REPAIR / MAINT OF INTERNAL ELECTRIC SUPPLY WORKS IN CERTAIN MD/ OTM ACCN OF ZONE-IB AREA AND REPAIR / MAINT OF SEWAGE PUMP HOUSE AT JAIPUR MIL STN
2020_MES_408530_1
GE/J-57/2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
270 days
JAIPUR
As per NIT
5 documents required · 5 mandatory
₹500
GE JAIPUR
₹50,000
Yes
2 Mar 2021
31 Dec 2020
29 Jan 2021
31 Dec 2020
27 Jan 2021
14 Jan 2021
31 Dec 2020 - 13 Jan 2021
Amount
Taking down carefully surface aluminum or copper point wiring with PVC casing capping or conduit (light, fan, socket, bell or power) including fixture and fittings such as switches, ceiling rose, regulators, sockets, light fittings etc and making good disturbed surfaces complete.
M&L for rewiring point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 sqmm (Green) drawn concealed conduit and terminated in and including modular metal flush boxes 1.0mm thick for mounting modular cover plate & frame, switches, sockets, fan regulators as required for one light point controlled by one switch.
All as per item No. 02 here-in-before but one fan point controlled by one switch.
All as per item No. 02 here-in-before but one light point controlled by two, two way switch.
All as per item No. 02 here-in-before but one socket outlet 6 amp controlled by one switch on the same board with other switches.
All as per item No. 02 here-in-before but one socket outlet 6 amp controlled by one switch on indepdendent board.
All as per item No. 02 here-in-before but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 4.0 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 4.0 sqmm (Green) drawn into into existing concealed conduit and terminated in and including modular metal flush boxes for mounting modular cover plate & frame for one socket point 16 Amps controlled by one switch.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 1.5 Sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings/fixing accessories and unwelded sunken galvanised pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3 mm thick phenoic laminated white sheet cover for mounting switches, scokets, fan regulators as required for one light point controlled by one switch.
All as per item No. 9 above but one fan point controlled by one switch.
All as per item No. 9 above but one light point controlled by two, two way switch.
All as per item No. 9 above but socket outlet 6 Amps controlled by one switch on the same board with other swithces.
All as per item No. 9 above but socket outlet 6 Amps controlled by one switch on independent board.
All as per item No. 9 above but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 4.0 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 4.0 Sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings/fixing accessories and unwelded sunken galvanised pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3 mm thick phenoic laminated white sheet cover for mounting switches, sockets as required for one 16 Amps socket outlet point controlled by one switch on independent board.
M&L for point wiring with 1100 volts grade PVC insulatd FRLS multistranded copper conductor cable 1.5 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 1.5 Sqmm (Green) drawn into and including PVC casing-capping not less than 32x16 mm ISI marked ivory colour with all fittings/fixing accessories and unwelded sunken galvnised pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3mm thick phenlic laminated white sheet cover for mounting sheet cover for mounting switches, sockets, fan regulators one light point controlled by one switch.
All as per item No. 16 above but one light point controlled by two, two way switch.
All as per item No. 16 above but one fan point controlled by one switch.
All as per item No. 16 above but one socket outlet 6 Amps controled by one switch on the same board with other switches.
All as per item No. 16 above but one socket outlet 6 Amps controlled by one switch on independent board.
All as per item No. 16 above but one bell point controlled by one bell push.
M&L for point wiring with 1100 volts grade PVC insulatd FRLS multistranded copper conductor cable 4.0 Sqmm (Phase-Red, Neutral-Black) and earth continuity conductor 4.0 Sqmm (Green) drawn into and including PVC casing-capping not less than 32x16mm ISI marked ivory colour with all fittings/fixing accessories and unwelded sunken galvnised pressed steel terminal boxes of thickness not less than 1.0mm covered with 3mm thick phenlic laminated white sheet cover for mounting sheet cover for mounting switches, sockets for one 16 Amps socket outlet point controlled by one switch on independent board.
S&F angle holder, insulated polycarbonate body with back plate complete.
S&F switch piano flush button single pole one way 6 Amp complete.
S&F switch piano flush button single pole one way 16 Amp complete.
S&F flush type, 6 Amp, single pole, two way complete
S&F bell push, flush type, 6 Amps 240 volts complete.
S&F socket outlet, 2-in-1, 3 pin 6 & 16 Amps flush type compete.
S&F socket outlet, 2-in-1, 3 pin 6 Amps flush type compete.
S&F hum free electronic step fan regulator 120-280 volts of 100 watts capacity (socket type) including connecting up complete.
S&F switch modular 1 way 6 Amps, 230 volts, 1 module.
S&F modular socket 6 Amps, 2/3 pin combined 2 module AC 230 volts.
S&F modular switch 1 way 16 Amps, 230 volts, 1 module.
S&F modular socket 6/16 Amps, 2/3pin combined 2 module AC 230 volts.
S&F modular fan regulator 120 watts, 2-module AC 230 Volts.
S&F switch modular 2 way 6 Amps, 230 volts, 1 module.
S&F modular bell push 6 Amps 1 module.
S & F modular blanking plate 1 module.
S&F modular white cover plate with frame and metal flush box 1/2 module.
S&F modular white cover plate with frame and metal flush box 3 module.
S&F modular white cover plate with frame and metal flush box 4 module.
S&F modular white cover plate with frame and metal flush box 6 module.
S&F modular white cover plate with frame and metal flush box 8 module.
S&F door bell AC 240 volts, single pole complete.
S&F in replacement switch modular 1 way 6 Amps, 230 volts, 1 module.
S&F in replacement modular socket 6 Amps, 2/3pin combined 2 module AC 230 volts.
S&F in replacement modular switch 1 way 16 Amps, 230 volts, 1 module.
S&F in replacement modular socket 6/16 Amps, 2/3pin combined 2 module AC 230 volts.
S&F in replacement modular fan regulator 120 watts, 2-module AC 230 Volts.
S&F in replacement switch modular 2 way 6 Amps, 230 volts, 1 module.
S&F in replacement modular bell push 6 Amps 1 module. Make : Legrand Arteor series/ Schneider Zencilo series/Crabtree Murena series or equivalent as approved by GE.
S & F in replacement modular blanking plate 1 module. Make : Legrand Arteor series/Schneider Zencilo series/Crabtree Murena series or equivalent as approved by GE.
S&F in replacement modular white cover plate with frame and metal flush box 1/2 module.
S&F in replacementin replacement modular white cover plate with frame and metal flush box 3 module.
S&F in replacement modular white cover plate with frame and metal flush box 4 module.
S&F in replacement modular white cover plate with frame and metal flush box 6 module.
S&F in replacement modular white cover plate with frame and metal flush box 8 module.
S&F ceiling rose 3 plates polycarbonate body complete.
M&L for sub main wiring along with earth continuity conductor with, PVC insulated FRLS multistranded copper conductor cable (Phase-Red, Neutral-Black, Earth-Green) drawing into and including concealed rigid non metallic PVC conduit, medium grade, ISI marked ivory colour along with accessories 2x 6.0 Sqmm + 1x6.0 Sqmm earth wire in 20mm dia conduit.
All as per item No. 59 above but 2x10 Sqmm + 1x10 Sqmm earth in 25mm dia conduit.
M&L for earthing with galvanized steel earth plate electrode 600mmx 600mmx6mm thick buried directly in ground (earth pit not less than 2.25 meter deep below normal ground level) with the top edge of the plate not less than 1.5m below normal ground level connected to galvanized earth lead wire 4mm dia by means of steel bolts, nuts, check nuts and washers all as shown in electrical plate No. 03 of SSR Part -I connected to earthing point and including 15mm bore light grade G.I. protection pipe (upto 7.5 mtr from edge of the pit), PCC pit in mix 1:3:6 type C1 with PCC 1:2:4 type B-1, 40mm thick cover, watering arrangement with funnel and wire mesh and 20mm bore light grade G.I. watering pipe, common salt and charcoal filling, necessary excavation and earh work including testing on completion.
S&F MCB distribution board, powder coated, CRCA steel sheet, degree of protection IP 43, IK-09 with reversible double door, recess mounted , having insulated 100 Amps tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required with SPN, 240 volts, 4 ways. Make : Legrand Cat Ref No. 507610 or Schneider Cat No. A9HSND04 or Hager or equivalent as approved by GE.
All as per item No. 62 above but SPN, 240 volts, 8 ways. Make : Legrand Cat Ref No. 507611 or Schneider Cat No. A9HSND12 or Hager or equivalent as approved by GE.
All as per item No. 62 above but SPN, 240 volts, 12 ways. Make : Legrand Cat Ref No. 507612 or Schneider Cat No. A9HSND12 or Hager or equivalent as approved by GE.
All as per item No. 62 above but SPN, 240 volts, 2 ways. Make : Legrand Cat Ref No. 5077 91 or Schneider or Hager or equivalent as approved by GE.
S&F MCCB four pole, 125 Amps, 16 KA thermally adjustable between 70 to 100% including 4 spreader link set of same make as that of MCCB for connection, required lugs as required. Make : Legrand Cat Ref No.420016 or equivalent in Schneider/Hager or equivalent as approved by GE.
S&F MCB distribution board, tripple pole and neutral, powder coated CRCA steel sheet, suitable for MCCB incomer upto 160 Amps, 4 way 415 volts, degree of protection IP 43, IK-09 with reversible double door, recess mounted, having 250 Amps insulated tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required. Make : Legrand Cat Ref No. 507745 or equivalent in Hager/Schneider or equivalent as approved by GE.
S&F MCBs of 'C' series single pole 6 to 32 Amps having breaking capacity 10 KA, ISI marked including required wiring connections with copper lugs of suitable size provided in MCB DBs complete. Make : Legrand Cat Ref No. 408587 to 408595 or equivalent in Schneider/Hager or equivalent as approved by GE.
All as per item No. 68 above but double pole 10 to 32 Amps. Make : Legrand Cat Ref No. 408631 to 408636 or equivalent in Schneider/Hager or equivalent as approved by GE.
S&F LED batten (1.2M) made of CRCA sheet housing with a PC glossy diffuser duly prewired connection having a nominal system lumen output of 2000 lumens at a minimum system efficacy of 125 lumen per watt and total power consumption not more than 16 watt including driver. It has a rated system life time of 40000 burning hours at L70 and should have a color temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete. Make : Philips Cat Ref No. Endura Next Batten "BN 308C LED 20S -6500 L 120 PSU WH" , CG/ Bajaj/ Panasonic or equivalent as approved by GE.
S&F LED batten (1.2M) made of CRCA sheet housing duly prewired connection having a nominal system total power consumption not more than 20 watt including T8 LED tube life time of 15000 burning hours at L70 and should have a color temperature of 6500K, CRI>80, THD<10% and PF>0.95 complete. Make : Philips/ Crompton /Havells / Bajaj/Panasonic or equivalent as approved by GE.
S&F LED fixture 10 watt having lumen output 100 lumens per watt including connection. Make : Philips Cat Ref No. BN 021C LED 10S-6500 PSU GR S1 or equivalent in CG/Panasonic/Havells or equivalent as approved by GE.
S&F LED bulk head fitting 9 watt IP 66 & IK 09 with pressure die cast aluminium housing & polycarbonate diffuser duly pre wired connection with 0.75 Sqmm PVC insulated & sheathed three core flexible multi stranded copper conductor cable all as per Philips Cat Ref No. WT 202W LED 6S PSU S2 PC or equivalent in Panasonic/Havells/CG or equivalent as approved by GE.
Supply and fix in replacement 10 watts LED T-lamp B-22 base (warm white/Golden Yellow) 100 lumens, AC 220 volts . Make : Philips Part No. 9290018611 or equivalent in Panasonic/ CG/ Bajaj or equivalent as approved by GE.
Taking down MCB distribution boards with incoming and outgoing controls any make any capacity after disconnecting complete.
Taking down carefully sub main wiring with PVC casing capping/PVC surface conduit and making good disturbed surfaces complete.
S&F in repair recess mounted LED panel of size 1'x1', 17 watts 1500 lumen output having luminous efficacy >85 lm/W, 6500K, 50Hz, p.f. >0.90, CRI80, THD <30%, , Long Life 25000 burning hours including making connection Complete.Make - Philips ref Cat Part No RC 375B LED 15S W30L30PCV IN or equivalent as approved by GE..
Supply and fixing in repairs energy efficient recessed mounted LED luminaire suitable for 2'x2' grid ceiling with fullglow fully diffused diffuser and lumen output of 3600 lumens having constant current electronic driver of 36 watt duly connected with 0.5 sqmm white colour PVC insulated & sheathed three core flexible multi stranded copper conductor cable as required. Make - Philips ref Cat Part No RC 308B LED 36 S -6500 G4 L60 W 60 PSU OD or equivalent as approved by GE. .
Supply, installation, testing and commissioning of LT panel board fabricated out of 2mm thick stainless steel (SS 316) with copper bus bar 4 pole equal of capacity in colour code R, Y & B, 200 Amps 415 Volts indoor type wall mounted of size not less than 750mmx650mmx250mm, installed on procelain insulators with bus bar chamber. The panel shall be dust and vermin proof, protection class IP 42 class, front opening & compartmental type with approach for cable entry and for easy maintenance duly internally wired with FRLS, PVC insualated stranded copper conductor cable of 1.0 Sqmm including LED indicator for R, Y & B and comprising of the following :- Incoming : One number MCCB 125 Amps 4 pole 16 KA 415 Volts, 70-100%, 50 Hz Make Legrand Cat No. 4200 16 or equivalent in Hager/Schneider. Outgoing : (a) Single phase tamper proof meter with optical port 10 to 60 Amps-04 Nos. Make : Secure Saral or equivalent in HPL/L&T. (b) MCB DP 40 Amps 'C' series 10 KA AC 240 volts-05 Nos.
M&L for brick work with sub class 'B' bricks, straight or curved on plan to any radius in half brick thick wall build on cement mortar 1:4 and 2 coats of white/colour washing to match the surface complete.
S&F in repair switch piano flush button single pole one way 6 Amp complete.
S&F in repair switch piano flush button single pole one way 16 Amp complete.
S&F in repair socket outlet, 2-in-1, 3 pin 6 & 16 Amps flush type compete.
S&F in repair socket outlet, 2-in-1, 3 pin 6 Amps flush type compete.
S&F in repair hum free electronic step fan regulator 120-280 volts of 100 watts capacity (socket type) including connecting up complete.
Excavation in trenches not exceeding 1.5 m wide and n.exc. 1.5 m deep for foundation of poles/stay/cable etc including getting out in any type of soil complete all as specified and directed
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in hard and dense soil
Removing excavated material n.exc. 50m and depositing where directed at a level n.exc. 1.5 m above the starting point.
Sand cushioning to cable with dry fine sand in trenches 8 cm below the cable and 15 cm above the cable after laying complete.
Bricks laid in trenches flat with width equal to length of brick for cable protection well burnt sub class 'B' laid across the cable complete.
Dismantling and taking out UG cable any size unserviceable items fixed in any position and removal from site, all as directed.
S&F 1100 volt grade heavy duty XLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 16 Sqmm nominal cross section 4 core laid in trenches,fixed to pole or passing through pipes including all necessary clamps,nuts, bolts washers complete all as specified and directed.
S&F 1100 volt grade heavy duty XLPE cable with PVC insulated aluminum conductor served with inner sheathing of PVC tape armoured with galvanized steel strip or wire and overall PVC sheathed of size 10 Sqmm nominal cross section 2 core laid in trenches,fixed to pole or passing through pipes including all necessary clamps,nuts, bolts washers complete all as specified and directed.
Labour and tools for taking out single stage non clogg submersible centrifugal sewage pump set upto 4.0 KW, 3 phase, 415 volts, 50Hz, from sewage sump with submersible cable, SWR rope ete after disconnecting electric connection for ascertaning, testing the pump set and relowering the same at original position including making necessary connection all required at site under relevant item of BOQ as supply only.
Supply only jointing kit for submersible cable.
Supply only end bush for submersible cable
Supply and fix only linked chain made of round MS bar of 6.0 mm dia.
Preparation of old painted steel surface of pump and motor and applying two coats of synthetic enameled paint.
M&L for transporting the single stage non clog submersible type sewage pump set of capacity upto4.0 KW to auth service Centre and dismantling of pump and motor, repair/ replacing defective parts as ordered and re-assembling and testing including replacing worn out nuts, bolts, washers complete as required at site and making electrical all as specified and directed at site. Note : (a) Lowering and lifting of sewage pump set in sewage well shall be measured and paid for separately under successive item here in before. (b) Spares shall be measured and paid for separately under successive items here-in- after.
Rewinding the stator of Pump Model KRTUK -100, 210/34 with supper enameled copper wire of suitable size and class of insulation as per original including insulation paper, sleeves, thimbles etc.
Rewinding the stator of Pump Model KRTUK -100, 180/14 with supper enameled copper wire of suitable size and class of insulation as per manufacturer's recommendation including insulation paper, sleeves, thimbles etc.
Supply only CI Impellor of KRTUK-100-210/44 as per existing.
Supply only CI Impellor of KRTUK-100-180/14 as per existing.
Supply only Wearing Ring all as specified as per existing.
Supply only Centering Ring all as specified as per existing.
Supply only Moisture Portion of Motor as per existing.
Supply only Deep groove ball bearing upper as per existing.
Supply only deep groove ball bearing lower as per existing.
Supply only Mechanical seal upper as per existing.
Supply only mechanical seal lower as per existing.
Supply only Shaft protection sleeve as per existing.
Supply only Bearing sleeve as per existing.
Supply only Gasket "O" ring set as per existing.
Supply only Set of fastener as per existing.
Supply only Temp sencer as per existing.
Supply only AISI rope with thrust insert shackle lock complete as per existing.
Supply aonly oil suitable for pump
S&F PVC green hose pipe flexible type heavy size duty 80 mm dia complete with clamps and coupling joint.
S&F PVC green hose pipe flexible type heavy size duty 100 mm dia complete with clamps and coupling joint.
Taking down old defective worn out rubber gasket and supply & fixing rubber gasket 3mm thick, making holes for fixing nut & bolts incl replacing 04 Nos 5/8" dia, 75mm long nut, bolts & washers, checking for any leakage all as required.
Taking down defective leaked MS flange 100mm bore, rethreading the pipe/welding MS flanges to pipe, replacing defective rubber gasket 3mm thick and refixing the pipe in original position including necessary nut, bolts & washer all as required.
Supply and fix in replacement GI pipe medium grade 100 mm bore, both end threaded including making both end connection with existing pipe/pump with necessary nut, bolts and washers of existing size properly to arrest leak all as required.
Supply and fixing in replacement GI flange internally threaded having 04 nos hole with rubber gasket 3mm thick, 04 Nos 5/8" dia 100mm long MS bolts with nut and double washers, suitable for GI Column/pipe line of size 100 mm bore with nuts bolts and washers complete.
Taking down defective rubber coupling and supply and fixing new flexible coupling for 6 BHP sewage pump set of same size and dia meter including fixing new nuts, bolts and washer and making proper alignment of engine and pump set all as required.
M&L for servicing of 6 BHP diesel engine by draining out old engine oil, cleaning sump, replacing defective fuel filter, filling new engine oil , cleaning the sewage pump thoroughly, including replacing minor spares as required at site all as required.
Replacement of submersible cable PVC insulated and overall round sheathed 2.5 sqmm 3 core ISI marked heavy duty.
Labour & tools for scooping taking out sludge and foreign material and cleaning of main sewage sump of any size not exceeding 10 meter depth with tool and plant as required at site for draining of sewage water and closing of main incoming pipe line chamber by any means during cleaning of sewage sump and after cleaning the sump to open the incoming sewage pipe line and safe disposal of the sludge at place note more than 1.5 KM away at such a place which is not detrimental to public health. Note : Rate also includes to dispose the sewer water hygienically to avoid any inconvenience to users during cleaning of of sewage well.
Cleaning the surrounding areas of sewage pumping installations upto 100mtrs, taking out scrubs/bushes/grass, cutting out branches of trees upto 100mm girth, taking out the sludge away from sewage pump set and disposing the same at safe place and maintaining the area neat and clean during entire contract period upto date of completion all as required.
Taking up pipe 100 mm dia GI pipe line from trenches/PCC pillars by opening nuts, bolts, washers and cleaning the inner surface thoroughly by using wire brush to clear the entire sludge all as directed at site.
Supply and fix sluice Valves flanged type of class 1.6 PN of 100 mm bore with all accessories such as stainless steel spindle, gate, MS round wheel to operate including 3mm thick rubber washer, nut, bolts and washers complete.
Renewal of non-return valve flanged type with all accessories including 3mm thick rubber washer, nut, bolts and washer complete.
Renewal of mild steel plain or chequered plate Fe-290 (Gde E-165), 5 mm thick, cutting in size to cover the cable duct complete.
Renewal of digital type ammeter 0-100 Amps 3 phase with CTs 100/5 Amps including making necessary connection in existing LT panel complete.
Supply and fixing in replacement in existing LT panel digital type voltmeter 0-500 volts including making necessary connection complete.
M & L for repairs to existing DOL starter 5 HP by disconnecting elect connections, taking out starter from LT panel, opening the starter, taking out defective power contactor/relay/no volt coil/timer unit and supply the fixing the defective parts of same make and capacity, testing the starter and refixing the same in existing place, making necessary connection and testing the starter complete.
M&L for PCC block Type B1 1:2:4 (20mm graded aggregate) in CM 1:4 with angle iron protection all around as per existing block at site for covering roof of sewage sump complete. Note : Angle shall be measured and paid separately.
M&L for mild steel bars 10mm dia Fe-410-W (Gde. E-250), sut to length, bent to shape required, including cranking, bending, spirally as required for reinforcement of PCC slab cover for sewage sump complete.
M&L for framed work for RCC cover for sewage sump with angle iron Fe-290 (Gde E-165) of size as required at site including cutting the angle to desired shape, welding frame to match the same to fix on existing opening complete.
S&F in replacement mild steel plate, plain or chequered, 5mm thick Fe-290 (Gde E-165), cut to size or shape as per site requirement including applying two coats of black bituminous plate over a coat of red oxide primer complete.
Schedule of Credit
SHREE BHAGWATI ENTERPRISES
M/S Sheeba Enterprises
M/S TRADE LINKERS
Stuti Trading Company
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .