| 3 | Rejected-Technical 1 102 FIRST FLOOR PERIYAR PATHAI WEST 10 ARUMBAKKAM CHENNAI TAMIL NADU 600106 | CHENNAI | TAMIL NADU | 600106 | - | Rejected-Technical This firm submitted completed similar works documents are not meet as per Tender norms. (This firm not completed minimum 30KVA UPS works) |
Tender Value
Refer Docs
EMD Value
₹33,410
Closing Date
16 Aug 2022, 6:00 pmClosed
The Registrar
IMSc, Taramani, Chennai-113
Design Supply Installation Testing and commissioning of 2 x 30 KVA UPS machine and its associated works for HPC Improvement at IMSc Chennai 113
2022_IMSC_704210_1
IMSc / ELEC / e-TR-03 / 2022
Open Tender
Electrical Works
Works
150 days
IMSc Taramani
Solvency, Similar works, IT Turnover, IT returns, OEM authorisation, Company details.
5 documents required · 5 mandatory
₹0
₹33,410
29 Nov 2022
1 Aug 2022
18 Aug 2022
1 Aug 2022
16 Aug 2022
1 Aug 2022
1 Aug 2022 - 5 Aug 2022
Amount
UPS Machine and its accessories
Design, Supply, Installation, Testing and Commissioning of 1 x 30 KVA, Three phase Input and Three phase output, online double conversion IGBT based PWM inverter, pure sine wave, 415 V, 50 Hz UPS System with independent copper wounded suitable capacity isolation transformer as per detailed Specifications specified in the Tender book.
1 x 30 KVA, 415 V, 3 Phase Input and Output UPS Modules (Rectifier / Charger + Inverter) with all accessories.
Supply and installation of Battery Banks with SMF VRLA Batteries of 34 no of 65 AH, 12 Volts for back-up time of 20 minutes at full load includes connecting power cables between UPS and batteries, battery circuit breaker, metallic fabricated racks and standard accessories and completion of work as per specifications suitable for 1 X 30 KVA UPS machines including all end terminations and as directed by engineer in charge.
Supply and fixing of 100 A, 4 pole, 3 phase and neutral STS , TWO input and SINGLE output STS switches suitable for 3 phase UPS power distribution with auto transfer facility < 5 ms including communication interface and other specification indicated in section V in the tender documents.
Supply, Installation, testing and commissioning of 1100V grade following sizes XLPE insulated and PVC sheathed Armoured CU / ALU. UG cables including necessary cabling works as specified in section-V. In build up trenches, on walls with proper clamping poles and through embedded pipes on floor including supply and installation of cables and fixing all material as per the scope of work. Including removal of existing cables in the panel.
4C x 35 sq mm ALUMINUM conductor (XLPE) cable
4C x 16 sq mm Copper wiring with required heavy duty PVC conduit and its accessories including End termination and earthing.
End termination of the following 1100 v grade XLPE insulated AR / Copper / Aluminium conductor UG cables including supply of single compression cable gland crimping lugs and gland earthing. ( Aluminium socket for aluminium cable and copper socket for copper cables )
4C x 35 sq mm ALUMINUM conductor (XLPE) cable
Supply and fixing of 150 / 160 A, HRC, 3 phase and neutral SFU / SDF unit assembled in MS metal sheet enclosure with necessary end termination and earthing with required HRC fuses.
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .