Loading…
Loading…
Tender Value
₹47 L
EMD Value
₹94,000
Closing Date
1 Sept 2026, 6:00 pm
GE 866 EWS, Carnicobar
GE 866 EWS CARNICOBAR PIN-913866 C/O 99APO
SPECIAL REPAIR TO LT PANEL BOARDS INSTALLED AT 955 SQN NEAR LOGISTIC NEAR AIRMEN MESS NEAR CSD NEAR MI ROOM NEAR AIRMEN POTA CABIN NEAR SMC MESS and ACCN AND 151 SQN SUB STN INCLUDING ASSOCIATED CABLE WKS AT AF STATION CARNICOBAR
2026_MES_783931_1
8822/E8
Open Tender
Civil Works
Item Rate
270 days
GE 866 EWS, Carnicobar c/o 99 APO
As per tender documents
9 documents required · 9 mandatory
₹500
GE 866 EWS
₹94,000
Yes
11 Aug 2026
11 Aug 2026
8 Sept 2026
18 Aug 2026
1 Sept 2026
25 Aug 2026
11 Aug 2026 - 18 Aug 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Taking out old unserviceable panel board from existing position and making good of disturbed portion of floor and wall including disconnecting all cables and joints complete all as specified and as directed. | 9 | EACH JOB | - | - |
| 2 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 1.3 x 1.1x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :-
Location : 955 SQN | 1 | EACH JOB | - | - |
| 2.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 400 Amps, 36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 2.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 250 Amps, 36 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) MCCB 3 Phase, 04 Pole 100 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(iii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(iv) MCB C Type 32 Amps SPN - 02 Nos | - | - | - | - |
| 3 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 2.0 x 2.0x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :-
Location : Near Logistic | 1 | EACH JOB | - | - |
| 3.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 350 Amps, 36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 3.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 100 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 02 Nos
(ii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 04 Nos
(iii) MCCB 3 Phase, 04 Pole 40 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 06 Nos | - | - | - | - |
| 4 | Supply installing testing and commissioning in replacement of factory made and tested, CPRI approved LT main feeder pillar outdoor type of size 2.0 x 1.5 x 0.75 mtr, weather, vermin proof, free standing floor mounting type mounted of floor/over the duct, with required mounting channel, cable alley for all the feeders, suitable for 440 Volts, 3 phase 4 wire 50Hz AC supply system, conforming to IS - 5039, IP-54 class protection and made of 3.15mm CRCA mild steel sheet with 50x 50x6mm angle iron frame, hinged doors, front & rear opeing and locking arrangement ( including provision of 65mm lock with 2 Keys) with necessary bus bar arrangment with insulated Aluminium bus bar 600 Amps rating for three phase & neutral, 4 strips, installed on epoxy insulators housed in separated bus chambers covered with heat shrinkable sleeves with necessary bus bar tapings for MCCBs with suitable capacity of Alumium bus bar strips including heat shrinkable sleeves, and providing extended bus bars with chember arrangement for outgoing cables, copper control wiring of required size for instruments grouting with PCC foundation work (necessary excavation PCC foundaton included in the quoted rate) and including the following accessories :-
Location : Near Airmen Mess | 1 | EACH JOB | - | - |
| 4.1 | INCOMMER
(i) MCCB 3 Phase, 4 Pole 400 Amps,36kA rupturing cap,ICs = 100%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) Digital voltmeter 0 to 500 volt - 01 Set
(iii) Digital ameter 0 to 400 amp - 01 Set
(iv) Phase indicating lamp RYB with incating voltage in digital LED format ( set of three) - 01 Set
(v) Digital Multifunctional meter (Showing PF, Frequecy, Current, Voltage, Temperature, Timings etc)
(vi) Selector switch - 02 Nos | - | - | - | - |
| 4.2 | OUTGOING
(i) MCCB 3 Phase, 04 Pole 250 Amps, 36 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 01 Nos
(ii) MCCB 3 Phase, 04 Pole 63 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 05 Nos
(iii) MCCB 3 Phase, 04 Pole 40 Amps, 16 kA rupturing cap,ICs = 75%Icu with adjustble thermal and fixed magnetic setting 415 volts 50 HZ AC supply - 04 Nos | - | - | - | - |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.42 MB
BOQ_878352.xls
BOQ • 0.34 MB
8822Tenderdocument.pdf
Tender Documents • 1.06 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].