Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Rejected-Technical | Rejected-Technical Documents are not as per nit |
| 4 | Rejected-Technical 16 B KURLA INDUSTRIAL ESTATE NEAR SEVA SADAN ROAD NARAYAN NAGAR GHATKOPAR W MUMBAI MAHARASHTRA 400086 | MUMBAI SUBURBAN | MAHARASHTRA | 400086 | Rejected-Technical Documents are not as per nit |
Tender Value
Refer Docs
EMD Value
₹28,453
Closing Date
5 Nov 2020, 3:00 pmClosed
SMESouth
sixth floor Technical wing Prabhadevi
SITC of Auotmatic Fire Alarm And FIRE Detection System at Byculla TE Building
2020_MTNL_593189_1
SM (E)/ South /NIT/20-21/20
Open Tender
Electrical Works
Works
90 days
Prabhadevi
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
Accounts Officer CASHBW MTNL Mumbai
₹28,453
12 Nov 2020
26 Oct 2020
6 Nov 2020
26 Oct 2020
5 Nov 2020
26 Oct 2020
26 Oct 2020 - 3 Nov 2020
Supplying, Installing, Testing & Commissioning of Multi criteria Photoelectric Type Smoke Detectors i/c basecomplete as per attached specifications.
Supplying, Installing, Testing & Commissioning of thermistor type dual action i.e. Rate of Rise cum fixedTemp. (60° C) Heat Detectors as per attached specifications i/c base complete as required.
Supplying, Installing, Testing and Commissioning of polarity insensitive twin LEDs Response Indicators withsuitable 16 Gauge MS Box/ ABS (Acrolo Nitrite Bitudine Styrene) box with die pressed anodized aluminium/ ABS (Acrolo Nitrite Bitudine Styrene) facia plate and LED mounted
Supplying, Installing, Testing and Commissioning of Manual Push Button Station with Hammer & Chain (Pill Box) in Aluminium Cast/ M.S box as per specifications
Supplying, Installing, Testing and Commissioning of polarity insensitive Electronic Hooter with speaker withranges of 25 to 30 Mts. with 3 Watt speakers as per specifications.
Supplying, Installing, Testing & Commissioning following zones microprocessor based Main Control Panel as per specifications suitable for wall/floor mounting, fabricated from16 SWG CRCA Sheet incorporating audio visual indications for each zone mains operated with 24 Volt sealed Maintenance Free rechargeable battery and battery charger complete as required as per specification attached. (Note: 4 nos. (2 NO & 2 NC) potential free points may be provided for extending infrastructure of fire detection alarm).
a)16 Zone Panel with PA system with battery of not less than 32 AH Capacity.
Providing & fixing following type of Fire Extinguisher with hose of suitable length including first charge/refilling & providing hook hose clamps etc with ISI mark on the Extinguisher
a) CO2 type (4.5 Kg) wall mounting type
Supplying & Fixing following size of PVC insulated PVC sheathed Copper Conductor FRLS Armoured Cable of 1.1KV grade on surface i/c clamping as required
a) 2 x 1.5 Sqmm Cable (FRLS)
Supplying & Making End Termination with Brass Compression Gland for PVC insulated PVC sheathed copper Conductor FRLS Armoured Cable of 1.1 KV complete as required.
a) 2 x 1.5 Sqmm Cable (FRLS)
Supply & Fixing of M.S. Box suitable for fixing of Detector Base complete as required.
Supplying, Installing, Testing and Commissioning of A/C cut off relay Box having a suitable size of MS box for incorporating one no. Toggle switch, connector, din channel and two nos. relays.
Supplying & Laying of 14 SWG(2.24mm) Copper Earthing Wire from LDB to Fire Panel.
Supplying, Installing, Testing and Commissioning of microprocessor based Local Control Panel as per specifications for following zones suitable for wall/floor mounted fabricated out of 16 SWG CRCA sheet audio visual indication for each zone without power supply module operated through main control panel.
a) 8 Zone
Supplying & Fixing laminated floor plans amounted on hard board showing areas covered by each zone along with control panel etc complete as required at site.
S/F of following size of multicore flexible copper conductor cable for extending infrastructure alarm on surface etc. i/c clamping & terminations as required.
a) 6 Core 1.5 Sqmm
b) 10 Core 1.5 Sqmm
Exit Sign Board Made out of 16 SWG CRCA Sheet Powder Coated Box housing electronic circuit with high intensity Red LED showing escape route by showing arrow, Operation in voltage 24 VDC of size 8" x 4"
dismantling of following existing old materials/ Equipments i/c shitting it at place shown by building authority and handed over the same to building incharge.
a) Detectors
b) Manual Call Points
c) Hooters
d) Response Indictors
e) Junction Boxes
f.) Exit Sign Boards
g.) AC Cut off Relay Box Unit
Dismantling of following zone existing old Main Fire Control panel i/c shitting it at place shown by building authority and handed over the same to building incharge.
a) 16 Zone and above
Dismantling of following zone existing old Local Fire Control panel i/c shitting it at place shown by building authority and handed over the same to building incharge. a) 8 Zone
Dismantling of following size existing old PVC insulated PVC sheathed armoured cable making coil and keep it at place decided by building authority and handed over to building incharge. a.) 2 x 1.5 Sq.mm Armoured Cable
Removing and Relaying existing old following size PVC insulated PVC Sheathed FRLS armoured cable i/c spacersand saddle complete as required. a.) 2 x 1.5 Sq.mm Armoured Cable
OASIS ENGINEERS
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .