Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹43.8 LAccepted-AOC | L1 | Accepted-AOC ACCEPTED | |
| 2 | L2₹54.8 L+₹11.0 L (25.2%)Rejected-AOC | L2 | Rejected-AOC REJECTED | |
| 3 | L3₹58.5 L+₹14.8 L (33.7%)Rejected-AOC | L3 | Rejected-AOC REJECTED | |
| 4 | Rejected-Technical B 17 SHRIRAM INDUSTRIAL ESTATE G D AMBEKAR ROAD WADALA MUMBAI CITY MAHARASHTRA 400031 | MUMBAI | MAHARASHTRA | 400031 | - | Rejected-Technical No Remark in WLR |
Tender Value
₹43 L
EMD Value
₹86,000
Closing Date
14 Mar 2022, 6:00 pmClosed
GE NW BHANDUP
GE(NW) BAHDNUP, MUMBAI
SPECIAL REPAIR FOR REPLACEMENT OF LT PANEL BOARD AT INS HAMLA AND PROVISION OF HIGH MAST AREA SECURITY LIGHT AT NCHC POWAI UNDER GE(NW) BHANDUP
2022_MES_507001_1
8182/B
Open Tender
Civil Works
Item Rate
180 days
POWAI
AS PER TENDER DOCUMENTS
8 documents required · 8 mandatory
₹500
GE(NW) BHANDUP
₹86,000
Yes
24 Aug 2022
9 Feb 2022
15 Mar 2022
9 Feb 2022
14 Mar 2022
28 Feb 2022
Amount
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type(C.P.R.I Approved), platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-51 as per IS : 2147 and it shall be suitable to withstand a Fault level of 50 KA (rms) for one second shall be dust and vermin proof, and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Location:- 'A' Zone Sub Station. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 1200 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 1200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type(C.P.R.I Approved), platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-51 as per IS : 2147 and it shall be suitable to withstand a Fault level of 50 KA (rms) for one second.hall be dust and vermin proof, and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Location:- 'D' Zone Sub Station. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 1200 Amp 4 Strips, Aluminium conductor, with color coded(R,Y,B,N) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 1200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type(C.P.R.I Approved), platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system conforming to IS : 375 all as specified herein after. Degree of protection shall not be less than 1P-51 as per IS : 2147 and it shall be suitable to withstand a Fault level of 50 KA (rms) for one second.hall be dust and vermin proof, and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS Iron angle frame, front and Back opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Location:- 'C' Zone Sub Station Make:- Universal Switch Gear Control or any equivalent as per List of Makes. The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 1000 Amp 4 Strips TPN, Aluminium conductor, with color coded(RYBN) heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 1000/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-51) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- Sea Hawk Bldg The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 300/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 160 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 24 No. SPARES :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 04 No. Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-51) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- Union Bank The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 200 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 04 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 02 No. SPARES :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Indoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-51) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- 'A' Zone DG set LT panel The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 400 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 400/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 160 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 05 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. SPARES :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos, (ii) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-42) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- 'New NICA LT panel Outdoor Type The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 300 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 300/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 160 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 125 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos, (ii) MCCB 63 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (iii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. SPARES :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-42) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- 'SI Canteen LT panel Outdoor Type The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 200 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 200/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 02 No. SPARES :- (i) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-42) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- 'B' Zone 200 KVA T/F'S LT panel Outdoor Type The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 400 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 400/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 250 Amps 36 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 02 No, (ii) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 03 No, (iii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. SPARES :- (i) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (ii) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (iii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installing, testing and commissioning factory made and tested LT Panel Outdoor type, platform mounted, suitable for 415 Volts 3 Phase and neutral, 4 wire, 50Hz AC supply system.conforming to IS : 375 all as specified. The panel shall be dust and vermin proof, protection class shall not less than(IP-42) and made of 2.00 mm thick Stainless Steel Sheet SS316 thick & suitable frame work/ support made out of 50x50x6 mm MS iron angle, front opening type with space for cable entry from back side of the panel, with proper ferrule & cable gland, internal wiring with PVC insulated multistranded copper conductor FRLS cable of adequate size but not less than 1.5 sqmm complete. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels. Make:- Universal Switch Gear Control or any equivalent as per List of Makes. Location:- 'B' Zone 400 KVA T/F'S LT panel Outdoor Type The scope of work also comprising of the following:- BUS BAR CHAMBER :- (a) 800 Amp 4 Strips, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) Protection MCB 6 A SP C Series- 1 Set. (Set of three). (iv) CT 800/5A Set of -03 Make of Metering Accessories :-L&T/ AE/ Trinity/ Schneider.
INCOMING SUPPLY :- (i) MCCB 400 Amps 36 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. OUTGOING SUPPLY :- (i) MCCB 250 Amps 36 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos. (ii) MCCB 200 Amps 36 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 Nos,Include with Provision of Rotary Switch with Lock arrange) (iii) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 03 No, (iv) MCCB 63 Amps 18 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (v) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. SPARES :- (i) MCCB 200 Amps 36 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 (ii) MCCB 100 Amps 25 KA, 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz = 01 No, (iii) MCB 32 Amps 'B' Series 10 KA, SPN = 01 No. Note : All MCCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Supply, installation, Testing commissioning of Automatic power factor improvement capacitor Bank(APFC Panel) having aggregate capacity : 150 KVAR in 07 stages with micro processor along with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of Stainless Steel sheet (SS) SL316 sheet 2.00 mm thick & frame SS Channel having bus bar of Aluminum 200 Amps cap, three phase and one neutral fixed on insulator and bus bar insulated by coloured heat shrinkable sleeve & housed in specified compartment both side open able . All the cover shall have with suitable locking arrangements , fully internally wired with suitable size of thimbles. Incoming / outgoing internal connection with PVC insulated PVC sheathed multistranded copper wire of suitable size all as directed & comprising the following :- Location : 'B' Zone Sub Station.Make : ABB/HPL/Umiversal Switchgear or any equivalent make approved by the GE. Note :The panel manufacturer should have Govt. Approved CPRI Certification.and The contractor duly shall submit the Manufacturer'S Design and drawings of LT panels.
BUS BAR CHAMBER :- (a) 800 Amp 3 Strips & Neutral Strip 400 Amp, Aluminium conductor, with color coded heat shrinkable sleave and shall be mounted on non hygroscopic, non combustible, track resistant, high strength DMC material, interconnection of all incomings & outgoings. INSTRUMENT CHAMBER :- (i) Digital Multifunction Meter ( VAF+PF ) 3 Phase- 01 Set. (ii) Red,Yellow,Green Phase indicating Lights LED type 220V AC- 1 Set. (Set of three). (iii) CT's 800/5A, Make: L&T/ Trinity/ AE - 1 Set of 03 Nos. (iv) Protection MCB 6 A SP C Series- 5 Nos. Make of Metering Accessories :-L&T/ AE/ Schneider. INCOMING SUPPLY :- 1. MCCB 500 Amps 36 KA , 4 Pole with Fixed thermal & magnetic release 415 volts , 50Hz,=01 No., 2. Power Factor Correction relay 14 Stage 3 Phase, Make: L&T/ Epcos/ Trinity - 1 No. 3. Capacitor duty contactor for 20 KVAR, Make L&T/ Schneider - 4 Nos. 4. Capacitor duty contactor for 10 KVAR, Make L&T/ Schneider - 4 Nos. 5. Capacitor duty contactor for 5 KVAR, Make L&T/ Schneider - 6 Nos. 6. MCB 63 A. 10 KA TP for 20 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 4 Nos. 8. MCB 25 A. 10 KA TP for 10 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 4 Nos. 9. MCB 16 A. 10 KA TP for 5 KVAR, Make: L&T/ Schneider/ HPL/ Legrand - 6 Nos. Note : All MCCB'S/MCB'S shall conform to IS : 13947 (Part 3, 1993) and IEC-60947 (Part 2) with MES Approved List Makes
Material and labour for earthing complete with GI earth plate electrode 600x600x6 mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground lavel) with top edge of the plate not less than 1.5mtr below normal ground lavel connected to GI Earth strip 32x6 mm by mean of bolts, nuts, check nuts and washer of brash all as shown in electrical plate No 5 connected to earthing test point all as specified or indicated including PCC pit and CI cover fullel with watering pipe, wire mess and copper lugs etc GI protection pipe 40 mm dia medium grade including testing on completion all as specified and directed.
Supply and lay cable XLPE Insulated screened Meter PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 25 sq mm 4 core.
Supply, fabrication, errection , commissioning and testing of High Mast lights with motorised lowering and lifting of 16 meter high galvanized mast suitable for 08 Nos lantern symmetrically fitted along with their control gear and having two point suspension system with steel wire rope of 6 mm dia, thickness - 3 mm top and 4 mm bottom diameter of mast top 150 mm and 410mm bottom, and double drum winch, trailing cable - 2 Per mast (5 Core 2.5 sqmm) Lighting finial, Anchor plate & templete including foundation as per manufacturer specify with foundation bolts & Nuts complete. Make Surya/Philips/ Crompton
Supply and fixing LED flood light 200 watt 230 V AC pressure die cast aluminum housing outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant and suitable for high mast pole with all connected accessories and equipments complete with driver and lamp etc Make: Philips / Surya/ Crompton”
Excavation in trenches n.exc 1.5 m wide and n. exc 1.5 m in depth and getting out in soft/loose soil for removing/laying of cables complete all as specified and as directed by Engineer-in-charge.
Returning, filling including spreading , leveling , watering and well ramming in layers n.exc 25 cm complete all as specified and as directed by the Engineer-in- Charge
Removing excavated material to a distance n.exc 50 m and depositing where directed at a level n.exc 1.5 mtr above the starting point complete all as specified and as directed by Engineer-in-Charge
Supplying and laying unreinforced precast concrete cable cover class LV type 1, flat, size 250 x 150 x 40 mm complete all as specified and directed by the Engineer - in - charge.
Supply and spreading sand (stone crush) dust in trenches as cushioning to under ground cable on top and bottom of cable all as specified.
Deduct Credit for Demolished/ Dismantled material Rs. (-) 1,76,600.00 (Minus) as listed in Schedule of Credit Note: Tenderers will not quote against this item being a tentative amount to be considered to arrive at the 'Contract Sum'
AIRDOT ENGINEERING
NOEL ENGINEERS
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .