Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹23.3 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹26.5 L+₹2.7 L (11.2%)Rejected-AOC 1 TROPICAL REFRIGERATION PHONIX BAY PORT BLAIR PORT BLAIR ANDAMAN NICOBAR 744101 | SOUTH ANDAMANS | ANDAMAN AND NICOBAR ISLANDS | 744101 | L2 | Rejected-AOC Being Not L1 | |
| 3 | L3₹31.4 L+₹7.5 L (31.5%)Rejected-AOC | L3 | Rejected-AOC Being Not L1 | |
| 4 | Rejected-Technical | - | Rejected-Technical Not enlisted with requisite category c(i) | |
| 5 | Rejected-Technical | - | Rejected-Technical Not enlisted with requisite category c(i) |
Tender Value
₹24 L
EMD Value
₹48,000
Closing Date
2 Jan 2024, 6:00 pmClosed
Lt Col Sandeep Juneja Offg CWE
Commander Works Engineer Military Engineer Services Junlighat Post Minniebay Port Blair 744103
81062 Rep Maint of Air conditioning plant, central AC plant package type AC plat at INS Utkrosh NTS Teylerabad NAD dollygunj under AGE EM No II at GE Minniebay Port Blair
2023_MES_631128_1
81062 Rep Maint of AC Plant GE Minniebay
Open Tender
Civil Works - Others
Item Rate
180 days
Port Blair
as per NIT
8 documents required · 8 mandatory
₹500
GE Minniebay
₹48,000
Yes
23 Feb 2024
5 Dec 2023
8 Jan 2024
5 Dec 2023
2 Jan 2024
19 Dec 2023
6 Dec 2023 - 12 Dec 2023
Amount
Overhauling of compressor 36TR complete including taking down unserviceable parts and refixing new parts whererever necessary complete all as directed by Engr-in-Charge after pumping down the complete system and collecting the refrigerant into condencer, compressor oil into clean container, disconnecting the compressor from suction & discharge side and including leak testing of compressor after reassembling the parts, recharging/filling retrieved oil & gas, replacement of belt if required and testing upto satisfactory cooling performance complete all as specified and as directed. SM No 654/0025/CR-1/08, 654/0025/CR-1/09 Make: Bock compressor.(NTS Teylerabad) Note: (i) spare parts , refrigerant (gas) & compressor oil for top up if required shall be measured and paid for seperately as supply only in respective item of this schedule. (ii) Metal filling , grinding, polishing spring, washer, quarter, and consumable items such as grease cotton waste etc., are deemed to be included in the quoted rate. (iii) Belt shall be paid seperately as supply only.
M&L for repair to suction & discharge valve of compressor 36 TR of capacity by means of replacing the teflon washer sheet, suction & discharge valve ring, spring, 'O' rings, gaskets etc complete and testing for proper holding of valve, leak testing etc all as specified and as directed. make: BOCK compressor. Note: The rate shall be inclusive of suction & discharge valve which is consider as one job.
M & L for descaling the shell & tube condenser of 36 TR capacity at by circulating the descaling chemical (scale gun) (HCL acid) through condenser by pressure feeding method after disconnecting condenser water lines, and opening the end covers of both side, brushing condenser water tubing, removing the scales, normalising the copper surface circulation normalising agent and refixing all dismantled parts including replacement of gasket set all as specified and directed by Engineer-in-charge.
M & L for leak testing of AHU unit cooling coil after pumping down the complete system, isolating the cooling coil from both ends and charging the dry nitrogen gas for pressure leak test, after detecting leak point, release the nitrogen gas, repairing the leak point but means of soldering/brazing and connecting the cooling coil with system, vaccumised the complete system and re-charge the system by refrigerant, testing and commissioning up to satisfactory cooling performance of 72TR capacity. Note: (i) Refrigerant gas shall be mesaured and paid separately as supply only. (ii) Nitrogen gas required deemed to be inclusive in the quoted rate.
M&L for servicing of package type indoor unit of capacity 5.5/8.5/10/16 TR by opening front grill, bottom grill cleaning filters, by spraying water jet, removing dust/dirt from package unit all over, checking electric connection, checking any leakage by applying soap solution on joint & liquid/vapour lines properly checking functionality of all spares & replacing the same under relevent item of schedule & put the air conditioner into operation complete all as specified and directed by Engr-in- charge/GE. Note : (i) Spare parts will be measured and paid separately. (ii) Sliding the filter out and washing it with water and drying in the shade, reinstalling the same. (iii) Checking the compressor for oil leakage and inspection of vibrations insulation rubber for wear and tightening the mounting lugs.
All as per item No 5.00 above but outdoor unit of package unit of capacity 5.5/8.5/10/16 TR .
S&F in replacement of stainless steel fan guard grill for Condenser fan suitable for out door unit of capacity upto 16 TR as per sample including taking out old rusted fan grill and fixing the new grill with nuts bolts and washers and making good the surface by painting complete all as specified and directed.
S & F in Replacement of panel air filters, dry type, washable, rated air flow capacity 1600 CFM 99.9%, down to particle 20 micron of Suitable sizes or nearest for AHU of central AC plant at NTS Teylerabad
M&L for pumping down the gas of the Package type AC plant of various capacities pressure testing the complete plant by dry nitrogen gas by separating high side and low side, rectifying the leakage by gas welding brazing pressure testing vaccuming the system and re-charging the system with gas, testing and commissioning complete.(INS Utkrosh 16Tr,10Tr, & NAD 8.5Tr) Note:- (i) Nitrogen gas required shall deemed to be include in the quoted rate. (ii) Refrigerant gas shall be mesaured and paid separately as supply only.
Cleaning / servicing the cooling coil of AHU AC plant by capacity of 8.5 TR by pressure air method with using air blower and cleaning the cooling coil with cleaning the solution, cleaning the AHU base tray completely and applying one coat of synthetic enamelled paint inside the base tray, including greasing to AHU blower shaft bearing for smooth functioning, cleaning the AHU filter replacement of V-belt (if required) of NAD Dollygunj all as specified .
S&F in replacement of copper pipe of size 1/2" complete all as specified and directed.
S&F in replacement of copper pipe of size 1" complete all as specified and directed.
M&L for dismantling old unserviceable compressor & supply, installation, testing & commissioning of new compressor as per existing make and type 3 ph 415 V 50 Hz of capacity not less than 5.5/5 TR & connecting suction, discharge line by jointing with copper rod & oxygen flame and making electric connections & wiring with microprocessor control panel & sensor complete all as specified and directed. SM/MES No MES-876/3007-PA-3/12-Each unit holding 03 Compressor MES-876/3007-PA-2/12- Each unit holding 03 Compressor MES-876/3007-PA-1/12-Each unit holding 03 Compressor 654/0003/Pkg/06-Each unit holding 02 Compressor 654/0002/Pkg/06-Each unit holding 02 Compressor 654/0001/Pkg/06-Each unit holding 02 Compressor Note: (i) The cost of any other sensing/protective device Eqpt required to make the plant functional related to compressor shall be included in quoted rates. (ii) The cost of hiring of technician from the OEM of compressor for installation & commissioning shall be included in quoted rate.
All as per item No 13.00 above but outdoor unit of package unit of capacity 8.5 TR. SM/MES No 654/0004/PKG/07 654/0005/PKG/08 654/0006/PKG/09 654/0039/PKG-1/18 654/0040/PKG-2/18 654/0041/PKG-3/18
M&L for pumping down the gas of the Central AC plant of various capacities pressure testing the complete plant by dry nitrogen gas by separating high side and low side, rectifying the leakage by gas welding brazing pressure testing vaccuming the system , testing and commissioning complete.( NTS Teylerabad 36 TR).
Preparation of old painted surfaces and applying two coats of synthetic enamelled paint to external surfaces to compressor with motors - 03 No's, foundation of compressor & motor units- 03 No's, suction & discharge refrigerant pipe line, condenser water pump with motor & foundation - 02 No's, water pipe line, AHU unit and motor/blower- 01 No, condenser - 03 No's of any capacity of central AC plant. (INS Utkrosh / NTS Teylerabad)
Supply & fix replacement of MCCB 4-pole 250 Amps with breaking capacity 36 KA adjustable thermal magnetic setting Ios=100% of Icu all as specified and directed.
M & L for dismantling burnt out three phase, 50 C/S capacity 25 HP motor for rewinding with same guage, weight and same number of turns of super annealed copper wire including paper/tape of approved quality and varnishing with Class I varnishing compound including heating and re-assembling the motor, testing and commissioning after repair complete all as specified. 654/0025/CR-1/08 654/0026/CR-2/08 208345/15174
M&L for dismantling of Monoblock pump set up to 10 HP removing scales cleaning, heating varnishing of motor winding, servicing the pump sets by repalcing the worn out bushes, bearings, gland rope, gland bolts & nuts, painting Two coat etc and reassembling the complete pump set including testing and commissioning complete all as directed by Engineer - in - Charge.
S & F in replacement of pressure gauge of HP size 4" dia of rating 0 - 300 PSI all as specified .
S & F in replacement of water pressure gauge of 4 " dia of range 0 - 7 Kg /sqcm or 0 - 100 PSI all as specified
S & F replacement of pressure gauge of LP OP (low pressure /oil pressure) size 4" dia of rating -30 to 150 PSI all as specified
S & F in replacement of HP cut out Type MP - 5 suitable for R - 22 gas complete all as specified and as directed.
S & F in replacement of LP/HP combination cut out MP - 15 Suitable for R 22 gas complete with flare nut complete all as specified and as directed.
S & F in replacement of oil pressure control switch type MP - 55 suitable for R - 22 complete with flare nut complete all as specified and as directed.
S & F in replacement of solenoid pilot control valve type 10 with two / three coil assembly of same model all as specified. (INS Utkrosh & NTS Teylerbad, NAD Dollygunj)
Supply only synthetic refrigeration compressor oil suitable for 36TR compressor.
S&F in replacement of thermostatic expansion valve as per existing model capacity of 36 TR AC Plant all as specified
S&F in replacement of thermostatic expansion valve as per existing model capacity of 8.5 to 16 TR AC Plant all as specified
Supply only refrigeration gas R 421A in manufacturer sealed cylinder. Note:- (i) Gas to be supplied in manufacturer sealed container. (ii) Empty containers will be returned to contractor .
Supply only refrigeration gas R 32 in manufacturer sealed cylinder. Note:- (i) Gas to be supplied in manufacturer sealed container. (ii) Empty containers will be returned to contractor .
Supply only refrigeration gas R 407 in manufacturer sealed cylinder. Note:- (i) Gas to be supplied in manufacturer sealed container. (ii) Empty containers will be returned to contractor .
Supply only refrigeration gas R 410 in manufacturer sealed cylinder. Note:- (i) Gas to be supplied in manufacturer sealed container. (ii) Empty containers will be returned to contractor .
S&F in replacement of 6/10 mfd capacitor suitable for cooling fan motor of outdoor unit of package AC plant 5 TR capacity (INS Utkrosh).
S&F in replacement of 20 mfd capacitor suitable for cooling fan motor of outdoor unit of package AC plant 8.5 TR capacity
S&F in replacement of 20 mfd capacitor suitable for cooling fan motor of outdoor unit of package AC plant 10 TR capacity(INS Utkrosh)
S&F in replacement of condensor fan motor including blade1/5 HP single phase complete for 5 TR package AC plant .
S&F in replacement of condensor fan motor 1/5 HP single phase complete for 8.5 TR package AC plant complete all as specified and directed at site.
S&F in replacement of condensor fan motor 3/4 HP single phase complete for 10 TR package AC plant complete all as specified and directed at site.
S&F in replacement of condensor fan motor 3/4 HP single phase complete for 16 TR package AC plant complete all as specified and directed at site.
S&F in replacement of micro control with PCB complete for package AC unit 5 to 16 TR complete all as specified and directed at site.
Supply and fix replacement of threaded flanged joints suitable for 80/100mm bore GI pipe.
Supply and Fixing in replacement of Air cooled condensor out door type unit (without compressor) with tank and copper tubing for discharge line unit assembly including contactor capacitor suitable for capacity 5 TR all as specified and directed. Note: Out door unit shall be compatible and in sync with complressor dimensions. S&F fixing of compressor shall measured and paid separately
Supply and Fixing in replacement of Air cooled condensor out door type unit (without compressor) with tank and copper tubing for discharge line unit assembly including contactor capacitor suitable for capacity 5.5 TR all as specified and directed. Note: Out door unit shall be compatible and in sync with complressor dimensions. S&F fixing of compressor shall measured and paid separately
Supply and Fixing in replacement of Air cooled condensor out door type unit (without compressor) with tank and copper tubing for discharge line unit assembly including contactor capacitor suitable for capacity 8.5 TR all as specified and directed. Note: Out door unit shall be compatible and in sync with complressor dimensions. S&F fixing of compressor shall measured and paid separately
Supply & fix replacement of power contactor Make: MNX 45 of L&T or equivalent in Siemens, C&S Electric or Schneider Electric as approved by GE.
Supply & fix replacement of power contactor Make: L&T MNX 25 /Havells/Legrand/Crompton or equivalent as approved by GE
Supply & fix replacement of power contactor Make: MNX 18 of L&T or equivalent in Siemens, C&S Electric or Schneider Electric as approved by GE
Supply & fix of electronic type star delta starter fully automatic suitable for 10 HP water circulation motor. Make: L&T/Crompton/Siemens or equivalent as approved by GE all as specified & directed.(NTS Teylerabad)
Supply & fix in replacement of over load relay suitable for 36 TR compressor motor starter all as specified & directed.
Supply & fix in replacement of timer 36TR compressor motor starter all as specified & directed. Make : BCH
Supply & fix in replacement of drier core suitable for 36 TR Central AC plant,all as specified & directed.
Supply & fix in replacement of drier core suitable for 16 TR Central AC plant,all as specified & directed.
Supply & fix in replacement of drier core suitable for 10 TR Central AC plant,all as specified & directed.
Supply & fix in replacement of drier core suitable for 5 TR Central AC plant,all as specified & directed.
Supply & fixing in replacement spare parts for repairs of compressor as under:-
Main bearing seal end
Main bearing pump end
Connecting rod assembly
C R bearing
Cylinder Sleeve
Piston
Oil pressure release valve
Suction Valve reed
Oil filter assembly
Piston ring set
Aluminium washer set
Gudgeon Pin
Gudgeon pin Bush
Discharge valve assembly
Oil pump Assembly
Rocker for unloading mechanism
Piston Circlip
O' Ring set with tefelon set
Liner unloading Ring with Spring & Pin
Connecting rod nut & bolt
Retaining spring
Suction retaining plate
Safety valve
Gasket set complete
Discharge Service Valve
Suction Service Valve
Cylinder Liner
Unloader Sleeve
M & L Steel structural fabrication for support to pipe works fabricated from structural steel sections including nuts,cable trays,clamps bolts,washers, welding ,bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primary coat, one under coat and one finishing coat of paint complete all as specified and directed .
Supply and replace MCCB of capacity of 160 Amps, 4 pole 25 KA, 415 Volts with thermo magnetic release, adjustable type complete all as specified and directed.
Supply and replace MCCB of capacity of 100 Amps, 3 pole 16 KA, 415 Volts with thermo magnetic release, fixed type complete all as specified and directed.
Supply and replace MCCB of capacity of 63 Amps, 3 pole 16 KA, 415 Volts with thermo magnetic release, fixed type complete all as specified and directed.
M&L for earthing complete with galvanized steel earth plate electrode 600 mm x 600 mm x 6.0 mm thick buried directly in ground vertically to a depth not less than 2.25 meter deep below ground level with top edge earth plate at a depth not less than 1.5M below normal ground level connected to galvanized iron strip 25 X 4 mm (upto 7.5 metres) by means of bolts, nuts check nuts and washers of galvanized steel and connected to main switch board or main control board as directed and including provision of concrete pit in PCC (1:3:6) type C1, pre-cast RCC (1:2:4) type B1 cover slab 45 cm x 45 cm x 5 cm reinforced with 8 mm dia. TMT bars @ 150 mm centre to centre both ways, with one handle for lifting made out of 8 mm dia MS bar, provision of funnel, wire mesh, 20 mm bore galvanized steel tubing (Medium grade) for watering, charcoal or coke and salt in alternate layers, 40 mm bore galvanized steel tubing medium grade for protection of earth lead connection, necessary excavation and earth work in any type of soil and including necessary testing and dismantling of existing unsv earthing complete all as shown in Figure 15A of IS 3043 :1987, complete all as specified and directed.
M&L for dismantling of old ducting of any type and shape including all accessories viz. Corner, Cleat, Carriage bolt, Gasket etc. complete all as specified and directed.
Supply , assembly and erection of GI sheet with C & SS rectangular/square duct made out of 'L' shaped hollow profile, duly factory boxed, incl all accessories such as Corner, Cleat, Carriage bolt, Gasket and appropriate sealant on longitudinal joints etc complete of size 24 Gauge etc. and including providing duct insulation with resin bonded fibre glass wool roll of density 24 kg/Cum, with factory laminated aluminium vapour barrier, thickness of insulation with including following:- (a) M&L for cleaning the duct surface (to be insulated ) by scrapping carefully with wire brush etc. to make the surface completely free of millscale, dirt, dust, grease and other foreign materials, taking special care so that all duct joints are sealed against any leakage. (b) M&L for applying rubber based adhesive CPRX compound. (c) M & L for securing the insulation with and including mechanically fastened nylon/ steel straps of size 12 mm/50 mm at maximum intervals of 1.2 mtr. (d) M&L for sealing of all longitudinal joints and circular overlaps with and including Aluminium fol tape 50 m wide to make the insulation leak proof. complete all as specified and directed.
M&L for Dismantling, opening, rewinding and refixing of, 3 phase, 440V, 50 Hz induction motors capacity 12.5 with super enameled copper wire of existing gauge and existing class insulation including superior quality varnishing, heating / drying coils, making connections from coil to terminal box, spray painting with two coats of synthetic enamel paint, necessary mechanical works for shaft/bearing housing , renewal of DE and NDE bearings, transportation from installation to workshop & back including connecting testing and commissioning at site for satisfactorily operation as required etc. complete all as specified and directed.
Supply and installation in replacement of PN 1.6 manual butterfly valve of sizes 80 mm complete all as specified and directed.
Supply and installation in replacement of PN 1.6 manual Non return butterfly valve of sizes 80 mm complete all as specified and directed.
Supply and fixing in replacement of indoor Thermometer with Digital Hygrometer and Humidity gauge., The hygrometer shall be able to measures Humidity and temprature, records level to display highs and lows, magnatic backing for convinient placement and able to display temprature in both Celsius and Farenheit all as specified and directed. Make-Acu Rite 00325
S&F in replacement of GI pipe medium grade 80 mm diameter alongwith its fitting include, L bends, sockets etc FRP cooling, duly welding with existing condenser and FRP cooling tower, duly painted with one coat of red oxide and two coats of black paint with arrow marking painted on it, incoming and outgoing all as specified and directed
Supply and fixing in replacement of Psychrometer, it shall be able to measure -20C to 50C Humidity and temprature, including provn for fixing on wall complete all as specified and directed by Engr-in-Charge
Tropical Refrigeration
M/s Karbhagam Sales Agency
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .