Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹60.6 LAdmitted-Finance | L1 | Admitted-Finance | |
| 2 | L2₹62.7 L+₹2.1 L (3.52%)Admitted-Finance | L2 | Admitted-Finance | |
| 3 | L3₹70.4 L+₹9.8 L (16.1%)Admitted-Finance 135 CHAKRANA TIWARI CHAKA NAINI PRAYAGRAJ 211008 UTTAR PRADESH | PRAYAGRAJ | UTTAR PRADESH | 211008 | L3 | Admitted-Finance | |
| 4 | Not Admitted-Fee/PreQual/Technical | - | Not Admitted-Fee/PreQual/Technical Not Complied with technical specification |
| Sl No | Description | Qty | Unit | vijay builders L3 | M/s R.S CONSTRUCTIONS L1 | M R ENGINEERS & TRADERS L2 |
|---|---|---|---|---|---|---|
| 1.00Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr. ST poles, 30 mm² ACSR Conductor for creation of 25 KVA Sub Station at Hamlet Patian Village Ladha, 2x63 KVA Sub stn. At Hamlet Ramble Village Ladha & Hamlet Upper Manta Village Moud & Insertion of 9 mtr. long ST poles in HT line at village Ladha and Moud. | ||||||
| 1.01 | 9 mtr. Long ST Pole (ST-410 SP-33) | 59 | no. | 1,47,500 ₹12,09,500 | 1,18,000 ₹10,62,000 Lowest | 2,95,000 ₹10,91,500 |
| 1.02 | GI V Cross -arm with top Bracket including clamps | 660 | Kg | 26,400 ₹1,18,800 | 3,300 ₹82,500 Lowest | 66,000 ₹1,98,000 |
| 1.03 | GI Channel X-arm including clamps and Braces | 660 | kg | 26,400 ₹1,18,800 | 3,300 ₹82,500 Lowest | 66,000 ₹1,98,000 |
| 1.04 | 30 sqmm ACSR Weasel Conductor | 6.4 | km | 51,200 ₹2,88,000 | 25,600 ₹2,24,000 | 38,400 ₹2,17,600 Lowest |
| 1.05 | PG Clamps for 30 mm² ACSR Conductor | 18 | no. | 1,800 ₹6,120 | 180 ₹360 Lowest | 360 ₹2,160 |
| 1.06 | 11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm. | 150 | no. | 15,000 ₹52,500 | 7,500 ₹37,500 | 3,750 ₹29,250 Lowest |
| 1.07 | 11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting. | 60 | no. | 6,000 ₹27,000 | 3,000 ₹21,000 | 1,500 ₹17,400 Lowest |
| 1.08 | Galvanized Nuts and Bolts | 60 | kg | 3,000 ₹12,000 | 600 ₹7,800 Lowest | 3,000 ₹15,000 |
| 1.09 | 11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type | 3 | Set | 6,000 ₹36,000 | 600 ₹30,600 | 6,000 ₹30,000 Lowest |
Tender Value
Refer Docs
EMD Value
₹1.4 L
Closing Date
31 Jan 2023, 4:00 pmClosed
Executive Engineer Electric Division UdhampurJPDCL
Executive Engineer Electric Division UdhampurJPDCL
Creation of 25 KVA SS and 2x63 KVA SS alongwith HT/LT
2023_PDD_203034_1
ED/Udh/122 of 2022-23 dt. 20-01-2023
Open Tender
Electrical Works
Turn-key
45 days
In District Udhampur
Please refer Tender documents.
2 documents required · 2 mandatory
₹2,000
Executive Engineer Electric Division UdhampurJPDCL
₹1.4 L
5 Apr 2023
20 Jan 2023
1 Feb 2023
20 Jan 2023
31 Jan 2023
20 Jan 2023
20 Jan 2023 - 27 Jan 2023
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of 11 KV line on 9 mtr. ST poles, 30 mm² ACSR Conductor for creation of 25 KVA Sub Station at Hamlet Patian Village Ladha, 2x63 KVA Sub stn. At Hamlet Ramble Village Ladha & Hamlet Upper Manta Village Moud & Insertion of 9 mtr. long ST poles in HT line at village Ladha and Moud.
9 mtr. Long ST Pole (ST-410 SP-33)
GI V Cross -arm with top Bracket including clamps
GI Channel X-arm including clamps and Braces
30 sqmm ACSR Weasel Conductor
PG Clamps for 30 mm² ACSR Conductor
11 KV Polymer composite Pin Insulator 12 KV, 5 KN, lighting impulse 75 KV Positive and 80 KV Negative, Creepage distance 320mm.
11 KV Polymeric Composite Disc insulator 12 KV, min failing load 45 kn, lightening impulse 75 Positive and 80 KV Negative, creepage distance 320mm with fitting.
Galvanized Nuts and Bolts
11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip 25X3 mm
Painting of 9 mtr ST poles with two coat of Aluminium Paint.
Al jointing sleeves
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioningfor creation of 25 KVA Sub Station at Hamlet Patian Village Ladha & 2x63 KVA Sub stn. at Hamlet Ramble Village Ladha & Hamlet Upper Manta Village Moud
11/0.433kV, 3-phase 25 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
11/0.433kV, 3-phase 63 KVA Distribution Transformer with Bimetallic Terminal Connectors Energy Level-2, Aluminium wound, and with LV Cable Box having detachable Aluminium Gland plate
Gapless surge arrestor 9KV, 10KA, LA with polymer housing station type
11kV GO, Switch 3-Phase, 3-Pole, 200 Amp, Vertical Type
11 kV Horn Gap Fuse Set 3 Phase 200A
120 mm² 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
95mm² 1.1kV Grade, PVC Insulated Alumnium Stranded Conductor FRLS type
9 mtr. Long ST Pole (ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV, min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
GI Channel/Angle/Flat of sizes including clamps
Galvanized Nuts and Bolts.
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239. GI Strip for neutral earthing of size 50 mm x 6 mm & 32mm x 3mm for connection of transformer body, G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber with RCC slab cover.
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm with tension fitting
LT distribution box for 63 KVA DTR with MCCB for incomer and SfU's for outgoing circuits.
LT Fuse set made of 50x6mm Angle iron with 50x6mm Aluminium strip fixed on Bus bar insulators.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
Danger Plates with Clamps
Cement bottoming 1:2:4 mix as per REC standards 0.5cum/pole
Painting of ST poles 9 mtr. Long with two coats of aluminium paint
Survey, Supply, Transportation, Carriage, Erection, Testing and Commissioning for erection of LT line 1 phase 2 wire LT on 8 mtr long ST poles, 30 mm sq. ACSR Weasel Conductor at Village Ladha & Moud.
8 mtr. Long ST Pole (ST-410 SP15)
G.I M Clamps for Shackle Insulator
30 sqmm ACSR Weasel Conductor
Shackle Insulator
Galvanized Nuts and Bolts.
Danger Plates with Clamps
Anti-Climbing Device with Clamps
Earthing complete by GI Rod 20 mm, 2.5 mtr long through G.I. Strip25X3 mm
Painting of 8 mtr ST poles with two coat of Aluminium Paint.
Galvanised Stay Set with 50x8mm stay clamp, guy insulator (2Nos.), anchor plate (200x 200 x 6 mm), nut-bolts, 2 Nos turn-buckles, 1.8m long, 16 mm diameter solid GS stay rod & 7/3.15 mm dia GI stranded wire complete
M R ENGINEERS & TRADERS
vijay builders
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .