Loading…
Loading…
Tender Value
₹41.5 L
EMD Value
₹83,000
Closing Date
5 Aug 2026, 6:00 pm
GE Utility Electric Supply
GE Utility Electric Supply DELHI CANTT-10
AUGMENTATION OF EXTERNAL ELECTRIC SUPPLY FOR HQ 35 INF BDE UNDER GE U E S DELHI CANTT
2026_MES_778756_1
GE ELECT/TOKEN-18/2026-2027
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
GE Utility Electric Supply
AS PER TENDER DOCUMENTS
7 documents required · 7 mandatory
₹500
GE Utility Electric Supply
₹83,000
15 Jul 2026
15 Jul 2026
7 Aug 2026
15 Jul 2026
5 Aug 2026
29 Jul 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply,installation, testing and commissioning of transformer step down, outdoor type copper wound Level-III, IS 1180, 11KV/433 Volts (at no load) AC 3 phase 50 Hz, capacity 400 KVA, core type, Oil immersed naturally cooled, oil natural air natural (ON/AN), with external cooling tubes, delta connected on primary side (HT) and star connected on secondary side (LT) in accordance with vector group DYn-11 with neutral brought out on secondry side (LT) and having taping at ±10% in steps of 2.5% on HT side to be changed by means of hand operated off load tap changer. The maximum temperature rise should not exceed 40°C in oil and 45°C in HT/LT winding when measured by resistance method after continuous full load run on an ambient temp of 40°C transformer shall be of BOLTLESS core design. Transformer shall be double wound, core type with low loss, non ageing, high permeability prime grade CRGO with M4 grade or better, perfectly insulated and clamped to minimize noise and vibrations. The transformer shall be IS/IEC 60076 and as per IS-1180 part-I of 2014 marked, Including the cost of PCC/RCC alongwith necessary framework for foundation & fencing in perimeter location for placing of TRANSFORMER complete all as per IE/IS specification and shall comprise of the following :-
(a) One cable box on HT side (Primary side) consisting of three nos porcelain bushing with copper rods complete with nuts and washer with cable glands suitable for reception / taking out 3 core 120 Sqmm, HT 11000 volts grade, XLPE insulated and PVC sheathed, heavy duty , armoured cables including jointing materials complete.
(b) One cable box on LT side (secondary side) consisting of four nos porcelain bushing with copper rods for connected bus ducts complete with nuts and washers with cable glands suitable for reception/taking out 400 sqmm 3.5 core, LT 1100 volts grade, XLPE insulated and PVC sheathed, heavy duty, armoured cables including jointing materials complete. | 1 | Each | - | - |
| 1.01 | (c) Conservator with filter type drain valve and oil level guage.
(d) De-hydrating breather with first fill of dehydrating agent (Silica Gel).
(e) Explosive vent, Thermometer pocket on tank cover, oil level guage, Oil drain filter valve, Lifting lugs, oil filling hole with cap/plug with connection plate complete, Air release valve plug and four nos plain solid cast steel detachable rollers.
(f) One no 100 mm dia, dial type thermometer, vapour pressure type, having range 0-120° C with metal guard having maximum perimeter temperature reading indicator with re-setting device.
(g) Two earthing terminals on tank cover to facilitate fixing of 50 x 6mm galvanised iron earth strip for earthing of body.
(h) Rating plate and terminal marking plate.
(j) Extra bushing for neutral in the LT cable box for providing independent set of earthing for neutral.
(k) First fill of new and unused transformer oil, IS-335 marked, filtered and tested upto 40 KV dielectric strength at 2.5 mm air gap between testing electrodes.
(l) Providing adequate size and nos of channels, embeded in floor, for movement of transformer.
(m) Transformer losses shall not exceed the loses mentioned in IS: 1180(2014) Part - I with energy Effeciency level - III.
(n) Oil temperator indicator , winding temperature indicator, marshalling box single window, double flit buchholz relay with alarm and trip contact including connection to existing RMU relay with PVC insulated PVC sheathed cable galvanized steel strip or wire armoured electric control cables (Heavy duty) with stranded copper conductor of size 1.5 sq mm 10 core 1100 volts grade.
Note:
(i) Foundation drawings need to be provided by OEM/contractor for transformer and need to be approved from accepting officer / Engr-in-charge.
(ii) Factory testing costing deemed to be included in quoted rate. Factory testing should be carried out in presence of representative of accepting officer along with Engr-in-charge. | - | - | - | - |
| - | Supply, laying & testing of HT cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 11000 volts grade, of size 120 sq mm 3 core complete all as specified and directed by Engr-in-charge. | 110 | RM | - | - |
| - | Supply and fixing of cable jointing kit in 11 KV grade cable for indoor termination, heat shrink type, joint complete with jointing material and accessories suitable for XLPE, armoured, Al conductor cable of size 120 to 185 sq mm 3 core complete all as specified and directed by Engr-in-charge. | 1 | Each | - | - |
| - | Supply and fixing of cable jointing kit in 11 KV grade cable for outdoor termination, heat shrink type, joint complete with jointing material and accessories suitable for XLPE, armoured, Al conductor cable of size 120 to 185 sq mm 3 core complete all as specified and directed by Engr-in-charge. | 1 | Each | - | - |
| - | Supply, laying and testing of LT cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 400 sq mm 3½ core complete all as specified and directed by Engr-in-charge. | 90 | RM | - | - |
| - | All as per item No -5- above but of size 3.5 Core 240 Sqmm complete all as specified and directed by Engr-in-charge. | 130 | RM | - | - |
| - | All as per item No -5- above but of size 3.5 Core 185 Sqmm complete all as specified and directed by Engr-in-charge. | 150 | RM | - | - |
| - | All as per item No -5- above but of size 3.5 Core 120 Sqmm complete all as specified and directed by Engr-in-charge. | 190 | RM | - | - |
| - | All as per item No -5- above but of size 3.5 Core 95 Sqmm complete all as specified and directed by Engr-in-charge. | 200 | RM | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
TD18.pdf
Tender Documents • 1.25 MB
BOQ_872230.xls
BOQ • 0.26 MB
AmendNO1t18.pdf
PDF • 0.59 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].