GE (I) (CGN) KOLKATA
GE (I) (Coast Guard Navy) Military Engineer Services Damodar Complex Naval Transit Accommodation Hastings, Kolkata 700 023
PROVISION OF PATHWAY LIGHTS AND DECORATIVE HERITAGE TYPE LIGHTS AT CGRE MANICKTALA UNDER GE (I) (CGN) KOLKATA
2026_MES_748473_1
8701/54/2025-2026/04/E8
Open Tender
Electrical and Maintenance Works
Item Wise
120 days
Manicktala
As per tender document
9 documents required · 9 mandatory
₹500
GE (I) (CGN) Kolkata
₹86,400
Yes
14 Jan 2026
14 Jan 2026
5 Feb 2026
14 Jan 2026
4 Feb 2026
29 Jan 2026
Supply and fixing minimum 10 watt, 230 V AC LED bollard landscape light fitting of Sturdy IP 65 LED Bollard with excellent/glare free soft light output through its PMMA window ensuring maximum illumination aspect in surrounding with aluminium die cast material for fixture along with anti-ageing spray treatment on housing for longer life complete all as specified and directed.
Supply and fixing of decorative heritage ornamental type poles of height 3 mtr including of Antique double arm vintage type bracket with 02 Nos of 30 watt, 230 V AC, LED light fittings with execellent/ glare free soft light out put through its PMMA window ensuring maximum illumination aspect in surrounding for longer life complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 sq. mm 3.5 core complete all as specified and directed. ( for CSS panel to Main Lt panel)
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 sq. mm 4 core complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60cm×60cm× 6mm thick, buried directly in ground vertically at a depth not less than 2.25 metres deep below ground level with top edge of the earth plate at a depth not less'than 1.5 metres below normal ground level, surrounded fromall sides by 15 cms thick and packed layer of charcoal dust and common salt filling in alternate layer etc and connected to and including GI earth strip 32 x 6 mm size upto by means of bolts, nuts, check nuts and washers made out of galvanised iron and protected by medium grade 50 mm dia 5 mtr long and connected to main control panel and GI pipe 20 mm medium grade as watering pipe including funnel, wire mesh, PCC pit made up of PCC 1:2:4 type C2 and RCC cover 40 mm thick with 8 mm bar 15 c/c including excavation and earth work all as specified in SSR Part 1-2020 complete all as specified and directed.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 sq. mm 2 core complete all as specified and directed.
M&L for cement concrete (PCC) in foundation, filling as in mass concrete type B2, (1:4:8) with 40 mm graded stone aggregate with complete form work complete all as specified and directed.
Excavation in trenches, n. exc. 1.5m wide and n. exc. 1.5m in depth; for laying of cable, n. exc 10 sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm complete all as specified and directed.
Removing excavated material n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above the starting point complete all as specified and directed.
M&L for Dry sand filling as cable cushoining complete complete all as specified and directed. . (Note - Thickness for sand shall be measured after punning down 23 cm layer)
Demolition of Concrete in ground floors and pavings of foundations any thickness any size (below or above ground level) complete all as specified and directed.
M & L Bricks, common burnt clay building bricks, old size sub-class ‘B’ designation 75 laid perpendicular to the axis of cable,abutting 10 mm gap in between complete all as specified and directed.
Taking out carefully 10 Watt LED Conical Bollard Light alongwith submain complete all as specified and as directed. (Taken out lights to be kept in E/M store).
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.24 MB
BOQ_838221.xls
BOQ • 0.29 MB
TENDER54.pdf
Tender Documents • 0.79 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .