Superintending Engineer EUCC-V LESA Cis-gomti
LESA Bhawan Near Residency, Kaiserbagh, Lucknow-226018
Undergrounding work and installation of 11 KV RMU for Separation of industrial load for reduce the tripping of industrial feeder-Awas Vikas emanating from 33/11 KV S/S Talkatora, Lesa Ciss Gomti, Lucknow
2021_MVVNL_606116_1
20/EUCC(V)/LESA/2021-22
Open Tender
Electrical Works
90 days
33/11 KV S/S Talkatora
As per tender document
2 documents required · 2 mandatory
₹3,540
A/c. No.10101985364, IFSC CODE No. SBIN0003347,SBI
₹23,100
13 Aug 2021
26 Jul 2021
31 Jul 2021
26 Jul 2021
31 Jul 2021
26 Jul 2021
Amount
Safe Dragging, loading, carriage and unloading of following store materials with proper stacking from ESC Daliganj to JE dump store and JE dump store to work site within municipal areas.
11 KV 3x185 sq mm XLPE cable
11 KV 3x185 sq mm O/D C/J Kit
11 KV 3x185 sq mm I/D C/J Kit
11 KV 3x185 sq mm C/J Kit S/th
ST pole 11 mtr long
M.S.channel 100x50 sq mm
M.S.Angle 65x65x6 sq mm
11 kv pin insulator
M S Earthing Rod 20x2500 mm
11 kv pin with nut
1x240 LT XLPE Cable
Pipe boring type earthing minimum 20 mtr deep from ground level or upto water level with B class G.I. pipe 2 " dia. Connection of equipment with earthing included in the job as per specification/norms for 11 KV RMU
Digging of pit in Kachcha/Pakka land in depth upto 1/6 length of pole, Dragging of STP from nearby place/dump, Erection of single pole along with stone pad in bottom with proper alignment on 11 mtr long ST pole and refilling with ramming of earth
Grouting of pole in depth 3 feet below ground lable in ratio 1:4:8 in cement, sand and brick ballast as per RESPO norms.
Construction of pole plinth 300 mm x 450 mm above ground level in 1:2:4 in cement, coarse sand and stone gritt as per RESPO norms.
Painting of new erected ST pole with two coat of Red oxide paint, PO red paint at top of pole 2 mtr and balance by two coats of best quality aluminium paint ISI of Berger/Nerolac/Asian paints as per norms.
Fabrication & erection of 11 KV cable exposure type double pole with the provission of bus bar with fixing of necessary clamps and other acessories like danger board,number plate,barbed wire, 9 no. pin insulators with pins, 2NO. MS-CHANNEL & 2no. MS angle for supporting the hoisting on Pole.Its jumpering by single core PVC aluminium cable with proper size of lug. Painting of double pole with one coat of red oxide & two coats of enamel paints (ISI mark). Its grouting in ratio 1:4:8 & plinthing 300 mm above ground level (All material to be arranged by contractor except steel,pole,PVC aluminium cable,earthing rod,Pin & Pin insulator).as per RESPO norms. .
Supply, erection and commissioning of 11 KV RMU 3 way as per approved drawing
Construction of plinth suitable for 11 KV RMU 3 way
Construction of Toe wall around RMU Plinth of size 0.75 x 0.25 mtr. at base and 0.25 mtr. at top as per RESSPO norms by first class bricks in the ratio 1:6, base concreting of the wall to be done in ratio 1:6:12 and plaster 12 mm thick in ratio 1:4 (All materials shall be provided by contractor).
Fabrication and erection of RMU fencing with tennis wiremesh 10 SWG (37mmx50mm), 2.5 mtr height as per drawing along with Fabrication of one number gate made of MS angle, MS channel, MS Flat together with locking arrangement and its installation (All materials shall be provided by contractor).
Laying of 11 KV XLPE cable 3x185 sq mm S/C by digging of trench 900 mm deep & 600 mm wide its boxing with bricks & sand, laying of cable & filling of sand up to top cover of trench properly levelling & ramming. The ferruling of cable is also included in this work (All materials shall be provided by contractor except 11 KV cable)
Laying of 11 KV XLPE cable 3x185 sq mm D/C by digging of trench 900 mm deep & 750 mm wide its boxing with bricks & sand, laying of cable & separation of cables by brick wall, filling of sand upto top cover of the trench properly levelling & ramming & covering with stone slab after laying of cable. The ferruling of cable is also included in this work (All material will be provided by contractor except 11 KV cable)
Laying of 11 KV 3x185 sq mm XLPE single cable in HUME Pipe 150 mm dia by digging of cable trench of suitable size as per Site Condition (All materials shall be provided by contractor except 11 KV cable)
Laying of 11 KV 3x185 sq mm XLPE single cable in G.I./M.S. Pipe 100 mm dia by digging of cable trench of sutiable size as per site condition (All materials shall be provided by contractor except 11 KV cable)
Laying of 11 KV 3X185 sq mm XLPE single cable by drill method
Laying of 11 KV 3X185 sq mm XLPE single cable by drill method through HDPE Pipe 100 mm dia at road crossing (All materials shall be provided by contractor except 11 KV cable)
11 KV Single Cable laying in existing trench (All materials shall be provided by contractor except 11 KV cable)
Digging of pit of size 3x2x1 mtr. for making straight through joint 11 KV work involved filling of soil levelling and ramming of the same.
Making Heat & shrinkables joints of following sizes and types 11 KV 3x185 sqmm XLPE cable by Heat and shrinkables jointing kits. (Jointing kit will be provided by deptt. )
Straight through for 11 KV 3x185 sqmm
Outdoor/Indoor end termination kit for 11 KV 3x185 sqmm XLPE cable
Hoisting of 11KV, 3x185 sq mm XLPE on D/P with G.I. pipe 4" dia , clamp nut and bolt and other required material (All materials shall be provided by contractor except 11 KV cable)
Hoisting of 11KV, 3x185 sq mm XLPE in RMU Pannel, clamp, nut and bolts (All materials shall be provided by contractor except 11 KV cable)
Re-Hoisting of Existing 11 KV 3x185/120/70 sq. mm XLPE cable on D/P with GI Pipe 4" dia clamp, nut and bolts (All materials shall be provided by contractor except 11 KV cable)
Straightening of Tillted Pole
Re-Grouting/Concreating & Plinthing up to 300 mm above from Ground level of existing Poles
Earthing of Poles with M.S.earthing rod 20x2500 mm, Earth wire with nut and bolt as per RESSPO norms (All materials shall be provided by contractor except MS-Earthing Rod).
High Pressure Testing
Supply & Fixing of Cable Root Marker Stone of 11 KV
Dismantaling of 11 KV existing O/H line & taking down of existing ACSR Conductor and rolling back of same.
Dragging, loading and carriage with unloading of dismantled materials as scraps from site to Daliganj Store/ J.E.dump Store
A. A. ENGINEERING CO.
ARIHANT ELECTRIC COMPANY
Sidhi Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid