. Complete with all accessories prewired and including connecting up with three core flexible copper conductor cable with suitable size complete all as specified and as directed. Note: (a) All fittings shall be ISI marked and shall have approval of CMRI Dhanbad . (b) Original Test certificate of Manufacturer shall be produced by Contractor .
S & F in replacement of Cable PVC insulated unsheathed single core 1100V FRLS grade stranded flexible copper conductor of size 1.5 sqmm complete all as specified and directed.
S & F in replacement of Cable PVC insulated unsheathed single core 1100V FRLS grade stranded flexible copper conductor of size 2.5 sqmm complete all as specified and directed.
S & F in replacement of Cable PVC insulated unsheathed twin core of 23/0.0076 size flexible copper conductor complete all as specified and directed.
S & F in replacement of Cable PVC insulated unarmoured three core 1100V FRLS grade stranded flexible copper conductor of size 2.5 sqmm complete all as specified and directed.
S & F in replacement of recesses/suface mounted with ring square/round shape slim downlighter of 12 watt capacity with colour temperature cool day white/warm white as per requirement , Lumens 120, CRI more than 80 as per sample and site requirement including all accessore complete all as specified and directed.
M & L including T & P for attending complaints related to Geyser any capcity Inspection and maintenance of water heater (Geyser) of capacity, 25 lt to 50 litres including performing the following task at different locations at AF Stn Sarsawa complete all as specified and directed. Note: (a) Removing Geyser & flow unit & heating element & cleaning the inner, tank with suitable acid/Replacement of defective connection lead . (b) Checking and setting of thermostat between 50 to 55 degree Celsius (c) Check working of NRV stop cock, pressure release valve and servicing carefully to make it functional (d) Repairing of earthing connection, power switch, socket connection replacement of indicator lamp to make it functional (e) Examine water leakage and rectifying as required and replacement of rubber washer gasket etc to make it functional (f) Inspect over flow vent pipe, safety valve and remove blockage if required to make it functional. (g) Any other item required for making Geyser serviceable will be measured & paid seperately under respective items.
M & L including taking out of burnt coils of ceiling fan in replacement of all coils of ceiling fan motor, AC, 230 volt of 1200/1400 mm with super enamel copper winding wire of proper gauge, weight etc (having same nos of turns), winding using insulating materials varnishing, heating, baking, replacement of bearing, bush, shaft etc, re-assembling the fan after making it functional and testing ,maintain the speed of fan complete all as specified and directed.
All as per Item No 216.00 here-in-above but for exhaust fan upto capacity 450mm size/sweep complete all as specified and directed.
All as per Item No 216.00 here-in-above but for wall mounting fan upto capacity 750mm size/sweep complete all as specified and directed.
All as per Item No 216.00 here-in-above but for Pedestal fan of any sweep/size complete all as specified and directed.
All as per Item No 216.00 here-in-above but for cabin fan of any sweep/size complete all as specified and directed.
M & L for spray painting of ceiling fan ,exhaust fan wall mounted,Pedustal fan of any size any type with one coat of synthetic enamelled paint after cleaning and making good the old damaged paint complete all as specified and directed.
S & F Fan capacitor upto capacity of 1.5 MFD complete all as specified and directed.
All as per Item No 222.00 here-in-above but for 2.5 MFD complete all as specified and directed.
All as per Item No 222.00 here-in-above but for 3.15 MFD complete all as specified and directed.
All as per Item No 222.00 here-in-above but for 4 MFD complete all as specified and directed.
S & F ball bearing/shaft suitable/as per exciting sample for exhaust fan, ceiling fan and pedestal fan/wallmounted fan/cabin fan etc complete all as specified and directed.
S & F Gun metal bush for ceiling fan of any size/make/sweep complete all as specified and directed.
S & F Gun metal bush for exhaust fan of any size/make/sweep complete all as specified and directed.
S & F ‘U’ clamps for hanging ceiling fan with all nuts & bolts, washer, suitable size with rubber real complete all as specified and directed.
S & F in repairs ceiling fan canopy with nut and bolt of suitable size complete all as directed and specified.
S & F in replacement of down rod for ceiling fan made out of 15 mm dia MS pipe complete with holes, slotted or threaded from 0.75 mtr to 1.5 mtr long complete all as specified and directed.
S & F in replacemenmt of Fan blade for ceiling fan 1200/1400 mm sweep as per existing model complete all as specified and directed.
S & F replacement of Fan blade for Exhaust fan metal type any sweep as per as per existing model complete all as specified and directed.
S & F replacement of Fan blade for wall mounted fan any sweep as per as per existing model complete all as specified and directed.
S & F in replacement of metallic exhaust fan louvers of any shape (square or round as per site requirement) upto 450 mm sweep complete all as specified and directed.
S & F ceiling fans complete with blades, down rods, electronic regulator and accessories, 230 V, 1200 mm sweep. Min air delivery 210 CFM with service value 6.00 BEE. Five star rated with brushless direct current motor (BLDC) complete all as specified and directed.
S & F exhaust fan, MS body AC single Phase. 230V of size 300 mm sweep with, 1400 RPM, blades, and frame and louver complete all as specified and directed.
S & F wall mounting fans 230 volts single phase oscillating 400 mm sweep suitable for wall mounting complete all as specified and directed.
S & F plastic body ventilation fan 250 mm 50 Hz , 240 volt 1250 RPM with copper wound motor including all fixing accessories complete all as specified and directed.
S & F in replacement of Geyser flow unit / assembley made out of MS body as per matching shape/size or as per sample suitable for 15 to 50 litres capacity including safety valve complete all as specified and directed.
S & F in replacement of copper heating element of rating 1.5 KW to 2 KW to geyser 15 to 50 litres capacity, any type, make / as per sample complete all as specified and directed.
S & F in replacement of Thermostat as per sample suitable for 50/25 litres capacity of geyser complete all as specified and directed.
S & F in replacement of Flexible SS braided connection havey duty stain steel 15 mm dia, length up to 750 mm long with union at both ends for 15 mm dia pipe complete all as specified and directed.
S & F in replacement of Red and green indicator lamp as per existing size and shape complete all as specified and directed.
S & F in replacement of Plug top, 3 pin, 15Amps complete all as specified and directed.
S & F modular type AC box operated with 20 Amp single pole MCB including 15 amp modular socket complete all as specified and directed.
S & F Anchor bolt type fastner brass size 10mm upto 150mm length complete all as specified and directed.
Dismentling the flow unit, inlet,outlet pipe of Geyser & taking out to repair the inner MS tank of capacity 25/35/50 letres storage capacity by brazing at different spots after cleaning rusted leaking places and making tank leak proof including refixing, re-assembling & testing complete all as specified and directed.
M & L for painting of geyser 25 to 50 litres capacity with synthetic enamel spray paint with two coats of paint over one coat of red oxide primer including preparation of old surfaces complete all as specified and directed.
S & F of non return valve Brass metal vertical type size 15 mm complete all as specified and directed.
S & F for insulation of 25 to 50 Ltrs geyser as per existing insulating material in existing quantity for each geyser complete all as specified and directed.
S & F in replacement of MS steel water storage tank for upto 50 Ltrs capacity geyser as per existing gauge and shape complete all as specified and directed.
S & F in replacement of outer body 18 gauge complete with bottom and top cover as per matching to existing type and size for upto 50 Ltrs capacity geyser complete all as specifed and directed.
S & F electric water heater, storage type with MS tank and outer body made out of ABS & PP, heating element of 2 KW storage capacity 25 litre, BEE 5 Star rated complete with all accessories such as safety valve, thermostate, NRV, SS connection piece of suitable length etc complete all as specified and directed.
M & L for making arrangement for fixing of exhaust fan on steel/Aluminium frame window/ making opening in brick wall as per site requirement and also making good to disturbed surfaces as per matching to existing complete all as specified and directed.
M & L for repair and maintenance of split/Window type AC's of capacity 1.5/2 TR comprising of the following tasks installed at different locations including testing complete all as specified and directed by Engineer-in-Charge. Note: (a) Inspecting and checking the Indoor/outdoor units for noise free operation. (b) Checking the electrical connection for tightness. (c) Cleaning the condenser with cleaning agent followed with pressurized water and cleaning the cooling coil with air blower. (d) Greasing/Oiling of condenser fan motor and blower motor. (e) Checking for any refrigerant leakage. (f) Checking for serviceability of remote control unit.
S & F in replacement of starting relay for split type AC units of capacity 2 TR as required at site complete all as specified and directed.
S & F in replacement of starting relay for split type AC units of capacity 1.5TR as required at site complete all as specified and directed.
S & F in replacement of starting capacitor 80-100/100-120 mfd for split type A/C's of capacity 2 TR complete all as specified and directed.
S & F in replacement of running capacitor 30/36 mfd for split/window type AC unit as required at Site complete all as specified and directed.
Taking out and refixing after rewinding including replacement of bush/ bearings of condenser fan motor of split type AC units of capacity 1.5/2 TR complete all as specified and directed.
Taking out and refixing after rewinding including replacement of bush/ bearings of blower motor of split type AC units of capacity 1.5/2 TR complete all as specified and directed.
Disconnecting and taking down burnt compressor of capacity 2TR from split type AC unit and Supply and Fix new with charging of refrigerent after dehydration testing and vaccumming one as per existing model complete including testing all as specified and directed.
Disconnecting and taking down burnt compressor of capacity 2TR with CFC free Refrigerent (R410a,R32,R134a) from split type AC unit and Supply and Fix new with charging of refrigerent after dehydration testing and vaccumming one as per existing model complete including testing complete all as specified and directed.
Disconnecting and taking down burnt compressor of capacity 1.5 TR with CFC free Refrigerent (R410a,R32) from split type AC unit and Supply and Fix new with charging of refrigerent after dehydration testing and vaccumming one as per existing model complete including testing complete all as specified and directed.
Disconnecting and taking down burnt compressor of capacity 1.5 TR from split type AC unit and Supply and Fix new with charging of refrigerent after dehydration testing and vaccumming one as per existing model complete including testing complete all as specified and directed.
S & F in replacement of new remote control unit (cordless) with PCB for 1.5/2 TR split type A/C unit complete all as specified and directed.
S & F in replacement new blower motor as per sample and existing model for split type A/C unit complete all as specified and directed.
S & F in replacement of air filter for split type A/C units of capacity 1.5/2 TR complete all as specified and directed.
M & F for providing sleeve type insulation 9mm thick for any dia copper tubing from Indoor to outdoor units complete all as specified and directed.
Supply and charging CFC free Refrigerant (R410a,R32,R134a) to any type of AC complete all as specified and directed.
Supply and charging R22 Refrigerant to any type of AC complete all as specified and directed.
S & F in replacement the new swing motor of existing model sample for split type AC 1.5/ 2TR unit complete all as specified and directed.
M & L in replacement of copper tubing 10mm outer dia suitable for AC 2TR capacity complete all as specified and directed.
M & L in replacement of copper tubing 15mm outer dia suitable for AC 2TR capacity complete all as specified and directed.
M & L for repair & maintenance of water coolers of any capacity comprising of the following tasks at different location complete all as specified and directed by Engineer-in-Charge. Note: (a) Inspection, taking down, opening, dismantling, decaling, brushing cleaning of storage tanks. (b) Examination water tightness, leak proof of storage tank after cleaning. (c) Carry out operation of all stop cock, push cock, float valve etc. (d) Inspect overflow and remove blockage if any. (e) Check and correct earth continuity of electric items. (f) Check thermostat and test its functioning. (g) Inspect drain pipe and remove blockage if any. (h) Check and correct all electrical wiring & test its functioning. (j) Testing of water cooler after repair.
M & L for detection/rectification of leakage of gas in the system and gas charging in the system with appropriate quantity of gas including testing for smooth functioning of water cooler of any capacity complete all as specified and as directed. Note: (i) Unserviceable condensing coil if required shall be measured and paid separately. (ii) The cost of dismantling of unserviceable compressor if required deemed to be included in unit rate. (iii) Compressor shall be measured and paid separately under respective items of Sch "A".
S & F in replacement of thermostat switch for existing model sample as required at site complete all as specified and directed.
S & F in replacement fan motor capacitor 2.5/3.15mfd complete all as specified and directed.
S & F in replacement of overload protector for compressor of water cooler of any capacity as reqd at site complete all as specified and directed.
S & F in replacement of starting relay as required at site for water coolers of any capacity complete including connecting, testing complete all as specified and directed.
Disconnecting and rewinding of condenser motor single phase of 1/16 HP for water coolers & refixing the same with clamps bolts, nuts and rubber bushes including connecting, testing complete all as specified and directed.
S & F in replacement of CP push cock ISI marked 15mm base complete all as specified and directed.
S & F in replacement of starting capacitor 100/120 mfd for compressor complete all as specified and directed.
S & F in replacement of new condenser motor single phase of 1/16 HP as required at site for water cooler with clamps, bolts, nuts & rubber bushes complete including connecting testing complete all as specified and directed.
S & F in replacement of water cooler compressor reciprocating type (hermetically) sealed for any capacity as required at site water cooler complete all as specified and directed.
M & L for repair & maintenance of voltage stabilizer of capacity upto 5 KVA comprising of the following tasks at different location complete all as specified and directed. Note: (a) Rewinding of Transformer copper coil with new copper wire as per existing gauge. (b) Time delay relay-01 No. (c) Cut out relay-01 No. (d) printed citcuit relay- 01 No.
S & F in repair/replacement of voltage stabilizer of 5 KVA capacity complete all as specified and directed. Note: Old stabilizer will be deposited to MES store.
S & F in replacement of PCB card of split AC 1.5/2 Tonne AC as per existing make/model on site complete all as specified and directed.
S & F in replacement of PCB suitable for 5 KVA voltage stabilizer as per existing make/model on site complete all as specified and directed.
S & F new transformer in replacement of burnt out transformer of 5 KVA voltage stabilizer complete all as specified and directed.
S & F room window type air conditioner electric driven (single phase), cooling capacity 2 Ton BEE 3 star rated all as specified and directed.
S & F desert cooler electric driven (single phase), having nominal air flow capacity of 54 Ltr (or nearest size). plastic/PVC Body complete all as specified and as directed.
S & F in repair danger notice plate of 1.6mm thick mild steel viterous enameled white with letter figures and conventional skull and bones in signal red colour and fix with MS clamp for LT size 20 x 15 cm complete all as specified and as directed.
S & F in repair for Earthing to DBs with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick, buried directly in ground (earth pit not less than 2.25m below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to main earth lead GI wire 4.0 mm dia by means of bolts, nut, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.3 of MES Schedule Pt-I 1991, GI earth lead wire protected by GI pipe 15mm dia light grade and connected to earth test point including excavation in any type of soil,returning filling, disposal of soil, providing charcoal dust and common salt upto top edge of earth plate, construction of PCC pit with RCC cover, funnel, watering pipe of 20mm dia GI light grade and provision of earth test point including testing on completion complete all as specified and directed.
VIJAY ENTERPRISES (BID ID -3490353)
Raman Electric Trading Co (BID ID -3488384)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.PDF
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.60 MB
BOQ_827186.xls
BOQ • 2.27 MB
SART60.pdf
Tender Documents • 1.51 MB
Download all tender documents and submit your bid