| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹70.9 LAccepted-AOC | 1 | Accepted-AOC Lowest and reasonable | |
| 2 | 2₹76.9 L+₹5.6 L (7.88%)Rejected-AOC | 2 | Rejected-AOC Not Lowest | |
| 3 | 3₹76.9 L+₹5.7 L (7.93%)Rejected-AOC | 3 | Rejected-AOC Not Lowest | |
| 4 | 4₹84.1 L+₹12.8 L (18.0%)Rejected-AOC | 4 | Rejected-AOC Not Lowest | |
| 5 | 5₹86.1 L+₹14.8 L (20.7%)Rejected-AOC | 5 | Rejected-AOC Not Lowest |
Tender Value
₹1.1 Cr
EMD Value
₹1.9 L
Closing Date
2 Dec 2019, 6:00 pmClosed
CWE AF Jammu
CWE AF Jammu C/O 256 SU AF Pin-937256 C/O 56 APO
PROVISION OF CENTRAL AIR CONDITIONING AND ADDITION ALTERATION TO EE HALLS AT DALHOUSIE UNDER GE AF PATHANKOT
2019_MES_283423_2
CWEAFJ-05/2019-20
Open Tender
Civil Works
Item Rate
240 days
Dalhousie
Please refer Tender documents.
9 documents required · 9 mandatory
₹1,000
GE AF PATHANKOT
₹1.9 L
Yes
17 Feb 2020
20 Nov 2019
3 Dec 2019
20 Nov 2019
2 Dec 2019
20 Nov 2019
Amount
Roughening surfaces of old concrete floor by picking, sweeping clean and washing down with water to remove dust etc complete all as specified and directed.
15 mm thick screed bed or bedding layer of cement mortar in CM (1:4) for laying floor finished complete all as specified and directed.
Vitrified ceramic tiles 10mm thick dark shade/Double charged/ultra charged (square/rectangular) polished area of each tiles exceeding 0.36 sqm but not exceeding 0.42 sqm, in floors etc set and jointed in neat cement slurry and pointed in white or coloured cement to match complete all as specified and directed
Dismantling of wall and ceiling boards (fibre, pulp, insulation etc) or insulation board / slabs / blanket any thickness including cover fillets complete all as specified and directed
S&F GI frame work for seamless ceiling comprising of GI perimeter channel 0.55 mm thick with two unequal flanges of 20 and 30 mm and web of 27 mm fixed to surrounding wall using nylon sleeves and screws at 450 mm centre to centre/intermediate channel 0.9 mm thick having two equal flanges of 15 mm each and web of 45 mm suspended from soffit at approx 900 m centre to centre with GI cleat and steel expansion fasteners with and including ceiling section (not exc 1.2m length) of 0.55 mm thickness having kurled web of 50 mm and flange of 26 mm each with lips of 10.5 mm fixed to the intermediate channel with connecting clips across the intermediate channel at 457 mm centre to centre complete all as specified and directed
S&F Hangers 6 mm dia GI (upto 1200 mm length) adjusting level fixed to roof slabs by means of ceiling cleats made out of GI flat 40 x 3 mm size 60 mm long complete all as specified and directed.
White colured Celotex PIN RE tiles of thickness 15mm and size 595x595mm having NRC of 0.55, CAC (Ceiling Attenaution Class)>35, LR (Light Reflectance)> 0.84 and suitable for use in relative humidity up to 95% and having fire retardant of Fire class-1 complete all as specified and directed.Make :- (Saint Gobain/ Gyproc)
Two coats of oil bound distemper over a coat of chalk whitening and primer including complete removal of exsisting treatment complete all as specified and directed
Mild steel work conforming to Fe 290 GdeE-165 as in angle iron posts with swan neck (horn) and struts fencing including cutting tops to shape also directed drilling holes notching for wire etc necessary drilling bolting as welding / riveting etc complete all as specified and directed by Engineer-in-Charge.
4mm thick MS Plates FE -410W(Gde-E-250) quality-B (Plain or chequered) channels square cut or notched (ordinary and counter sunk) forming holes, without any attachment complete all as specified and directed.
Excavation in tranches , not exceeding 1.5m wide andnot exceeding 1.5m in depth for foundation etc or for shafts wells cesspits manholes pier holes etc not exceeding 10 sqm on plan and getting out Hard/dense soil complete all as specified and directed.
Removing excavated material not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point and entire satisfaction of Engineer-in-Charge complete all as specified and directed .
Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each all as required complete all as specified and as directed Engineer-in-charge.
PCC 1:5:10 Type D2 ( using 40mm graded crushed stone aggregate ) as in foundations, filling and mass concrete complete all as specified and as directed by the Engineer-in-Charge.
Brickwork with sub class `B` old size brick straight or curved on plan exc 6 mtr mean radius built in cement Mortar 1:6 complete and all as specified.
M & L for rendering 15mm thick in cement plaster 1:6 on other than fair faces of brick work or concrete surfaces ,finished even and smooth without using extra cement complete all as specified and directed by the Engineer-in-Charge
Preparation of new plastered surfaces and applying three coats of white wash on new plastered wall surface complete all as specified and directed .
S&F Anodised aluminium powder coating frame for Doors, windows, ventilators with one or more rebates including jointing cleat for fixing etc complete all as specified.
S&F Anodised aluminium powder coated door shutters, aluminium section weighing 0.55 kg/m including necessary joining cleats, glazing clips, rubber neoprene packing, handles 2 Nos in each door, hinges, anodised aluminium snap beading screws etc, complete all as specified.
5 mm thick tinted plain glass for aluminium windows/doors having each pane exc 0.5 sqm incl complete fittings all as specified and directed.
S & F medium density fiber board 18 mm thick fixed to timber frame work with screws incl 0.9 mm thick decorative laminate type -1 of surface finish,coloured and pattened as approvred by GE ,fixed with approved adhesive as per manufacture"s instructions for door shutter complete all as specified and directed.
S&F 0.71 mm thick plain Aluminium sheeting, alloy 31000 H4 in straight flashing (length and girth as fixed) complete and all as specified and directed by the Engineer-in-charge.
Taking down old unserviceable/deteriorated batten/PVC conduit point wiring from existing place i.e. light, fan, socket or power points complete with all unserviceable fittings such as switches, sockets, ceiling rose, pendants, Holders, etc and making good all disturbed surface to wall, floor etc by means of cement mortar (1:3) or plaster of Peris and to match / finish new surface as the existing surface either by using same colour distemper, Putti or white / colour wash all as required and directed by Engineer-in-Charge.
Taking down main switch/DB/ changeover/AC box of any capacity including fixing accessories
Concealed point wiring on wall and surface on ceiling/roof with necessary fixing arrangements with PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including rigid non metallic white / ivory PVC conduit medium grade ISI marked not less than 19 mm dia with all conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc including anodized MS sunken boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and Bakelite laminated sheet 3mm thick ISI marked for fixing of switches / sockets, fan regulators, wall mounting fittings, door bell & bulkhead etc with MS screw and cup washers including PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing including cutting the chases and making good the surface by cement mortar (1:3) and for matching / finishing of new surfaces either by means of plaster of peris/ Putti or distemper / colour wash with same existing colour surfaces all as specified and directed by Engineer-in-Charge for One light, fan, call bell and 5 Amp independent socket point controlled by one switch.
All as per Item No 25 above but for one 5 Amp socket point controlled by one switch on same board complete all as specified and directed
All as per item No 25 above but for power point wiring with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 1.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead complete all as specified and directed.
Surface conduit point wiring on wall and surface on ceiling/roof with necessary fixing arrangements with PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade drawn in and including rigid non metallic white / ivory PVC conduit medium grade ISI marked not less than 19 mm dia with all conduit accessories/ fittings such as junction boxes, bends, tee, elbow etc including anodized MS boxes made out of MS sheet of thickness not less than 1.6 mm with earth dolly and Bakelite laminated sheet 3mm thick ISI marked for fixing of switches / sockets, fan regulators, wall mounting fittings, door bell & bulkhead etc with MS screw and cup washers including PVC-FRLS insulated and unsheathed copper multi-stranded conductor of size 1.5 Sqmm, 1100 volts grade for continuous earthing all as specified and directed by Engineer-in-Charge for One light, fan, call bell, 5 Amp independent socket point controlled by one switch.
All as per Item no 28 above but for one 5 Amp socket point controlled by one switch on same board
All as per item No 28 here-in-before but for power point wiring with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 1.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead.
All as per item No 25 here-in-before but in existing concealed/surface conduit complete all as specified and directed by Engineer-in-Charge for One light, fan, call bell, 5Amp independent socket point controlled by one switch.
All as per item No 25 here-in-before but in existing concealed/surface conduit complete all as specified and directed by Engineer-in-Charge for One socket point controlled by one switch on same board
All as per item No 25 here-in-before but in existing concealed/surface conduit for power point wiring with 2.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable and 1.5 Sqmm PVC-FRLS insulated, unsheathed, copper conductor, stranded 1100 volt grade cable as continuous earth lead.
Switch flush type single pole one way 5 Amps, 240 volts, white finish, ISI marked complete all as specified .
Switch flush type single pole one way 15 Amps, 240 volts, white finish, ISI marked complete all as specified .
Socket outlet 5 pin, 5 Amps, 240volts flush type white finish , ISI marked complete all as specified.
Socket outlet 2 in 1, 3 pin, 5 &15 A, 240 volts, flush type white finish, ISI Marked complete all as specified.
Bell push, flush type 5 Amps white finish, ISI Marked complete all as specified.
Door bell multi music type 230V, single pole, ISI Marked complete all as specified.
Ceiling rose, surface backlite, 65 x 20 mm 3 three terminal ISI Marked complete all as specified.
Lamp holder insulated body with back plate suitable for angle / batten fitting ISI Marked
Sheet metal enclosure VTPN MCCB DB 4way, 415 V (vertical type) with bus bar double door type IP 43 - IK 09 for DB when MCBs & MCCB 100 Amps (as incomer) to be used, fixed properly on / in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs for cables/wires all as directed.
Double door metallic sheet metal enclosure for DB when MCBs to be used TPNL, 4 ways, 415Volts (horizontal type) with 200 Amps rated bus bar suitable for TPN MCB/ 4 pole Isolator fixed properly on in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs for cables/wires complete all as directed.
Double door metallic sheet metal enclosure for DB when MCBs to be used SPN 8 ways, 240 V with 200Amps rated bus bar complete fixed properly on in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs of cables/wires all as directed.
Double door metallic sheet metal enclosure for DB when MCBs to be used SPN 4 ways, 240 V with 200Amps rated bus bar complete fixed properly on in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs of cables/wires all as directed.
Double door metallic sheet metal enclosure for DB when MCBs to be used SPN 2 ways, 240 V with out bus bar complete fixed properly on in concealed position and to provide required sizes of flexible conduit at any open surfaces near DBs of cables/wires all as directed.
Supply and fixing in repalcement MCB SP 240 volt 6 Amp to 40 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
Supply and fixing in repalcement MCB SP 240 volt 40 Amp to 63 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
Supply and fixing in repalcement MCB SPN 240 volt 16 Amp to 40 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
Supply and fixing in repalcement MCB SPN 240 volt 40 Amp to 63 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
Supply and fixing in repalcement MCB TP 415 volt 40 Amp to 63 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
Supply and fixing in repalcement MCB TPN 415 volt 40 Amp to 63 amp 10 KA capacity having C-curve characteristics connected with suitable lugs.
S&F MCCB 100 Amps, 3 Pole, 415V, 16KA fixed type complete all as specified and directed
Sheet metal enclosure , 32A single pole and neutral with a two pin and earth plug and socket complete in metal clad board (Industrial type) with one single pole MCB 32 Amp fixed properly complete all as directed by Engineer-in-Charge
Sheet metal enclosure , 32A, 415 Volts triple pole neutral & earth with a three pin and earth plug and socket complete in metal clad board (Industrial type) with one TP MCB 32 Amp fixed properly on / in concealed position all as directed by Engineer-in-Charge.
Sheet metal enclosure , 63A, 415 Volts triple pole neutral & earth with a three pin and earth plug and socket complete in metal clad board (Industrial type) with one TPN MCB 63 Amp fixed properly on / in concealed position all as directed by Engineer-in-Charge.
Sub main wiring with two single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 6 sqmm drawn in PVC conduit with 6 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete excluding PVC conduit. Note : PVC Conduit and cutting cheaseling and making good will be measured and paid separately
Sub main wiring with four single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 6 sqmm drawn in PVC conduit with 2 run of 6 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete excluding PVC conduit. Note : PVC Conduit and cutting cheaseling and making good will be measured and paid separately.
Sub main wiring with four single core PVC-FRLS insulated unsheathed multi stranded copper conductor cable of size 10 sqmm drawn in PVC conduit with 2 run of 10 Sqmm PVC-FRLS insulated unsheathed multi stranded copper conductor as a continuous earth wire complete excluding PVC conduit. Note : PVC Conduit and cutting cheaseling and making good will be measured and paid separately
Rigid metallic medium 20mm dia PVC conduit ISI marked in concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed/Surface position all as directed by Engineer-in-Charge.
Rigid metallic medium 25mm dia PVC conduit ISI marked in concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed/Surface position all as directed by Engineer-in-Charge.
Rigid metallic medium 32 mm dia PVC conduit ISI marked in concealed position inclusive all fitting such as tee, bends, reducer, elbow, bell mouth, tube ends and all fixing accessories such as couplers lock, nuts, saddlers, pipe hooks etc fixed properly on as in concealed/Surface position all as directed by Engineer-in-Charge.
Cutting chases in brick walls, pinning in at the depth of 30 mm, making good to facings where required and pointing in cement mortar 1:3 cutting chases for concealed conduit wiring,submain wiring etc and making good and palstering the surface with cement or plaster of peris and matching with same colour scheme, cutting exceeding 10cm but not exceeding 30cm girth complete.
Recess mounting LED luminaries 36 Watt (2'x2') with more light distribtuion and clutter free ceiling with powder coated CRCA sheet steel white powder coated housing with square in a perforated metallic frame complete.
Decorative ultra slim linear LED lighting fixtures with extruded polycorbonate envirnmental friendly energy saver LED light fitting 1 x 20/22 watt (4'), 230 Volts, single tube mounting including LED Tube 20/22 Watt complete with electronic driver spring loaded rotor type lamp holder, end cover, connector box etc and accessories, prewired, LED including required fixing arrangements and electrical connection three core copper cable from ceiling rose to led light fitting all as directed in replacement of lamp holder.
M&L taking down exhaust fan any make any size from any position including opening the stator and rotor of fan and providing new lubricating, grease in bearing/bushes, repainting, reassembling including commissioning and testing complete & refixing fan to existing site or as directed incl providing nuts, bolts, locking bolts, blades screws, split pin, rubber reel, PVC connector, rubber pad, washers whereas required complete all as directed by Engineer-in-charge.
Supply and fix LED Lamp 10 watt, 240 volts complete all as specified
Supply, laying and testing cable XLPE insulated, screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 70 Sqmm, 3½ core with suitable lugs complete all as specified.
Sand cushioning 8 cm before laying underground cable in trenches and 15 cm after the cable is laid and all as specified and directed by Engr-in-charge. Note:-The laid sand shall be gently punned down by hand to 18 cm depth.The punned thickness only shall be measured and paid.
Brick protection with well burnt sub class ‘B’ brick abutting each other( width wise) across the cable laid in trenches complete and all as specified.
Material & labour for tubing GI light grade 50mm bore for cable protection laid in ducts, fixed to wall or poles including fixing arrangement all as required and directed by Engineer-in-Charge.
Supply and fix MS/GI powder coated perforated type cable trays of size 300 x 50 mm x 2mm using MS angle, channels, flats etc. All MS supports used shall be given one coat of red oxide primer and 2 coats of synthetic enamel paint of approved colour complete all as specified and directed
Earthing complete with copper earth plate electrode 600x600x3.15 mm thick buried directly in ground (Earth pit not less than 2.25 Mtr deep below ;normal ground level ) with top edge of earth plate not less than 1.5 Mtr below normal ground level connected to copper strip 20X3 mm as earth lead by means of bolts, nuts washers and check nuts of steel/GI duly protected with 40 mm bore light grade GI pipe upto main board , 20mm bore GI watering pipe light grade with CI/MS funnel and wire mesh including excavation , earth work in any type of soil and removing the surplus soil to a distance not exceeding 50 Mtr, add charcoal dust and common salt after mixing with BFC (Back Fill Compound) in adequate quantity as recommended by the manufacturer or as directred by the Engr-in-charge all as shown in electrical plate No. 03 of SSR part-I 2009 having pit in PCC 1:2:4 type B-1 including angle iron frame made of angle iron of size 40x40x6mm grouted in PCC pit for CI cover of required size, funnel with wire mesh complete and all as specified and as directed by Engr-in-charge.
S&F copper strip 20x3mm complete with saddles/ insulators made out of PVC or fibre and fixing screws for roof conductor/down conductor including welding or brazing for joints all as required at site or directed by Engr-In-Charge.
Material and labour for test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm, drilled and screwed including 03 Nos 8mm dia 25mm long hex head screwcomplete all as specified and as directed by Engr-In-Charge.
Supply, installation, commissioning and testing of air cooled package type air conditioners of capacity 11 TR comprising of hermetic sealed scroll compressors with microprocessor based control including copper refrigerant piping, electrical inter connection wiring complete between indoor to outdoor unit suitable for operation on R-407C refrigerant all as specified and directed by Engineer-in-Charge Make Blue Star or equivalent in other make and comprising of following :- (a) Installation, pressure testing, gas charging, lifting & shifting and commissioning of air cooled ductable air conditioner-01 each. (b) Aluminium powder coated supply grills of suitable size as per site requirement including fixing arrangement – 01 job (c) Aluminium powder coated supply diffuser of suitable size as per site requirement complete with including fixing arrangement – 01 Job. (d) Fire RIDARDNAT Canvas for connection of ducts for making noise and vibration proof of ducting – 01 Nos for each joint. (e) Smoke cum MS fire damper of least 90-120 minutes fire rating as per specification inter locking of fire damper using copper control wiring – 01 No. (f) MS Angle iron stand of suitable size for outdoor unit - 01 No. (g) PVC drain pipe suitable for 11 TR package type AC complete with fixing arrangement – 4.2 RM.
(h) Control wiring with suitable size of copper wire from indoor to outdoor unit of 11 TR AC complete – 01 Job.Dehumidification capacity 250 Ltr/day cat 30 Degree Centigrade, 80%RH) Dehumidifying capacity (Kgs/hr) 9.2 air flow (M3hr) 2800 complete – 01 Job. (j) MS volume control damper complete
Supply, installation and testing of heating system with 12 KW strip heater for each machine including complete with fixing arrangement with all accessories as specified and directed by Engineer-in-Charge.
Supply, assembly and erection of GI ducting with GI sheet with C & stainless steel rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gaskit and appropriate sealant on longitudinal joints etc complete of size 24 gauge complete all as specified and directed by Engineer- in – charge
Supply, assembly and erection of GI ducting with GI sheet with C & stainless steel rectangular/square duct made out of L shaped hollow profile, duly factory boxed including all accessories such as corner, cleat, carriage bolt, gaskit and appropriate sealant on longitudinal joints etc complete of size 22 gaugecomplete all as specified and directed by Engineer- in – charge
M & L for duct insulation with 9 mm thick nitrile insulation of class ’O’ type with proper cleaning of duct surface (to be insulated) by scrapping carefully with wire brush etc to make the surface completely free of millscale dirt, dust, grease and other foreign material and confirming with the following :- (a) Sealing of all longitudinal joints and circular overtaps with and including tape 50mm wide to make the insulation leakproof. (b) Securing the insulation with and including mechanically fastened nylon/steel straps of size 12mm/50mm at maximum intervals of 1.2 mtr all as specified and directed by Engineer-in-Charge.
All as per item No 80 above but acoustic insulation to duct with 12mm thick fibreglass covered with aluminium perforated sheet complete all as specified and directed by Engineer-in-Charge
M & L for copper refrigerant piping per circuit from indoor to outdoor unit 11 TR package type AC duly insulated with nitrile rubber of 50mm dia and cladding with aluminium foil tape complete all as per specified and directed by Engineer – in – Charge.
Fabrication, installation and testing of LT panel KIOSK type floor mounted dust/vermin proof outdoor type double door, powder coated of size 1.5x1.2x0.6 mtr or suitable for given items, factory fabricated, made out of MS sheet of thickness 2mm mounted on angle iron legs made out of angle iron of size 40x40x6mm with front & rear opening with locking arrangement, powder coated, contain bus bar chamber to accommodate 3phase & 1 nutral copper busbar of size 40 x 10mm fixed on hydroscopic based insulators in horizontal position(steped manner) in upper part of panel; In middle part of panel provide seprate chambers for 01 No. incoming MCCB and 03 Nos. for Outgoing MCCBs connected to busbar by copper strip of size 20 x 5mm; bottom part acoommodate connections of Cables complete all as required on site and as directed by Engineer-incharge including the Following :-(a) MCCB 125 Amps FP 35 Ka (adjustable type) . I/C - 01 No. (b) MCCB 63 Amps TPN 35 Ka (adjustable type) . O/G - 03 No. (c) Digital Multi-function meter – 01 No (d) Set of selecor switches - 01 Set (e) Indicator lamps (R, Y. B) – 01 Set. ( Note ) All accessories pre wired with suitable size copper conductor cable including making necessary arrangements for fixing all as required at site or directed.
Material and labour for cleaning of the existing duct of air conditining by means of duct cleaning equipment by applying effective way to clean air ducts and ventilation systems or to employ source removal methods of cleaning. This requires professional duct cleaning equipment such as the danduct Clean DC4 brush, cleaning machine . The dirt and debris can then travel down the ducts to the ventilator, which removes it from the system complete all as specified and directed by Engr-in-charge.
Ashoka Engineers
KULBHUSHAN AGGARWAL
HVAC Engineering Co
Auto India
JYOTI ENTERPRISES
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .