Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.0 LAccepted-Finance A 14 USHA SADAN NEAR POST OFFICE COLABA MUMBAI 05 | MUMBAI | MUMBAI | MAHARASHTRA | 400005 | L1 | Accepted-Finance Being lowest quoted amt | |
| 2 | L2₹11.8 L+₹1.9 L (18.8%)Accepted-Finance | L2 | Accepted-Finance Higher quoted amt than L1 | |
| 3 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Others-Payable address in DD is wrong |
| Sl No | Description | Qty | Unit | S S enterprises L1 | M/s Rashid Mohammed L2 |
|---|---|---|---|---|---|
| 1.00 | Taking down existing unserviceable point wiring of any description / type / size of light / fan /power /two way /bell etc on TW batten/ conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling so as to match with the existing finishes all as specified & directed by Engr in Charge | 281 | Point | 90 ₹25,290 Lowest | 120 ₹33,720 |
| 2.00 | Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc. for stone concrete block or slab walls and making good, cutting exceeding 20cm girth | 100 | RM | 100 ₹10,000 Lowest | 150 ₹15,000 |
| 3.00 | M & L for Point wiring with 1.5 Sq mm copper conductor single core PVC insulated FRLS 1100 Volts multistranded drawn through and including rigid PVC Casing and Capping as required at site and conduit accessories of suitable size medium grade in existing MS boxes duly cleaned as per existing site covered with new suitable sheet 3 mm thick for fixing switches / sockets/ regulators etc including running up of 1.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly and making good surface including taking down of old unserviceable point wiring and accessories all as specified for One light/fan point controlled by one, one way switch 5 amps SP all as specified and directed by Engineer-in-Charge | 50 | Point | 1,000 ₹50,000 Lowest | 1,250 ₹62,500 |
| 4.00 | All as per Sl item No. 03 here in before, but for One light point controlled by two 2 - way switch 5 amps, SP | 2 | Point | 950 ₹1,900 Lowest | 1,250 ₹2,500 |
| 5.00 | All as per Sl item No. 03 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board . | 24 | Point | 950 ₹22,800 Lowest | 1,250 ₹30,000 |
| 6.00 | All as per Sl item No. 03 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board. | 16 | Point | 500 ₹8,000 Lowest | 650 ₹10,400 |
| 7.00 | All as per Sl item No. 03 here in before, but for One Bell point controlled by one, one way switch 5 amps, SP | 2 | Point | 950 ₹1,900 Lowest | 1,250 ₹2,500 |
| 8.00 | All as per Sl item No. 03 here in before, but for using 4 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 4 Sq mm copper conductor PVC insulated cable as earth continuity conductor | 18 | Point | 2,500 ₹45,000 Lowest | 2,500 ₹45,000 Lowest |
| 9.00 | M & L for Point wiring in concealed conduit complete all as specified with 1100 volts grade 1.5 sqmm PVC insulated FRLS, multistraded copper conductor conforming to IS:694:1990 with ISI marking (For Phase, Neutral and Earth) in and including Non mettalic PVC rigid conduit medium grade with ISI mark of size 20 mm dia with all accessories concealed in wall / ceiling / roof etc, for fixing modular switches, sockets fan regulators etc of suitable modules and earth wire to be connected to common earth dolly and making good surface including taking down of old unserviceable point wiring and accessories all as specified and directed by Engineer-in-Charge | 100 | Point | 1,100 ₹1,10,000 Lowest | 1,300 ₹1,30,000 |
| 10.00 | All as per Sl item No.09 here in before, but for One light point controlled by two 2 - way switch 5 amps, SP | 2 | Point | 1,050 ₹2,100 Lowest | 1,300 ₹2,600 |
Tender Value
₹9.9 L
EMD Value
₹19,800
Closing Date
31 Mar 2026, 6:00 pmClosed
AGE I POKARAN
MILITARY ENGINEER SERVICES ASST GARRISON ENGINEER I POKARAN MILITARY STATION POKARAN-345021
REPAIR AND REPLACEMENT OF INTERNAL WIRING AT CERTAIN BLDGS AT CETC NACHANA AND ASCON NODE UNDER AGE I POKARAN
2026_MES_753858_1
8350/E8
Open Tender
Civil Works
Item Rate
POKARAN
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
AGE I POKARAN
₹19,800
Yes
28 Apr 2026
23 Feb 2026
3 Apr 2026
24 Feb 2026
31 Mar 2026
17 Mar 2026
3 Mar 2026 - 10 Mar 2026
Taking down existing unserviceable point wiring of any description / type / size of light / fan /power /two way /bell etc on TW batten/ conduit including removal of batten / conduit / gutties / wooden boards / switches / sockets / regulators/ light fittings etc and removal of unserviceable material out of site area and making good the disturbed surfaces of wall/ceiling so as to match with the existing finishes all as specified & directed by Engr in Charge
Cutting chases, pinning in, making good to facings where required and pointing in cement mortar 1:3 to ends or edges of landings, steps, cills, sunshades, shelves, lintels, etc.; and cutting chases for concealed water tubing or concealed conduit wiring, etc. for stone concrete block or slab walls and making good, cutting exceeding 20cm girth
M & L for Point wiring with 1.5 Sq mm copper conductor single core PVC insulated FRLS 1100 Volts multistranded drawn through and including rigid PVC Casing and Capping as required at site and conduit accessories of suitable size medium grade in existing MS boxes duly cleaned as per existing site covered with new suitable sheet 3 mm thick for fixing switches / sockets/ regulators etc including running up of 1.5 Sq mm copper conductor PVC insulated cable as earth continuity conductor along with wiring and connecting to the common earth dolly and making good surface including taking down of old unserviceable point wiring and accessories all as specified for One light/fan point controlled by one, one way switch 5 amps SP all as specified and directed by Engineer-in-Charge
All as per Sl item No. 03 here in before, but for One light point controlled by two 2 - way switch 5 amps, SP
All as per Sl item No. 03 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board .
All as per Sl item No. 03 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board.
All as per Sl item No. 03 here in before, but for One Bell point controlled by one, one way switch 5 amps, SP
All as per Sl item No. 03 here in before, but for using 4 Sqmm single core copper conductor cable of multistranded PVC insulated sheathed FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 4 Sq mm copper conductor PVC insulated cable as earth continuity conductor
M & L for Point wiring in concealed conduit complete all as specified with 1100 volts grade 1.5 sqmm PVC insulated FRLS, multistraded copper conductor conforming to IS:694:1990 with ISI marking (For Phase, Neutral and Earth) in and including Non mettalic PVC rigid conduit medium grade with ISI mark of size 20 mm dia with all accessories concealed in wall / ceiling / roof etc, for fixing modular switches, sockets fan regulators etc of suitable modules and earth wire to be connected to common earth dolly and making good surface including taking down of old unserviceable point wiring and accessories all as specified and directed by Engineer-in-Charge
All as per Sl item No.09 here in before, but for One light point controlled by two 2 - way switch 5 amps, SP
All as per Sl item No.09 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on independent board .
All as per Sl item No.09 here in before, but for One 3 pin 5 Amps switch socket outlet point controlled by one switch on the same board.
All as per Sl item No.09 here in before, but for One Bell point controlled by one, bell push
All as per Sl item No.09 here in before, but for using 4 Sqmm single core copper conductor cable of multistranded PVC insulated FRLS 1100 Volts grade for 3 Pin 15 Amps switch socket combination point on independent board including running of 4 Sq mm copper conductor PVC insulated cable as earth continuity conductor
S & F switch piano single pole flush type 5 amps, 230 volts.
S & F switch piano single pole flush type 15 amps, 230 volts.
S & F single pole Modular switch 1 way 6 Amps, 1 Module
S & F single pole Modular switch 1 way 16 Amps, 1 Module
S & F switch piano two way flush type 5 Amps capacity 230 volts.
S & F modular switch 2 way 6 Amps, 1 Module
S&F bell push 5 A flush type
S&F Modular Bell Push 6A, 1 Module
Supply and fix socket outlet modular type multipurpose 2/3 Pin, 6 amps, 230 volts combined 2 Module
Supply and fix socket outlet modular type multipurpose 3/5 Pin, 6/16 amps, 230 volts combined 2 Module
Supply and fix socket outlet flush type multipurpose 2 in 1, 3 Pin, 5 amps, 230 volts all as specified
Supply and fix socket outlet flush type multipurpose 2 in 1, 3 Pin, 5/15 amps, 230 volts all as specified
S & F switch socket combination flush type multipurpose 2/3 pin 5 amps 2 in 1 230 Volts all as specified.
S & F switch socket combination 5 in 1 multipurpose 3/5 pin 5/15 amps flush typewith complete all as specified.
M&L Modular white cover plate with frame ( both inner & outer plate cover) 1 module
M&L Modular white cover plate with frame ( both inner & outer plate cover) 3 module
M&L Modular white cover plate with frame ( both inner & outer plate cover) 4 module
M&L Modular white cover plate with frame ( both inner & outer plate cover) 6 module
M&L Modular white cover plate with frame ( both inner & outer plate cover) 8 module
S & F Modular ceiling fan regulator stepped socket size (modular) suitable to work on 230 volts complete all as specified, 2 Module
S & F S & F stepped type electronic fan regulator flush type on the existing phenolic laminated sheet etc. as reqd
S&F bell (buzzer / ding dong) working on 230 volts AC Supply
S & F lamp holder insulated body surface bakelite with back plate suitable for angle / batten fittings
Supply and fixing LED light fitting mirror type with high out put diffuser 2 feet, 10 watt 220 V AC decorative type with driver holder and LED lamp including connecting up with three core flexible copper conductor cable of suitable size complete
Supply and fixing LED lights fitting 1x 20W, 220V, AC decorative box type with driver, holder including LED tube light connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete.
supply and fix LED Lamp Retro fit type 9 watts 230 V and all as specified by Engr-in-charge
Supply and fixing LED street light fitting 35 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete.
Supply and fixing round shape or square shape 15 watt 220 volts AC recessed type with high efficiency PMMA diffuser soft glare free light complete with drivers, holders, LED lamp suitable for roof ceiling including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and directed
Supply and fixing LED luminaire 600 mm x 600 mm, 35/36 watt, 220 V AC recessed type with high efficiency PMMA diffuser soft glare free light complete with driver, holders & LED lamp suitable for roof ceiling including connecting up with driver three core flexible copper conductor cases of suitable size complete all as specified and directed
S & F LED light fitting 1x9W / 1X10W bulkhead luminaires including LED light driver holder connecting up with three core flexible copper conductor cable of suitable size all as specified and directed
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and currentcarrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning.incl taking down old unserviceable MCB DB all as specified and directed by Engr-in-charge.
All as per Item No. 45 but for 40 Amps SP MCB
All as per item No. 45 but for 32 Amps SPN MCB
All as per item No. 45 but for 40 to 63 Amps SPN MCB
S & F sheet metal enclosure MCB DB SPN 4 way with 200 amps rated bus bar 240 volts double door with locking system complete incltaking down old unsv MCB DB all as specified and directed by Engineer-in-charge.
All as per Sl item No. 49 here in before, but SPN 8 way DB
All as per Sl item No. 49 here in before but SPN 12 way DB
S & F horizontal type TPN DB 4 way single door made out of CRCA sheet housing duly powder coated & confirming to IS specification complete all as directed by Engr-in-Charge.
S & F Single pole and Neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amps (AC Box) all as specified and directed
S&F MCCBs 415V,25KA, 100 amps 4 Pole suitable for DB including removing the existing unserviceable one and making good the distrubed surface to match with the existing surface.
All as per Sl item No. 54 here in before, but 63 Amps, 10 KA
M & L Submain wiring with 2 runs of single core 4 sqmm PVC insulated FRLS multistranded 1100 volts grade wire, copper conductor drawn through and including non-metalic rigid PVC conduit and conduit accessories of medium grade not not less than 25mm dia including one run of single core 4 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor along with the wiring and connected from DB to DB/main board including taking down old unserviceable submain riwing complete all as specified and as directed.
All as per Sl item No. 56 but 2 runs of single core 6 sqmm and one run of single core 6 sqmm as earth continuty conductor Note :- Two runs of cable, one run of earth wire and one run of PVC conduit will be measured as one unit
All as per Item No. 56 but for submain wiring with 4 runs of single core 6 sqmm including one run of single core 6 sqmm PVC insulated sheated multistranded 1100 volts grade with copper conductor cable as earth continuty conductor. Note :- Four runs of cable, one run of earth wire and one run of PVC conduit will be measured as one unit
Supply and replace Fan condenser 2.5 mfd
Supply and replace fan condenser of 4.00 Mfd
Supply and replace split pins/lock pins for ceiling fans
Supply and replace MS Clamp with rubber bushes, bolts & nuts for ceiling fan along with lock pin all as specified
M & L for repairs to copper inner container like denting, soldering, brazing, leak testing and reassembling of any Ltrs capacity water heater (Geyser) complete all as specified.
Supply and replace Geyser element 2000 watts of any type or as per site requirement
Supply and replace Thermostat
Supply and replace Indicator bulb 230 V suitable for any make and colour.
Supply and replace PVC Cold/Hot water connection pipe 45 cms long 15 mm dia
M & L Rewinding of burnt ceiling fan of 1200 / 1400mm sweep motor with supper enameled copper wire of suitable size including repainting with white colour of any make, type, model incl transportation complete all as specified and directed by Engineer -in-charge.
All as per Item No. 68 but for rewinding of burnt Exhaust fan of 225 / 300mm sweep motor complete all as specified and directed by Engineer -in-charge.
M&L deep grove ball bearings 6202 / 6201 suitable for ceiling fans / exhaust fans of any type all as per specified and directed
S&F of ceiling fan / exhaust fan shaft as per the site requirement all as direted by Engineer-in-charge.
Earthing complete with galvanised steel earth plate electrode 60cm x 60cm x 6mm thick burried directly in ground to a depth not less than 2.25 m below ground level with top edge of earth plate not less than 1.5 m below normal ground level connected to GI earth lead wire 4 mm dia by means of bolts, nut, check nuts and washers etc of galvanised iron and earth lead protected by provision of GI pipe 15 mm bore of medium grade from earth electrode to DBs/Main switch all as shown in Electrical Plate No 3 of SSR Part I and connected to main switch board including excavation and earth work in any type of soil, PCC chamber in 1:2:4 Type B-1 using 20 mm graded stone aggregate 75 mm thick RCC cover in 1:2:4 type B-1 reinforced with 6mm dia bars at 75mm c/c both ways with 12mm dia MS bar handle made to shape, 20 mm dia medium grade GI watering pipe perforated at bottom with funnel and wire mesh, common salt and charcoal filling complete including testing on completion all as specified (Note: GI pipe 15mm dia & GI earth lead 4mm dia upto 7.5 m length is deemed to be included in quoted rate).
Supply and replace Service wire twin core of 10.0 sq mm multistranded 1100 grade
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.48 MB
TenderI.pdf
Tender Documents • 0.78 MB
TenderII.pdf
Tender Documents • 0.64 MB
TenderIII.pdf
Tender Documents • 0.70 MB
appxc.pdf
Tender Documents • 0.59 MB
credit.pdf
Tender Documents • 0.45 MB
BOQ_844370.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .