Loading…
Tenderkart now works inside Claude and ChatGPT: search and analyse tenders right from your chat
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹27.8 LAccepted-AOC F 42 VAISHNAV APARTMENT HOSHANGABAD ROAD SURENDRA PALACE BHOPAL MADHYA PRADESH 462023 | BHOPAL | MADHYA PRADESH | 462023 | L1 | Accepted-AOC Lowest bidder for the work | |
| 2 | L2₹34.7 L+₹5.2 L (17.5%)Rejected-AOC | L2 | Rejected-AOC Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹80,000
Closing Date
29 Oct 2020, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Commander Works Engineer Bhopal
Headquarters Commander Works Engineer Bhopal Military Engineer Services SI Lines Bhopal-462 001
REPAIR TO HT DISTRIBUTION NETWORK UNDER GE NASIRABAD
2020_MES_373356_1
83558/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Nasirabad
As per tender documents
7 documents required · 7 mandatory
₹500
GE Nasirabad
₹80,000
Yes
9 Dec 2020
3 Oct 2020
31 Oct 2020
3 Oct 2020
29 Oct 2020
17 Oct 2020
3 Oct 2020 - 22 Oct 2020
60 days
Amount
Dismantling ACSR or AAC conductors removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling insulators any type, any size complete all as specified and as directed.
Dismantling cross-arms of mild steel channel or angle sections etc. complete and setting aside for re-use or removing to store or for schedule of credit
Dismantling stay assembly complete (Note: Demolition of concrete, etc. and excavation measured shall be measured and paid separately separately.)
Disconnecting, taking out old unserviceable under ground cable of rated voltage 11 kV, nominal cross sectional area of main conductor 95 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Disconnecting, taking out old unserviceable under ground cable of rated voltage 11 kV, nominal cross sectional area of main conductor 120 sqmm, upto 4 core, any type from trenches including taking out concrete cable cover/ bricks etc. including removing materials to store for keeping in safe custody or for reuse or for taking credit (credit for above items should be made as per conditions separately) all as specified and directed by the Engineer-in-Charge.
Dismantling earth wire or copper conductor, service feeder or distributor span removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling air break gang operated switches vertical/horizontal mounted including insulators and operating mechanism for repair/ replacement of broken/worn out components and insulators etc. or carrying to MES store (spare/components for replacement to be provided free by department)
Taking up or down old unserviceable GI pipe of any size fixed/ laid in any position, keeping serviceable materials separately for reuse at site or removing to store or taken on schedule of credit complete all as specified and as directed.
Dismantling steel poles/ struts, any size, transporting to store and stacking or for schedule of credit
Dismantling concrete poles/ struts, any size, transporting to store and stacking or for schedule of credit
M & L for prestressed concrete pole, 11.0 metres long, 152 mm X 152 mm at top and 152 mm X 260 mm at bottom designed for wind load at the site complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Excavating in trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3.0 in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc. or for cable laying or not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/ loose soil complete all as specified and as directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm in soft/ loose/ hard/ dense soil complete all as specified and as directed.
Removing excavated material (soils) not exceeding 50 m and depositing where directed at a level n exc. 1.5 m above the starting point
Supply & spreading in trenches dry river sand cushioning to underground cable in trenches including spreading, levelling hand punning down complete all as specified and directed Note:- Depth of sand cushioning will be measured after punning down and levelling the sand properly.
M & L for laying of bricks locally available sub class 'B' bricks, non-modular sizes as per IS 1077: 1992 for cable protection cover laid flat and dry in trenches over the cable perpendicular to the direction of cable all as directed.
M & L for cement concrete in foundation, filling and mass concrete in M7.5(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete in foundation, filling and mass concrete in M10(Nominal Mix) using 40 mm nominal size graded crushed stone aggregate complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate in roof kerbs or mud stops, rounded or chamfered on edges complete all as specified and as directed.
M & L for auguring under road, pavement, hard standing, railway lines by trenchless technology using latest boring technique and necessary machine for insertion of GI pipe of 65 mm to 100 mm nominal bore complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 80 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supplying & laying in trenches, in road cutting and along pole 100 mm nominal bore, light grade, galvanised coated steel tube conforming to IS 1239 (Part-1): 2004 including all fittings conforming to IS 1239 (Part-2): 2011 complete all as specified and as directed.
Supply, fixing and stringing ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement and binding on insulator by means of 22 gauge aluminium binding wire to permissible sag complete all as specified and as directed.
M & L for cross arms, bracings, supports, clamps, back plates and stay clamp fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and applying two coats of aluminium paint over a coat of red oxide primer complete all as specified and as directed.
S & F gang operated air break switch, three poles, outdoor type, nominal system voltage 11 kV, rated voltage 12 kV, rated normal current 200 Amps, rated frequency 50 Hz, rated one minute power frequency withstand voltage between (i) earth & poles 28 kV (rms) (ii) across the isolating distance 32 kV (rms), rated lightning impulse withstand voltage (i) to earth and between poles 75 kV (Peak) (ii) across the isolating distance 85 kV (Peak), Rated short-time withstand current 25 kA for 3 seconds, rated peak withstand current 63 kA for climatic conditions at the site, mechanically operated mounted on insulator and steel frame with operating mechanism worked from ground level for current complete all as specified and as directed.
S & F drop out fuse unit expulsion type for outdoor air brake gang operated switches single pole mounted and including insulator for 11 kV working pressure fixed to and including MS channel with nuts, bolts, washers etc. synthetic bounded fuse carrying tube complete with line taps and suitable for current carryout capacity 15 Amps.
M & L for stay assembly of stay rod of diameter 20 mm complete with accessories as shown in electrical plate No. 1 (loop type insulator, stay clamps, excavation and concrete measured separately) complete all as specified and as directed.
M & L for hot dip galvanized stay strands of grade I, 7 Nos wires construction, wire diameter 4 mm, nominal strand diameter 12 mm, heavy zinc coating complete all as specified and as directed.
S & F galvanised mild steel wire 3.15 mm or 4 mm dia in overhead lines complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 50 sqmm to 95 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core 50 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, outdoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
S & F XLPE cable end termination, heat shrinkable, indoor type complete with jointing material and accessories suitable for voltage 6.35 kV/ 11 kV (Earthed), 3 core, 120 sqmm to 185 sqmm complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 95 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
Supply, laying and testing cross linked polyethylene (XLPE) insulated, PVC sheathed cables for working voltages 6.35 kV/ 11 kV, three phase, earthed system, 3 core, screened, armoured power cable, 120 sqmm of nominal area of conductor, aluminium conductor, ISI marked as per IS 7098 (Part-II): 2011 laid in trenches or under floors making all connections with necessary glands lugs bushing complete all as specified and as directed.
S & F pin type, porcelain, vitreous, white, brown or green insulator including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and as directed.
S & F disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type, white, brown or green, two-in-series assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and as directed.
Supply and erection in repairs of three piece metal oxide lightning arrestor suitable for 11 kV continuous operating voltage (3 phase) with rated voltage 12 kV (rms) with nominal discharge current rating of 2.5 kA and complete with galvanised clamping arrangements, GI bolts, nuts, washers etc. complete as specified and as directed.
S & F in repairs TNC (Trip Neutra Close) switch suitable for 11 kV / 33 kV circuit breaker control panel of battery capacity 12 V, 180 AH complete all as specified and as directed.
Supply & connect in replacement of battery 180 AH, 25 plate with initial Charger Specific gravity 12.60 of 12 volts complete all as directed by Engineer-in-Charge. (Make:- EXIDE/Amron or equivalent)
M & L for cleaning and up keeping of MES installations / campus by surface dressing or trimming of natural ground to remove small inequalities not exceeding 15 cm deep ( including removing vegetation / shrubs / brush wood / under-growth ), cleaning of drains ( drain size 0.50 m x 0.40 m for 60 m length) & carrying away the rubbish to a distance of not exceeding 50 m away complete within fencing perimeter approximately 30 m x 50 m. complete all as directed. Note : Each job will be measured for a completed month.
M & L for preparing and painting and painting on steel tubular swaged pole 410 SP-55 (11.00 metre long) including cross arms, GI brackets with two coats of aluminium paint over a coat of aluminium red oxide primer on exposed portion and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
M & L for preparing and painting on prestressed concrete pole, 11.00 metres long, 152 mm X 152 mm at top and 152 mm X 260 mm at bottom, with two coats of cement base paint on exposed portion including painting on cross arms, street light brackets with two coats of aluminium paint over a coat of aluminium red oxide primer and including making strips of width 30 cm upto 1.5 m from the ground level in black and yellow shade in alternate layer including numbering of poles using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
S & F in repairs ACSR (aluminium conductor galvanized steel-reinforced) of any size and type in accordance with site requirement in jumper including PVC sleeve (in Red/Yellow/Black colour) and binding on insulator by means of 22 gauge aluminium binding wire complete all as specified and as directed.
M & L for danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with mild steel clamps, bolts and nuts of approved size, for HT, 250 mm X 200 mm complete all as specified and as directed.
S & F anti-climbing device; spikes type fabricated out of mild steel bars (round, square and flat) including nuts, bolts, washers and welding in two halves made to shape to suit the cross section of the pole complete all as specified and as directed.
Preparation of newly or previously untreated steel surface of any description over 10 cm width or girth and applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed by Engineer-in-Charge
M & L for earthing complete with galvanised steel plate earth electrode 600 mm X 600 mm X 6 mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to earthing lead of 32 mm X 6 mm galvanised mild steel strip by means of bolts, nuts, check nuts and washers of galvanised iron from earth plate to test point upto 7.5 metre including all as shown in electrical plate No. 3 of SSR Part I (2009) including necessary concrete chamber in cement concrete M15 (Nominal Mix) using 20 mm nominal size coarse aggregate, precast RCC cover slab in cement concrete M15 (Nominal mix) using 20 mm nominal size coarse aggregate of size 40 cm X 40 cm X 5 cm reinforced with 8 mm dia TMT bars @ 150 mm c/c both ways with one handle for lifting made out of 8 mm dia bar, GI funnel, GI wire mesh filter, 20 mm dia GI pipe medium grade for watering, 40 mm dia GI pipe medium grade for protection of earthing lead, charcoal or coke and salt in alternate layers including necessary excavation and earth work in any type of soil/ strata and testing complete all as specified and as directed by the Engineer-in-charge.
M & L for walling (curved on plan to a mean radius exceeding 6 metre) of random rubble, uncoursed, well bonded, bedded and solidly hearted built in cement mortar (1:6) complete all as specified and as directed.
M & L for hardcore (broken stone or boulders) of gauge not exceeding 63 mm, deposited, spread and levelled in layers not exceeding 15 cm thick, watered and rammed to a true surface complete all as specified and as directed.
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate as in floor 25 mm thick finished even and fair complete all as specified and directed.
Material and labour for plastering 15 mm thick on stone masonry surfaces or other than fair faces of brick work or on one side of lathing (on vertical surfaces) in cement mortar 1:4 finished even and fair complete all as specified and as directed.
Preparation of newly plastered surfaces on walls and applying two coats of white wash complete all as specified and as directed.
Preparation of old painted steel surfaces of any description, over 10 cm width or girth and applying one coat of synthetic enamel paint complete all as specified and as directed by Engineer-in-Charge.
M & L for preparation of old steel surfaces of panel board and applying one coat of aluminium paint including numbering of panel board using two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer complete all as specified and as directed.
Demolition of lime concrete of any description and in any position not otherwise specifically provided for
M & L for cement concrete M15 (Nominal Mix) using 20 mm nominal size graded crushed stone aggregate in lintels upto 1.5 m clear span, cills, steps; seismic and other similar bands, plinth courses, string courses, lacing courses, parapets and railings upto 60 cm in height, copings, kneelers, apex stones, bed plates, kerbs, water troughs, slab staging for water tanks, filling of pressed steel door frame, fixing of hold fasts and the like including weathering, slightly rounded or chamfered angles and throating including necessary formworks complete all as specified and directed by Engineer- in-charge.
M & L for trimming of branches of trees touching HT/LT Electric over head line and making clear about 3 m in radius and carrying and disposal where directed not exceeding 50 m complete all as directed. Note :- Vehicle will be provided by department at spare time.
Supply only IDMT CGI-14N,CGI14N relay 11kv capacity Make :CG
Supply only 11KV VCB Mechanism or Spring charging Mechanism Make:-CG
Supply only 220V Spring Charging Motor Make:- Stelmec/CGL/Jyoti VCB
Supply only Tripping coil/closing coil Make:-ABB/CG
Supply only 11 KV VCB Charging key
Supply only 11 KV VCB Vacuum Bottle Interrupter Make:-CG
Supply only 11 KV VCB Crompton Insulator
Supply only 11 KV VCB Trolly Insulator
Supply only 11 KV VCB Crompton CT Set
Supply only 11 KV VCB PT Spout Crompton
M/s SUNIL ENTERPRISES
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .