Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹31.7 LAccepted-AOC D1C 47A JANAK PURI NEW DELHI 110058 | NEW DELHI | DELHI | DELHI | 110058 | L-1 | Accepted-AOC L-1 | |
| 2 | L-2₹35.9 L+₹3.2 L (9.92%)Rejected-AOC 19 62 1ST FLOOR WEST MOTI BAGH SARAI ROHILLA NEW DELHI 110035 | NEW DELHI | NEW DELHI | DELHI | 110035 | L-2 | Rejected-AOC L-2 | |
| 3 | L-3₹39.5 L+₹6.8 L (20.9%)Rejected-AOC B 3 105 PASCHIM VIHAR NEW DELHI 110063 | WEST | DELHI | 110063 | L-3 | Rejected-AOC L-3 |
Tender Value
Refer Docs
EMD Value
₹98,000
Closing Date
3 Jan 2023, 6:00 pmClosed
GE I RND DELHI
MILITARY ENGINEER SERVICE, GARRISON ENGINEER (I) RND, LUCKNOW ROAD, TIMARPUR, DELHI-110054
MISC REPAIR/ REPLACEMENT AND MAINTENANCE OF CENTRAL AC PLANT AND CONNECTED WORKS AT ION LAB AND JCB LAB OF METCALFE HOUSE AREA UNDER GE I RND DELHI
2022_MES_566310_1
GE/RND-88/DLI/2022-2023
Open Tender
Civil Works
Item Rate
180 days
Delhi
Class-D, Cat- c (i)
2 documents required · 2 mandatory
₹500
GE I RND DELHI
₹98,000
Yes
18 Jan 2023
30 Nov 2022
5 Jan 2023
30 Nov 2022
3 Jan 2023
22 Dec 2022
Amount
M&L Epoxy protective coating on Copper piping system, headers (Discharge line, Liquid line, all open fittings of copper, suction line etc) for 3 x 210 TR AC plant Make : YORK by Johnson Controls Model No. YVAA0263 as per OEM complete all as specified and directed. Note: One circuit of chiller shall be measured one unit.
Supply and charging the refrigerant R-134a/410 for 3 x210 TR chiller type AC plant Make : YORK by Johnson Controls Model No. YVAA0263 including testing complete all as specified and directed.
Pressure testing with Application of Nitrogen Gas and replacement of Spares/Consumables parts for 01 Chiller application to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogen gas complete all as specified and directed.
Supply and topping up coolant of compressor for 3 x 210 TR AC plant Make : YORK by Johnson Controls Model No. YVAA0263 as per OEM complete all as specified and directed.
S& F in Replacement of Compressor oil (YORK OIL, L5 Gal Pail) for 3 x 210 TR AC plant Make : YORK by Johnson Controls Model No. YVAA0263 complete all as specified and directed.
M&L for Servicing of complete AC plant 3x210 TR Make : YORK by Johnson Controls Model No. YVAA0263 including electrical panels, VSD Panels & setting of all parameters all as per OEM complete all as specified and directed.
S&F FILTER DRIER 3/8 0RFS for 3 x 210 TR AC Plant Make : YORK by Johnson Controls Model No. YVAA0263 as per existing OEM for each circuit complete all as specified and directed.
S&F CTG DEHY 100 PERCENT MOLECULAR for dehydrator for refrigrant circuit for 3 x 210 TR AC Plant Make : YORK by Johnson Controls Model No. YVAA0263 complete all as specified and directed.
S&F Oil Filter for 3x210TR AC plant Make : YORK by Johnson Controls Model No YVAA0263 As per existing OEM Make : YORK by Johnson Controls for each circuit complete all as specified and directed.
S&F O- RING size 2.62 x 81.97 mm for 3x210TR AC plant Model No YVAA0263 As per existing OEM Make : YORK by Johnson Controls for each circuit complete all as specified and directed.
M&L for overhauling of pump and motor 20 HP capacity by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing bush, seal, shaft, coupling, machine work etc and reconnecting back and testing complete all as specified and directed.
Disconnecting, dismantling and strip opening of the existing air handling unit of any description and in any position and of capacity of 5500 CFM to 15500 CFM for overhauling and servicing, including cleaning of cooling coils with chemical including taking out existing shaft, blower drum, pulley and de-humidifier pump etc of air handling unit, checking thoroughly serviceability of the parts, fixing the serviceable parts in position, replacement of the defective/non functional/unserviceable parts/spares, reassembling, commissioning, fixing in position and testing of the air handling unit on full load for its smooth and trouble free operation complete all as specified and directed. Note : Spare parts i.e V- belt, filters for AHU, Bearing & pulley shall be measured and paid separately under respective items.
Supply only Bearing and bearing hub as per existing size suitable for AHU 5500 CFM to 15500 CFM complete all as specified and directed.
Supply only metal pulley with hub as per existing size suitable for AHU 5500 CFM to 15500 CFM complete all as specified and directed.
Supply only V belt of size A42 complete all as specified and directed.
Supply only V belt of size A43 complete all as specified and directed.
Supply only V belt of size A46 complete all as specified and directed.
Supply only V belt of size A48 complete all as specified and directed.
Supply only V belt of size A49 complete all as specified and directed.
M&L in replacement of pre filter with 50mm thick with GI frame metal viscous/ washable synthetic type air prefilters (EU-3, 90% down to 10 micron), fine filter (EU-7, 99% down to 3 micron) as per existing size (600mm x 600 mm) complete all as specified and directed. Make of AHU - Carrier
Supplying, laying, testing and commissioning in replacement of following nominal sizes of chilled water piping plumbing 150 mm dia MS pipes (75 mm insulation) inside the building (with necessary clamps, vibration isolators and fittings but excluding valves, strainers, gauges etc.) duly insulated PUF moulded pipe section of density 20 kg/cum after a thick coat of cold setting adhesive (CPRX compound) wrapping with 500g polythene faced hessain and finally applying 0.63mm aluminium sheet cladding complete with type 3 , grade 1 roofing felt strip (as per IS:1322 as amended up to date ) at joints repairing of damage to building etc. as per specifications and as required complete all as specified and directed.
All as per item Ser No 21.00 above but 125 mm dia MS pipes (50 mm insulation).
All as per item Ser No 21.00 above but 100 mm dia MS pipes (50 mm insulation)
All as per item Ser No 21.00 above but 80 mm dia MS pipes (50 mm insulation)
All as per item Ser No 21.00 above but 65 mm dia MS pipes (50 mm insulation)
All as per item Ser No 21.00 above but 50 mm dia MS pipes (50 mm insulation)
Supply, installation, testing and commissioning in replacement of "B" class GI drain piping 80 mm dia complete with fitting etc & 25 mm thick PUF insulation with sealing tapes & 28 G Aluminium cladding complete as per drawings and specifications complete all as specified and directed.
M&L in replacement of Insulation of MS Pipe bore of pipe 40 mm dia with PUF slab 30 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete all as specified and directed.
All as per item Ser No 28.00 above but bore of pipe 50 mm dia.
All as per item Ser No 28.00 above but bore of pipe 65 mm dia.
M&L in replacement of insulation of MS Pipe with PUF slab 40 mm thick with and including applying bituminuous compound and GI cladding with 26 gauge GI sheet complete of sizes 80 mm dia Pipe complete all as specified and directed.
All as per item Ser No 31.00 above but bore of pipe 100 mm dia.
All as per item Ser No 31.00 above but bore of pipe 125 mm dia.
All as per item Ser No 31.00 above but bore of pipe 150 mm dia.
Supplying, fixing, testing and commissioning of BUTTERFLY VALVE 150 mm dia (MANUAL) with C I body, SS Disc, Nitrile Rubber Seal & O- Ring, PN 16 pressure rating for chilled water/ hot water circulation as specified valves, strainers, gauges in the chilled water plumbing duly insulated to the same specifications as the connected piping and adequately supported as per specifications complete all as specified and directed.
All as per item Ser No 35.00 above but bore of butterfly valve 100 mm dia.
All as per item Ser No 35.00 above but bore of butterfly valve 80 mm dia.
All as per item Ser No 35.00 above but bore of butter valve 65 mm dia.
S&F in replacement of BALANCING VALVE 125 mm dia WITH BUILT IN MEASURING FACILITY with C I body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled / hot water circulation complete all as specified and directed.
All as per item Ser No 39.00 above but bore of balancing valve100 mm dia.
All as per item Ser No 39.00 above but bore of balancing valve 80 mm dia.
All as per item Ser No 39.00 above but bore of balancing valve 65 mm dia.
All as per item Ser No 39.00 above but bore of balancing valve 50 mm dia.
S&F in replacement of 'Y' strainer 125mm dia with built in measuring facility with CI body flanged construction with EPDM coated disc with long pitch with protected out pipe insulation & PN 16 pressure rating for chilled/hot water circulation complete all as specified and directed.
All as per item Ser No 44.00 above but strainer 100 mm dia.
All as per item Ser No 44.00 above but strainer 80 mm dia.
All as per item Ser No 44.00 above but strainer 65 mm dia.
All as per item Ser No 44.00 above but strainer 50 mm dia.
All as per item Ser No 49.00 above but Suction Guide 50 mm dia.
S&F in replacement of Bellows type rubber expansion joints 125 mm dia for Chilled water piping located at Pump inlet & exit, AHU inlet & exit and at chiller inlet & exit. Complete with double bellows, tie rods, MS flanges, necessary hardware and gaskets etc. with insulation complete all as specified and directed.
All as per item Ser No 51.00 above but bellows type rubber expansion joints 100 mm dia.
All as per item Ser No 51.00 above but bellows type rubber expansion joints 80 mm dia.
All as per item Ser No 51.00 above but bellows type rubber expansion joints 65 mm dia.
All as per item Ser No 51.00 above but bellows type rubber expansion joints 50 mm dia.
S&F in replacement industrial type pressure gauges with SS-304 valves in position complete all as specified and directed.
S&F in replacement mercury in glass industrial type thermometers in position complete all as specified and directed.
Supply, installation, testing and commissioning in replacement of proportional type cooling and heating thermostats for the various Air Handling Units complete with required control wiring/installation kit etc complete all as specified and directed.
Supply, fabricating and installing in replacement of perforated M.S. cable trays of size 50x450x50x2 mm thick including horizontal and vertical bends, reducers, tees, cross members and other accessories as required, and duly suspended from the ceiling with M.S. suspenders, including painting etc complete all as specified and directed.
All as per item Ser No 59.00 above but 50 x 200 x 50 x 2 mm thick.
All as per item Ser No 59.00 above but 50 x 150 x 50 x 2 mm thick.
M&L and laying in trenches insulated, armoured heavy duty XLPE electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 sqmm 3.5 core as main power cable to chiller control panel including taking down old unserviceable cable complete all as specified and directed.
M&L and laying in trenches insulated, armoured heavy duty XLPE electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 sqmm 3.5 core as main power cable to hot water generator including taking down old unserviceable cable complete all as specified and directed.
M&L for overhauling of pump and rewinding of electric motor with super enamelled copper winding wire of existing gauge of capacity 20 HP by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing, bush,seal,shaft,coupling,machine work etc and reconnecting back and testing complete all as specified and directed.
M&L for overhauling of electric motor and blower of AHU including rewinding with super enamelled copper winding wire of existing gauge of capacity 5 to 7.5 HP by opening up and cleaning of all parts such as impeller , rotor, stator, fan cover, greasing including replacing all unserviceable/damaged part like impeller, bearing, bush, seal, shaft, coupling, machine work etc and reconnecting back and testing complete all as specified and directed.
Supply, assembling and erection of PGI sheet 22 gauge with TDF flange rectangular/square duct made out of 'L'shaped hollow profile ,duly factory boxed including all accessories such as Corner ,Cleat,Carriage bolt,Gasket and appropriate sealant on longitudinal joints etc including taking down old rusted duct complete all as specified and directed.
M&L for duct insulation with resin bonded fibre glass wool roll of density 24 Kg /Cum and 50mm thickness with factory laminated aluminium vapour barrier , thickness of insulation complete all as specified and directed including the following:- (a) Cleaning the duct surface( to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of mill scale ,durt,dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage complete as desired/required. (b) Applying rubber based adhesive CPRX compound. (c) Sealing of all longitudinal joints and circular overlaps with and including aluminium foil tape 50 mm wide, to make the insulation leakproof. (d) Securing the insulation with and including mechanically fastened nylon / steel straps of size 12mm / 50mm at maximum intervals of 1.2 mtr.
M&L for painting of all metal surfaces of Cetral AC plant 3x210 TR comprising 03 Nos chiller plant, Chiller Pump Motors, Hot water Generator Unit, LT Panel for AC Plant and AHUs with two coats of synthetic enamel heat resistant paint maching to existing colour over a coat of red oxide primer by spray gun machine including preparation of old painted surfaces/removing old faded/rust/ cemented material of surface of complete all as specified and directed.
M&L for painting of Cetral AC plant 3x10 TR complete ( i.e 03 Nos chillers unit, compressor, condensers, Condensing pipes, Chillers pump motors, Condensing pump motors, LT Panel for complete AC Plant etc) two coats of synthetic enamel heat resistant paint matching to existing colour over a coat of red oxide primer by spray gun machine including preparation of old painted surfaces/removing old faded/rust/ cemented material of surface of complete all as specified and directed.
M&L in replacement of MS iron work (MS equal angle iron, flat iron & bracing ) for supporting chilled water pipe, condesing pipe, base channel for pump motor or any other rquirement including necessary fabrication, welding nuts & bolts and including two coats of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F MCCB 630 Amps, 4 Pole breaking capacity 35KA including taking down old unserviceable MCCB complete all as specified and directed.
S&F in replacement of power contractor of MNX - 45 three pole complete all as specified and directed.
S&F in replacement of HRC fuse link DIN type 400 Amps, 100 KA , 415 volt complete all as specified and directed.
S&F in replacement of HRC fuse link DIN type 80 Amps 100 KA , 415 volt complete all as specified and directed.
Supply only digital Psychrometer with psycrometric chart - (01 No) and Digital Anemometer - (01 No) complete all as specified and directed.
M&L for repair of hot water generator of capacity 20 KW in five banks complete with one slave bank controlled by semi conductor rectifier & other necessary controls, electrical panels including control wiring with 2.5 sqmm multistranded copper FRLSH cable complete all as specified and directed.
Material and Labour for earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below the ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with GI strip 32x6 mm by means of nuts, bolts and washers. GI strip shall be laid in 40mm dia light grade GI pipe as protection from top of the plate up to test point (cost of protection pipe up to 7.5 meters from earth electrode will be included in the rates quoted by the contractor) as shown in electrical plat No. 03 of SSR Part-I with following:- (a) GI strip 32x6mm (b) Watering pipe GI light grade 25mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick re-inforced with 8mm dia bars 75mm centre to centre both ways with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover.
M&L Earth continuity conductor or main earthing lead of size 32 x 6 mm of GI fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc including taking down old unserviceable strip complete all as specified and directed.
M&L for Servicing of the window AC 1.5/2 ton capacity of any make, including oiling/greasing the blower motor, cleaning the evaporator condenser coils externally to remove the dust, replacement of defective thimbles etc reassembling and re-fixing the air conditioner at its original position or as directed by the experienced refrigeration mechanic complete all as specified and directed. Note:- (i) Any unserviceable items need to be replaced/gas charging etc shall be replaced & paid seperately under respective items. (ii) The cost of dismantling, taking out window AC 1.5/2.0 ton from window and shifting to location where directed for proper washing and servicing and refixing the same shall be deemed to be included in item rate quoted.
All as per item Ser No. 79.00 above but for split type AC/Inverter type AC 1.5/2.0 ton.
All as per item Ser No. 79.00 above but for split type AC/Inverter type AC 3.0 ton.
M&L in replacement Fan Motor of AC (Window/ Split Type) 1.5 TR Capacity including taking out the unservice-able Fan Motor from the AC complete all as specified and directed.
All as per item Ser No 82.00 above but AC (Window/Split Type) 2.0 TR Capacity.
All as per item Ser No 82.00 above but AC (Window/Split Type) 3.0 TR Capacity.
M&L Rewinding Fan Motor of AC 1.5/2.0/3.0 TR Capacity, (Window/Split Type) with Super Enameled Copper Wire of appropriate Gauge including taking out burnt Winding wire complete all as specified and directed.
M&L Air circular Blower Fan Motor of AC (Split Type), 1.5 /2.0/3.0TR Capacity including taking out unser-viceable Air circular Blower Fan Motor complete all as specified and directed.
S&F Air Filter suitable of AC (Window type) 1.5 /2.0/3.0 TR Capacity including taking out unserviceable Air Filter from AC complete all as specified and directed.
S&F Air Filter suitable of AC (Split type) 1.5 /2.0/3.0 TR Capacity including taking out unserviceable Air Filter complete all as specified and directed.
S&F Capacitor Running 36 mfd – 45 mfd suitable for AC (Window/Split Type) 1.5 TR/2.0/3.0 TR Capacity and of any make including taking out unserviceable Capacitor from AC complete all as specified and directed.
S&F Capacitor Starting 80 mfd – 120 mfd suitable for AC (Window/Split Type) 1.5 TR/2.0/3.0 TR Capacity and of any make including taking out unserviceable Capacitor from AC complete all as specified and directed.
S&F Fan Motor Blades AC (Window/Split type) 1.5/2.0/3.0 TR capacity including taking out unserviceable Blades of Fan Motor from AC complete all as specified and directed.
S&F Fan Motor Capacitor 6 mfd suitable for old ones AC (Window/Split Type) 1.5/2.0/3.0 TR capacity including taking our unserviceable capacitor from AC complete all as specified and directed.
S&F Front Plastic Grill (as per Sample) of AC (Window type) 1.5 TR/2.0/3.0 TR Capacity including taking out unserviceable Front Plastic Grill from AC all as per existing and complete all as specified and directed.
S&F Front Plastic Grill for inner unit (as per Sample) of AC (Split type) 1.5/2.0/3.0 TR Capacity including taking out unserviceable Front Plastic Grill from AC all as per existing complete all as specified and directed.
S&F Runner for air blower motor of AC (split type) AC 1.5/2.0/3.0 TR capacity (As per sample or as per site requirement) including taking out unserviceable Runner of Air Blower Motor from AC all as per existing complete all as specified and directed.
S&F Starting Relay of AC (Window/Split Type) 1.5 TR/2.0/3.00TR Capacity including taking out unserviceable Starting Relay from AC complete all as specified and directed.
M&L Strainer with Capillary Tube of AC (Window/ Split Type) 1.5 /2.0/3.0TR Capacity including taking out unserviceable Strainer with Capillary Tube from AC complete all as specified and directed.
S&F Thermostat Switch of AC (Window/Split Type) 1.5 TR/2.0/3.0 TR Capacity including taking out unserviceable Thermostat Switch from AC complete all as specified and directed.
S&F cooling coil suitable for window type room AC 1.5/2.0 TR including taking out unserviceable cooling coil complete all as specified and directed.
S&F Condensing coil suitable for window type AC 1.5/ 2.0 TR including taking out unserviceable condensing coil complete all as specified and directed.
S&F Condensing coil suitable for split type AC upto 3 TR capacity including taking out unserviceable condensing coil complete all as specified and directed.
S&F cooling coil suitable for split type AC upto 3 TR capacity including taking out unserviceable cooling coil complete all as specified and directed.
S&F Indoor unit suitable for 1.5 TR split type AC complete including taking out unserviceable Indoor unit complete all as specified and directed.
S&F outdoor unit suitable for 1.5 TR split type AC without compressor including taking out unserviceable outdoor unit complete all as specified and directed.
S&F Indoor unit suitable for up to 2 TR split type AC including taking out unserviceable Indoor unit complete all as specified and directed.
S&F outdoor unit suitable for up to 2 TR split type AC without compressor including taking out unserviceable outdoor unit complete all as specified and directed.
Suuply & Fix in replacement of Hermitacally sealed compressor for split/ window type AC capacity 1.5 Ton complete all as specified and directed.
All as per item Ser No 109.00 above but of split/ window type AC capacity 2.0 Ton.
All as per item Ser No. 109.00 above but of split/ window type AC capacity 3.0 Ton.
S&F PCB with remote for window type AC up to 2 Ton capacity including taking out unserviceable PCB unit complete all as specified and directed.
M&L PCB with remote for Split type AC 1.5/2/3 Ton capacity including taking out unserviceable PCB complete all as specified and directed.
M&L PCB & motherboard with remote complete set for Inverter Split type AC up to 2 Ton capacity including taking out unserviceable PCB & mother board complete all as specified and directed .
S&F wiring kit suitable for 1.5/2.0/3.0 ton capacity AC complete including taking out unserviceable wiring kit complete all as specified and directed.
S&F gas charging pin valve complete including taking out unserviceable pin valve complete all as specified and directed.
Supply and charging the gas refrigerant R22 (including refrigerant) of window type AC upto 3 ton capacity including testing after application of nitrogen gas pressure to find out any leakage, brazing and stopping of all leakage detected, re-application of nitorgen pressure to ensure leak proof gas circulator system flushing out the nitrogen gas complete all as specified and directed.
All as per item Ser No 117.00 above but R- 410 for split type AC up to 3 TR capacity.
All as per item Ser No 117.00 above but R-32 Refg upto 03 Ton AC.
S&F in replacement of casing of window type AC including company fitted condensing & cooling coil complete including PCB except compressor complete all as specified and directed.
M&L in replacement of split valve ¼” for split AC up to 3.0 ton capacity complete all as specified and directed.
All as per item Ser No.121.00 above but 1/2".
S&F in replacement compressor shut off valve 3/8" for split AC up to 2.00 ton capacity complete all as specified and directed.
S&F in replacement compressor shut off valve 5/8" for split AC up to 2.00 ton capacity complete all as specified and directed.
S&F in replacement of electrolyte grade copper tubing of size 1/4" suitable for any type of split type AC including synthetic rubber foam complete all as specified and directed. Note: - The quoted rate is inclusive of necessary T&P, Rope, Ladder etc with safety equipment for execution the work upto six stories building.
All as per item Ser No.125.00 above but size 1/2".
All as per item Ser No.125.00 above but size 3/8".
All as per item Ser No.125.00 but size 5/8".
S&F in replacement PVC conduit 20mm dia including all clamps & accessories and connecting the condensate pipe of ACs to this conduit for proper drainout of condensate water from ACs of Bldgs upto 5 (five) storey complete all as specified and directed.
S&F in replacement PVC conduit 25mm dia including all clamps & accessories and connecting the condensate pipe of ACs to this conduit for proper drainout of condensate water from Acs of Bldgs upto 5 (five) storey complete all as specified and directed.
SNOWY ENGINEERING INC
HONEY COLLECTION
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .