Supplying, Installation, testing and Commissioning of Fire Alarm System and Fire Extinguisher at IPandT Building, Port Blair
2022_APWD_6204_1
140/NIT/WSD/2021-22
Open Tender
Miscellaneous Works
Works
30 days
Port Blair
Please refer Tender documents.
4 documents required · 4 mandatory
₹0
₹4,237
24 Jun 2022
11 Jun 2022
20 Jun 2022
11 Jun 2022
20 Jun 2022
13 Jun 2022
11 Jun 2022 - 20 Jun 2022
Amount
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
2 x 1.5 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying , installation, testing & commissioning of 4-8 zone fire alarm panel shall be microprocessor based system UL 864, NFPA 72 standards have switch mode power supply, battery backup and in built charger, 18 gauge CRCA sheet with Epoxy powder coated finish , have front panel key/lock facility, operation on 120V-220V, 50/60 Hz AC main power supply .The panel shall have 2x16 line character dot matrix LCD display,Tactile keypad. It shall have user/admin password protection for keypad function, inbuilt transient protection for power supply and mother board, configure as any zone as alarm or supervisory alarm verification. It shall have one commen fire relay, one common fault and supervisiory relay. These panel have Resistable / steady 24V DC for compatible for 4 wire detectors.It shall have walk test and drill test facility and have two NAC output facility. NAC shall be progrmmed as auto silence/silence and inbuilt RS 485 communication. These panel have Maximum 16 panels or repeaters can be connected in a single network through RS-485. The panel has provision to have zone wise sounder output and/ or zone wise relay output and these communication will happen through RS-485 network. It shall be compitible with all types of conventional detectors and shall have IP- 50 rating UL Listed. Make: RAVEL or equivalent.
Supplying , installation, testing & commissioning of photo electric smoke detector with 360 digree visibility, dual blink LED, operating voltage on 9VDC to 33VDC. It shall support polarity free wiring and support response indicator. It shall be IP 42 rating. It shall be UL listed Make : Ravel or equivalent.
Supplying , installation, testing & commissioning of conventional type sounder wall mounted type rated at 100 +5DBA @ 1m for Audible annunciation, Fire Sires Sound, ABS - Make: Ravel or equivalent.
Supplying , installation, testing & commissioning of surface mounted Call Point (Break glass type) in manufacturers prescribed matching red enamel outlet box complete with key operated test - reset lock, as per all requirements of technical specifications & contracts works, Make: Ravel or equivalent.
Supplying of mechanical foam based portable Fire extinguisher, Spot pressure type, 09 ltr, make:- CEASE FIRE or equivalent.
Supplying of ABC powder based portable (Spot press type), 06 Ltr. Fire Extinguisher, make:- CEASE FIRE or equivalent.
Supplying of CO2 based Squeeze Grip type (Stored Pressure), 02 Kg.xtinguisher (0.2 Kg.) , make:- Fire Extinguisher, make:- CEASE FIRE or equivalent.
AKABEA INFRASTRUCTURES PRIVATE LIMITED
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .