Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.8 LAccepted-AOC 63 2ND MAIN ROAD NGO COLONY ADAMBAKKAM CHENNAI 600 088 | CHENNAI | CHENNAI | TAMIL NADU | 600088 | L1 | Accepted-AOC Being lowest tenderer | |
| 2 | L2₹15.5 L+₹42,850 (2.85%)Rejected-Finance NO 68 ANJANEYA TEMPLE CROSS OPP M S RAMAIAH HOSPITAL NEW BEL ROAD BANGALORE 560 094 | BENGALURU URBAN | KARNATAKA | 560094 | L2 | Rejected-Finance Being other than lowest tenderer | |
| 3 | L3₹16.3 L+₹1.2 L (8.21%)Rejected-Finance NO 51 TOWN HALL 3RD STREET ARAKKONAM TAMIL NADU 631 001 | ARAKKONAM | RANIPET | TAMIL NADU | 631001 | L3 | Rejected-Finance Being other than lowest tenderer |
Tender Value
₹17.3 L
EMD Value
₹34,600
Closing Date
18 Jun 2022, 6:00 pmClosed
Shri. Narinder Singh, IDSE, SE(SAG)
COMMANDER WORKS ENGINEERS CHENNAI PALLAVAN SALAI CHENNAI 600 002
86521E8 SPL REPS / REPLACEMENT OF BER DG SET ALONGWITH ALLIED WORKS AT OTA UNDER GE STM CHENNAI.
2022_MES_525806_1
86521E8
Open Tender
Electrical and Maintenance Works
Item Rate
120 days
STM CHENNAI
AS PER NIT
9 documents required · 9 mandatory
₹500
GE STM CHENNAI
₹34,600
Yes
21 Jul 2022
23 May 2022
25 Jun 2022
23 May 2022
18 Jun 2022
6 Jun 2022
23 May 2022 - 30 May 2022
Amount
BOQ UPLOADED ON 23 MAY 2022
SCH "A" PART-I (DG SET AND ALLIED WORKS)
Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, etc not exceeding 10 sqm on plan and not exceeding 1.5m depth and getting out in any type of soil all as specified and as directed.
Earthwork is deemed to be carried out by manual method. However mechanised method may be adopted without any extra cost to the government.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm in any type of soil complete all as specified and as directed.
Removing excavated surplus soil to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and as directed.
Fine sieved excavated dry soil laid to required width of trench at bottom and top for cable cushioning all as specified and as directed.
(a) Punned thickness only shall be measured.
(b) The soil used shall be free from sharp grains and deletrious materials like dry / decayed plants etc.,
Common burnt bricks sub class "B" of old size, designation 50, laid dry in trenches with width equal to length of bricks across the cable for cable protection all as specified and as directed.
Taking out existing cable any type / cross section 120 sqmm and supply, laying, connecting and testing XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, in trenches / drawn through pipe / fixed on walls / bare in road crossings / paths / drains / ducts / floors / fixed on poles / equipments of size 3.5 core 120 sqmm complete all as specified and as directed.
(a) Earthwork, sand cushioning, protection for cable etc., as required shall be measured and paid separately.
(b) Lugs and glands shall be used appropriately wherever required while connecting cables to the panel board and the quoted rates are deemed be include for the same.
Taking up / down water mains of galvanised iron tubing including all fittings from trenches / walls / roof / floor etc., and removal from site under Sch of credit and provision of steel tubing, galvanised, light grade, with all fittings such as bends, elbows, tees etc., and laid in trenches / under roads / crossings etc., 80mm bore of pipe for cable protection complete all as specified and as directed.
Earthwork, cutting across roads etc., as required shall be measured and paid separately.
Taking up / down water mains of galvanised iron tubing including all fittings from trenches / walls / roof / floor etc., and removal from site under Sch of credit and provision of steel tubing, galvanised, light grade, with all fittings such as bends, elbows, tees etc., and fixed complete to walls and ceilings or laid in floors / fixed on poles including necessary clamps, clips, wall hooks, wooden plugs for fixing the pipes in position, 80mm bore of pipe complete all as specified and as directed.
Earthing complete with galvanised iron earth plate electrode 600mm X 600mm X minimum 6mm thick, with and including earthing of 32mm x 6mm GI strip protected by 40mm dia GI pipe light grade upto a length of 7.5m. The plate shall be buried directly in ground vertically to a depth not less than 2.25 metres below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level, connected to earth lead as described here-in-before by means of bolts, nuts, washers and checknuts made out of galvanised iron or mild steel, earthing lead protected by as described here-in-before and connected to main switch board or main control board or electric pole all as shown on electrical plate No.3 of MES Sch Part-I including necessary earth work and excavation in any type of soil, plain cement concrete 1:3:6, type C1 chamber, reinforced cement concrete cover slab with locking arrangement and handle of 10mm dia MS round bars 450mm long, 1:2:4 type B1, 50mm thick with 8mm dia TMT bars at 140mm centre to centre both ways, GI pipe of bore 20mm medium grade for watering with funnel, wiremesh, salt, charcoal, lugs including testing complete all as specified and as directed.
Supply, installation, commissioning and testing of silent type DG set complete with sound proof canopy, diesel engine driven generating set of microprocessor / relay based AMF built-in control panel, Output of 125 KVA at NTP, with 10 % overload capability in accordance with ISO-8528 and ISO-3046 AC 415 Volts, 3 phase, 4 wire 0.80 power factor directly coupled to diesel engine water cooled mounted on common MS fabricated frame with AVM pads weather proof as per CPCB norms, acoustic enclosure installed on a PCC hard standing , to be constructed by the tenderer as per manufactures’ recommendation ,with and including all excavation for PCC foundation, vibration dampers and other accessories comprising of ENGINE, ALTERNATOR, AMF CONTROL PANEL, GEN SET CONTROLLER, CONTROL SYSTEM AND MISC WORKS complete all as specified and as directed.
The brief requirement of the DG Set is given in the BOQ. The tenderer shall however read the same in conjunction with the particular specifications given here-in-after and rate quoted is deemed to include for all the provisions given therein.
devan enterprises
C SRINIVASAN
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .